Free English MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.
CLICK HERE TO DOWNLOAD MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What are the key safety warnings for the MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
To ensure safe operation of your MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2, please adhere to the following warnings:
• The unit must not be installed by the user. Ask the dealer or an authorized company to install the unit. If the unit is installed improperly, water leakage, electric shock or fire may result.
• Do not stand on, or place any items on the unit.
• Do not splash water over the unit and do not touch the unit with wet hands. An electric shock may result.
• Do not spray combustible gas close to the unit. Fire may result.
• Do not place a gas heater or any other open-flame appliance where it will be exposed to the air discharged from the unit. Incomplete combustion may result.
• Do not remove the front panel or the fan guard from the outdoor unit when it is running.
• Never repair the unit or transfer it to another site by yourself.
• When you notice exceptionally abnormal noise or vibration, stop operation, turn off the power switch, and contact your dealer.
• Never insert fingers, sticks etc. into the intakes or outlets.
• If you detect odd smells, stop using the unit, turn off the power switch and consult your dealer. Otherwise, a breakdown, electric shock or fire may result.
• This air conditioner is NOT intended for use by children or infirm persons without supervision.
• Young children must be supervised to ensure that they do not play with the air conditioner.
• If the refrigeration gas blows out or leaks, stop the operation of the air conditioner, thoroughly ventilate the room, and contact your dealer.
• When installing or relocating, or servicing the air conditioner, use only the specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines. If air is mixed with the refrigerant, it can cause abnormal high pressure in the refrigerant line, resulting in an explosion and other hazards. Using any other refrigerant will cause mechanical failure or system malfunction.
What safety cautions should I observe when using the MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
To prevent damage to your MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2, please follow these cautions:
• Do not use any sharp object to push the buttons, as this may damage the remote controller.
• Never block or cover the indoor or outdoor unit’s intakes or outlets.
• Never wipe the remote controller with benzene, thinner, chemical rags, etc.
• Do not operate the unit for a long time in high humidity (80% RH or more), e.g., leaving a door or window open. In the cooling mode, water may condense and drop, potentially wetting or damaging furniture.
• Do not touch the upper air outlet vane or the lower air outlet damper during operation. Otherwise, condensation may form and the unit may stop operating.
What are the main components of the MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 indoor unit and remote controller?
The MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 indoor unit and remote controller consist of the following parts:
Indoor Unit:
• Air outlet: Where conditioned air is discharged.
• Vane: Directs the vertical airflow.
• Air intake: Where room air enters the unit.
• Filter: A long-life filter that requires cleaning indication after 2,500 hours.
The unit has 4 fan steps and an Auto with swing vane function.
Simple MA Remote Controller:
• ON/OFF lamp: Lights up in green when turned on, and blinks during startup and when an error occurs.
• ON/OFF button: Starts and stops the operation.
• Backlit LCD: Displays the current settings and status.
• TEMP. button (▲/▼): Adjusts the preset temperature.
• FAN button: Changes the fan speed.
• MODE button: Selects the operation mode (COOL, DRYING, FAN, etc.).
• VANE button: Adjusts the vane direction.
What do the icons on the remote controller display of my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 mean?
The icons on the remote controller display for the MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 indicate the following:
• CENTRAL icon: Appears when a local operation (ON/OFF, mode, temperature, fan speed, vane) is prohibited by a central controller.
• CHECK icon: Appears when an error occurs. The power indicator will blink, and the unit address (three digits) and error code (four digits) will be displayed.
• Energy-save icon (leaf symbol): Appears while the unit is in energy-save mode.
• Lock icon (key symbol): Appears when the Operation lock setting is active.
• Function Setup icon (F): Appears when indoor unit functions are being set up.
• Power-on icon (plug symbol): Appears when the power is on.
• Fan speed icon: Shows the selected fan speed.
• Vane icon: Shows the selected vane position.
• Operation modes: Displays the current mode (AUTO, COOL, HEAT, FAN, DRYING, VENTI, SETBACK).
• Temperatures: Shows indoor temperature and preset temperature(s). In AUTO (dual set point) or SETBACK modes, it displays both cooling and heating preset temperatures.
