What are the key safety precautions and warnings for the OMRON E5CC?

To ensure safe operation of the OMRON E5CC, please adhere to the following precautions:

WARNING: Minor electric shock, fire, or malfunction of the product may occasionally occur. Do not disassemble, modify or repair the product or touch any of the internal parts. Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable, unexpected operation may result in property damage or an accident.

CAUTION: Minor injury, fire, or malfunction of the product may occasionally occur. Please observe the following points:

• This product is designed for use in general industrial equipment. It must not be used in the applications listed below:

– Applications that have a serious impact on human life and property such as nuclear power control, railway facilities, aviation facilities, vehicles, combustion facilities, medical equipment, amusement facilities, and safety devices.

– However, for applications where the equipment requires safety devices or redundant circuits to prevent a serious impact when a problem occurs in the control system of the equipment, and for applications that require an industry-specific standards such as those from JISC, ensure that the safety devices or redundant circuits have been appropriately set up.

• This product is for indoor use only. Do not use this product in the following places:

– Places directly subject to heat from heating equipment.

– Places subject to splashing liquid or oil atmosphere.

– Places subject to direct sunlight.

– Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).

– Places subject to severe temperature changes.

– Places subject to icing and condensation.

– Places subject to vibration and large shocks.

• Use and store the product in a place where the ambient temperature and humidity are within the specified ranges.

• Do not block the vents on the product. Poor ventilation may cause fire.

• Be sure to wire the product correctly with the correct polarity of the terminals.

• Use crimp terminals of the specified size (M3.5, width of 7.2 mm or less).

• Do not connect anything to the unused terminals.

• Tighten the terminal screws to the tightening torque recommended in the instruction manual.

• Be sure to set the protection settings on the product to protect the system. OMRON will not be held responsible for any damage arising from insufficient protection settings.

• Before you use the product, allow for a 30-minute warm-up time after the power is turned ON. This is required for the correct temperature to be displayed.

• Do not use thinner or similar chemicals to clean the product. Use commercial alcohol.

• Separate the product from devices that generate high frequencies (such as high-frequency welders and high-frequency sewing machines) and devices that generate surges.

• When disposing of this product, treat it as industrial waste.


What are the precautions for safe and correct use of the OMRON E5CC?

Precautions for Safe Use:

• Always use the specified power supply voltage. Failure to do so may result in malfunction or fire.

• Ensure that the rated voltage is reached within two seconds of turning ON the power. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur.

• Do not touch the terminals while power is on to avoid electric shock.

• Do not allow metal particles, wire clippings, or fine metallic shavings or filings to enter the product, as this may result in malfunction, fire, or electric shock.

• Do not attempt to disassemble, modify, or repair the product.

• Install the product where the following conditions are met:

– Ambient temperature: -10 to 55°C (with no icing or condensation)

– Ambient humidity: 25% to 85%

– Altitude of 2,000 m or less.

– Recommended indoor panel installation.

– No corrosive or flammable gases.

– Away from water, oil, chemicals, direct sunlight, dust, salt, iron powder, vibration, or shock.

• Use and store the product within the specified temperature and humidity ranges.

• The life of output relays depends on switching conditions. Consider the actual application and use the product within the rated load and electrical life.

Precautions for Correct Use:

• Handle the product carefully to avoid damage from dropping or shock.

• Do not touch the display or keys with hard or sharp objects.

• Use specified crimp terminals (M3.5, width of 7.2 mm or less) for wiring.

• Keep wiring away from power cables carrying high voltages or large currents to prevent induction and noise.

• Use the product within the rated load and power supply.

• Allow a 30-minute warm-up period for accurate temperature display.

• A switch or circuit breaker must be installed to allow the operator to immediately turn OFF the power. It should be located within easy reach and marked as a disconnecting device.

• The unit may be damaged if the voltage output from the SSR drive output terminals is short-circuited.

• When setting the “Input type” parameter, refer to the “Input type” table in the PDF to ensure settings are correct, as incorrect settings will cause measurement errors.

• Use a single OMRON E5CC unit per power supply circuit for CT connection. If multiple units are used, errors will occur in the measured current values.


What are the installation dimensions and mounting instructions for the OMRON E5CC?