How do I select an operation mode on my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
To change the operation mode on your MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2, press the MODE button. This will cycle through the available modes in the following order:
COOL → DRYING → FAN → AUTO → SETBACK → HEAT
Note that not all functions are available on all models of indoor units. Functions that are not available will not appear on the display.
How does the AUTO (dual set point) mode work on my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
In AUTO (dual set point) mode on the MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2, you can set separate preset temperatures for cooling and heating. The unit will then automatically switch between cooling and heating operations depending on the room temperature to maintain the desired comfort level. The preset temperatures set in this mode will also be applied to the COOL/DRYING and HEAT modes respectively.
What is SETBACK mode on my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
The SETBACK function on your MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 automatically switches the operation mode between cooling and heating to maintain the room temperature within a specified range. The preset temperatures for cooling and heating in SETBACK mode can be set independently from the temperatures in other modes.
How do I set the temperature on my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
The method for setting the temperature depends on the selected operation mode:
In COOL, DRYING, HEAT, and AUTO (single set point) modes:
• Press the TEMP. ▲ button to increase the preset temperature.
• Press the TEMP. ▼ button to decrease the preset temperature.
In AUTO (dual set point) and SETBACK modes:
1. Press the TEMP. ▲ or TEMP. ▼ button. The preset temperature display (both cooling and heating) will start blinking.
2. While blinking, pressing TEMP. ▲ increases both temperatures, and TEMP. ▼ decreases both.
3. To set the cooling and heating temperatures individually, press the MODE button. Only the cooling preset temperature will blink.
4. Use the TEMP. ▲/▼ buttons to adjust the cooling preset temperature.
5. Press the MODE button again. Now, only the heating preset temperature will blink.
6. Use the TEMP. ▲/▼ buttons to adjust the heating preset temperature.
7. Press the MODE button a final time to complete the setting.
If no button is touched for a certain period during the setting process, the setting will automatically be confirmed and the display will stop blinking.
What is the preset temperature range for each mode on the MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
The available preset temperature ranges for your MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 are as follows:
| Operation mode | Preset temperature range |
|---|---|
| COOL/DRYING | 67 – 87 (95)°F / 19 – 30 (35)°C |
| HEAT | 63 (40) – 83°F / 17 (5) – 28°C |
| AUTO (single set point) | 67 – 83°F / 19 – 28°C |
| AUTO (dual set point) | [COOL] Preset temperature range for COOL mode. [HEAT] Preset temperature range for HEAT mode. |
| SETBACK | [COOL] Preset temperature range for COOL mode. [HEAT] Preset temperature range for HEAT mode. |
| FAN, VENTI. | Unsettable |
For AUTO (dual set point) and SETBACK modes, the cooling preset temperature must be greater than the heating preset temperature, and the difference between them must be equal to or greater than the minimum temperature difference required by the indoor unit model.
How do I adjust the fan speed on my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
Pressing the FAN button will change the fan speed. You can cycle through the available speeds, which may include several manual speeds and an AUTO setting. The specific number of settable fan speeds varies depending on the indoor unit model. If the unit does not have a fan setting function, the fan icon will blink when the FAN button is pressed, and the speed cannot be changed.
How do I adjust the vane direction on my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
Pressing the VANE button will switch the vane directions. You can cycle through several fixed positions (e.g., Setting 1, 2, 3, 4, 5), an AUTO setting, and a Swing setting. The available vane directions depend on the indoor unit model. If the unit does not have a vane function, the vane icon will blink when the VANE button is pressed, and the direction cannot be changed.
How can I restrict the temperature range on my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
You can restrict the preset temperature range for each operation mode by following these steps:
1. Press the ON/OFF button to stop the air conditioning unit.
2. Press and hold the FAN button for three seconds or longer. The temperature range restriction setting display will appear.
3. Press the MODE button to select one of the following options:
• A. No temperature range restriction.
• B. Temperature range restriction for COOL/DRYING mode.
• C. Temperature range restriction for HEAT mode.
• D. Temperature range restriction for AUTO (single set point) mode.
4. After selecting B, C, or D, press the FAN button to switch between setting the upper limit (Hi) and the lower limit (Lo).
5. Press the TEMP. ▲ or TEMP. ▼ button to set the desired upper or lower limit value.
6. Press and hold the FAN button for three seconds or longer to complete and save the setting.
After the restriction is set, if a user tries to select a temperature outside of the allowed range, the preset temperature display will blink.
What are the safety precautions for cleaning my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
Before cleaning your MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2, please observe these precautions:
• Before you start cleaning, stop the operation and turn OFF the power supply.
• Ask authorized people to clean the filter.
• When removing the filter, protect your eyes from dust. If you need to use a stool, be careful not to fall.
• When the filter is removed, do not touch the metallic parts inside the indoor unit to avoid injury.
• Do not dry the filters in direct sunlight or with a heat source like an electric heater, as this may warp them.
• Do not wash the filters in hot water (above 50°C, 122°F), as this may warp them.
• Always ensure the air filters are installed. Operating the unit without filters can cause malfunction.
How do I clean the filters on my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
To clean the filters of your MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2:
• Clean the filters using a vacuum cleaner.
• If you do not have a vacuum cleaner, tap the filters against a solid object to knock off dirt and dust.
• If the filters are especially dirty, wash them in lukewarm water. Rinse off any detergent thoroughly.
• Allow the filters to dry completely before putting them back into the unit.
How do I remove the filter from my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
To remove the filter for cleaning on the PLFY-P-NBMU-E2 Series:
1. Pull the knob on the intake grille in the direction indicated by the arrow to open it.
2. Open the intake grille.
3. Release the knob on the center edge of the intake grille and pull the filter forward to remove it.
What should I do if my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 is not heating or cooling well?
If your MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 is not heating or cooling effectively, check the following as the unit is likely operating normally:
• Clean the filter. Airflow is reduced when the filter is dirty or clogged.
• Check the temperature adjustment and set it to your desired temperature.
• Ensure adequate space around the outdoor unit. Check if the indoor unit’s air intake or outlet is blocked.
• Check for open doors or windows, which can affect performance.
Why doesn’t warm air blow from the indoor unit immediately when starting heating operation on my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
This is normal operation. Warm air will not blow until the indoor unit has sufficiently warmed up. This prevents cold drafts.
Why does my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 stop during heating mode before the set temperature is reached?
This is normal. When the outdoor temperature is low and the humidity is high, frost may form on the outdoor unit. If this happens, the unit performs a defrosting operation to remove the frost, temporarily stopping the heating. Normal operation should resume after approximately 10 minutes.
Why does the airflow direction change during operation or why can’t it be set on my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
The unit may automatically adjust the airflow direction under certain conditions. This is normal operation.
• During cooling mode: The vanes automatically move to the horizontal position after 1 hour if a downward airflow direction was selected. This is to prevent water from condensing on and dripping from the vanes.
• During heating mode: The vanes automatically move to the horizontal airflow direction if the airflow temperature is low or during a defrosting cycle.
Why do I hear a flowing water or hissing sound from my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
These sounds are normal and can be heard when refrigerant is flowing within the air conditioner or when the refrigerant flow is changing.
Why do I hear a cracking or creaking sound from my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
These sounds are normal and can be heard when parts rub against each other due to expansion and contraction caused by temperature changes.
Why does my room have an unpleasant odor when using the MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
This can be normal. The indoor unit draws in air that contains odors from walls, carpeting, furniture, and clothing, and then blows this air back into the room.
Why is a white mist or vapor being emitted from the indoor unit of my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
This is a normal occurrence under certain conditions:
• If the indoor temperature and humidity are high, this may happen when the cooling operation starts.
• During defrosting mode, cool airflow may blow down and appear like a mist.
Why is water or vapor being emitted from the outdoor unit of my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
This is normal operation and can be due to several reasons:
• During cooling mode, water may form and drip from the cool pipes and joints.
• During heating mode, water may form and drip from the heat exchanger.
• During defrosting mode, water on the heat exchanger evaporates, and water vapor may be emitted.
What should I do if the operation indicator does not appear on the remote controller display for my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
Try turning on the power switch. The power-on icon (“plug” symbol) should appear in the remote controller display. If the power switch is already on, check the power supply to the unit.
What does it mean when “(CENTRAL)” appears on the remote controller display of my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
When “(CENTRAL)” appears on the display, it