Dimensions:

• The overall dimensions of the OMRON E5CC are 48 x 48 mm (front) and 60 mm (depth).

Panel Cutout:

• The panel cutout size should be 45 x 45 mm.

• The recommended panel thickness is 1 to 5 mm.

Installation Mounting Methods:

Individual Mounting:

1. Insert the OMRON E5CC into the mounting hole in the panel.

2. Push the adapter in from the terminals on the rear until the adapter contacts the panel and is temporarily secured.

3. Tighten the two mounting screws on the adapter. Alternate between the top and bottom screws, tightening them a little at a time to keep them at the same tightness.

Side-by-side Mounting:

1. Insert the OMRON E5CC controllers into the mounting holes in the panel.

2. Insert adapters on the Digital Controllers.

3. Insert a watertight packing if waterproofing is required. The OMRON E5CC is not waterproof if mounted side-by-side without watertight packing.

To maintain a waterproof construction, insert the watertight packing onto the OMRON E5CC. When multiple units are mounted, the waterproof construction is lost.


How do I wire the different models of the OMRON E5CC?

The wiring for the OMRON E5CC depends on the specific model. Use M3.5 crimp terminals with a width of 7.2 mm or less. The terminal arrangement is shown below for different models. Always ensure power is OFF before wiring.

E5CC-QX/RX (Plug-in models):

• Terminals 1, 2: TC/Pt/Analog current/Analog voltage input.

• Terminal 3: Not used.

• Terminals 4, 5: Not used.

• Terminal 6: Control output 1 (Relay output for RX, Voltage output for QX).

• Terminal 7: Control output 1 (Relay output for RX, Voltage output for QX).

• Terminal 8: Not used.

• Terminals 9, 10: Not used.

• Terminals 11, 12: Power supply (100 to 240 VAC or 24 VAC/DC).

E5CC-QX2/RX2 ASM/DSM-800:

• Terminals 1, 2: TC/Pt/Analog current/Analog voltage input.

• Terminal 3: Not used.

• Terminals 4, 5: HB alarm/HS alarm input (CT1).

• Terminal 6: Auxiliary output 2.

• Terminal 7: Auxiliary output 2.

• Terminal 8: Auxiliary output 1.

• Terminal 9: Auxiliary output 1.

• Terminal 10: Control output 1 (Relay output for RX2, Voltage output for QX2).

• Terminal 11: Control output 1.

• Terminals 12, 13: Power supply (100 to 240 VAC or 24 VAC/DC).

E5CC-CX2/UX2 ASM/DSM-800 (Screw terminal models):

• Terminals 1, 2: Power supply (100 to 240 VAC or 24 VAC/DC).

• Terminal 3: Control output 1 (Linear current for CX2, Voltage for UX2).

• Terminal 4: Control output 1.

• Terminal 5: Auxiliary output 1.

• Terminal 6: Auxiliary output 1.

• Terminal 7: Auxiliary output 2.

• Terminal 8: Auxiliary output 2.

• Terminals 9, 10: HB alarm/HS alarm input (CT1).

• Terminal 11: Not used.

• Terminals 12, 13, 14: TC/Pt/Analog current/Analog voltage input.

Note: For analog current input, connect a 250 Ω resistor (model ES2-HB/U) between the B and – input terminals.


What are the functions of the keys and indicators on the front panel of the OMRON E5CC?

The front panel of the OMRON E5CC consists of a display and several indicators and keys:

Displays:

No. 1 Display (PV): Shows the process value (PV) or a parameter name. It is displayed in white.

No. 2 Display (SV): Shows the set point (SV), a manipulated variable, or a parameter setting. It is displayed in green.

Indicators:

(1) Control output 1 indicator (OUT1): Lit while the control output 1 is ON.

(2) Auxiliary output 1 indicator (AUX1): Lit while auxiliary output 1 is ON.

(3) Auxiliary output 2 indicator (AUX2): Lit while auxiliary output 2 is ON.

(4) STOP indicator (STOP): Lit while control is stopped.

(5) CMW indicator: Not used on this model.

Keys:

(6) Level key: Press for less than 1 second to switch between levels. Press for 1 second or more to move from the Operation Level to the Adjustment Level. Press for 3 seconds or more to move from the Operation Level to the Initial Setting Level.

(7) Mode key: Changes the parameter within a level.

(8) Down key: Decreases the setting.

(9) Up key: Increases the setting.


How do I navigate the different menu levels on the OMRON E5CC?

The OMRON E5CC has several operational levels. Here is how to navigate between them:

Power ON: When the power is turned on, the OMRON E5CC starts in the Operation Level. This is the default level for monitoring the process value (PV) and set point (SV).

Operation Level:

– Use the Up and Down keys to change the set point (SV).

– Press the Mode key to cycle through other parameters in this level, such as the alarm value.

To move to the Adjustment Level:

– From the Operation Level, press and hold the Level key for at least 1 second.

To move to the Initial Setting Level:

– From the Operation Level, press and hold the Level key for at least 3 seconds.

Note: You cannot move to the Initial Setting Level if control is running (STOP indicator is OFF). First, stop the operation by changing the “Run/Stop” parameter to “STOP”.

To move to the Protect Level:

– From the Initial Setting Level, press the Mode key to navigate to the “Protect Level” parameter. Then use the Level key to enter it.

– Alternatively, in any level, press and hold the Level and Mode keys at the same time for 1 second to move directly to the Protect Level.

To return to the Operation Level:

– From any other level, press and hold the Level key for at least 1 second to return to the Operation Level.


What are the available input types and their setting ranges for the OMRON E5CC?

The OMRON E5CC supports various sensor inputs. The input type must be set in the Initial Setting Level. The available types and ranges are listed below:

Input Type Setting Range (°C) Setting Range (°F) Default
Thermocouple K -200 to 1300 -300 to 2300 K
Thermocouple J -200 to 1200 -300 to 2100
Thermocouple T -200 to 400 -300 to 700
Thermocouple E -200 to 800 -300 to 1400
Thermocouple L -200 to 850 -300 to 1500
Thermocouple U -200 to 400 -300 to 700
Thermocouple N -200 to 1300 -300 to 2300
Thermocouple R 0 to 1700 0 to 3000
Thermocouple S 0 to 1700 0 to 3000
Thermocouple B 100 to 1800 200 to 3200
Thermocouple W 0 to 2300 0 to 4100
Thermocouple PL II 0 to 1300 0 to 2300
Platinum resistance thermometer Pt100 -200 to 850 -300 to 1500
Platinum resistance thermometer JPt100 -200 to 500 -300 to 900
Non-contact temperature sensor Setting Range
10 to 70°C Displayed as 10.0 to 70.0
60 to 120°C Displayed as 60.0 to 120.0
115 to 165°C Displayed as 115.0 to 165.0
140 to 260°C Displayed as 140.0 to 260.0
Analog input Setting Range
Current 4 to 20 mA -1999 to 9999
Current 0 to 20 mA -1999 to 9999
Voltage 1 to 5 V -1999 to 9999
Voltage 0 to 5 V -1999 to 9999
Voltage 0 to 10 V -1999 to 9999

Note: The default sensor type is Thermocouple K. The display unit (°C/°F) is also set in the Initial Setting Level.


How do I perform a parameter initialization (factory reset) on the OMRON E5CC?

You can initialize the parameters of the OMRON E5CC to their default factory settings. This action is performed from the Protect Level.

1. Press and hold the Level and Mode keys at the same time for at least 1 second to move to the Protect Level.

2. Press the Mode key until the “Initialize” parameter is displayed.

3. Use the Up or Down key to change the setting to “ON”.

4. To execute the initialization, either press the Level and Mode keys at the same time for 1 second, or turn the power OFF and then ON again.

This will reset all parameters in the Initial Setting, Adjustment, and Protect Levels to their default values.


What are the different alarm types available on the OMRON E5CC?

The OMRON E5CC provides various alarm types that can be assigned to the auxiliary outputs. The alarm type is selected in the Initial Setting Level.

No. Alarm Type Alarm Type Setting Operation
0 Alarm function OFF (no function) No alarm is output.
1 Upper/lower limit H/L The alarm is ON when PV is outside the range defined by Alarm value lower limit and Alarm value upper limit.
2 Upper limit H The alarm is ON when PV is greater than the alarm value (set point + upper-limit alarm value). (Default)
3 Lower limit L The alarm is ON when PV is less than the alarm value (set point – lower-limit alarm value).
4 Upper/lower limit range H/L range The alarm is ON when PV is within the range of Alarm value lower limit and Alarm value upper limit.
5 Upper/lower limit with standby sequence H/L Stby Same as Upper/lower limit, but alarm is suppressed until PV enters the non-alarm range for the first time.
6 Upper limit with standby sequence H Stby Same as Upper limit, but alarm is suppressed until PV enters the non-alarm range for the first time.
7 Lower limit with standby sequence L Stby Same as Lower limit, but alarm is suppressed until PV enters the non-alarm range for the first time.
8 Absolute value upper limit Abs H The alarm is ON when PV is greater than the alarm value.
9 Absolute value lower limit Abs L The alarm is ON when PV is less than the alarm value.
10 Absolute value upper limit with standby sequence Abs H Stby Same as Absolute value upper limit, but alarm is suppressed until PV enters the non-alarm range for the first time.
11 Absolute value lower limit with standby sequence Abs L Stby Same as Absolute value lower limit, but alarm is suppressed until PV enters the non-alarm range for the first time.
12 Loop Break Alarm (LBA) LBA The alarm is ON if the control loop is broken (e.g., sensor break, heater break).
13 PV change rate alarm PV rate The alarm is ON if the change rate of the process value is greater than the set value.
14 Heater burnout alarm (HB) HB The alarm is ON when the heater burns out. Requires a CT input.
15 SSR failure alarm (HS) HS The alarm is ON when the SSR fails (short-circuited). Requires a CT input.

Note: Alarm values are set in the Operation Level or Adjustment Level. The default alarm type is “Upper limit” (No. 2).


How do I troubleshoot error displays on the OMRON E5CC?

When an error occurs on the OMRON E5CC, the display will show an error code. The following table explains the error codes and the necessary actions to resolve them.

Error Display Error Name Description and Action
E111 Input value over The process value exceeded the displayable range (-1999 to 9999). Check the sensor and the input setting.
S.ERR Sensor input error The input is disconnected or short-circuited. The control output turns OFF. Check the sensor wiring and connection.
E333 A/D converter error The A/D converter has failed. The control output turns OFF. Replace the OMRON E5CC unit.
E555 Memory error The built-in memory has failed. The control output turns OFF. Perform initialization of settings. If the status does not change, the OMRON E5CC unit may need to be replaced. Check for strong noise sources.

If the display shows all OFF, it indicates a power supply error or that the OMRON E5CC has failed. Check the power supply voltage, wiring, and terminal connections.


What are the technical specifications of the OMRON E5CC?

Power supply voltage: 100 to 240 VAC, 50/60 Hz; or 24 VAC, 50/60 Hz; 24 VDC

Operating voltage range: 85% to 110% of rated supply voltage

Power consumption: 6.5 VA max. (100 to 240 VAC), 4.0 VA max. (24 VAC), 2.5 W max. (24 VDC)

Sensor Input:

– Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PL II

– Platinum resistance thermometer: Pt100, JPt100

– Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C

– Analog input: Current 4 to 20mA, 0 to 20mA; Voltage 1 to 5V, 0 to 5V, 0 to 10V

Input impedance: Current input: 150 Ω max., Voltage input: 1 MΩ min.

Control method: ON/OFF control or 2-PID control (with auto-tuning)

Control Output:

– Relay output: SPST-NO, 250 VAC, 3 A (resistive load)

– Voltage output (for driving SSR): 12 VDC ±20% (PNP), max. load current: 21 mA

– Linear current output: 4 to 20 mA DC / 0 to 20 mA DC, load 600 Ω max.

– Linear voltage output: 1 to 5 VDC / 0 to 5 VDC / 0 to 10 VDC, load 1 kΩ min.

Auxiliary output: 2 outputs, SPST-NO relay, 250 VAC, 2 A (resistive load)

Setting method: Digital setting using front panel keys

Indication method: 11-segment digital display and individual indicators. PV: White, SV: Green.

Ambient operating temperature: -10 to 55°C (with no icing or condensation)

Ambient operating humidity: 25% to 85%

Storage temperature: -25 to 65°C (with no icing or condensation)

Memory protection: Non-volatile memory (number of writes: 100,000 times)

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER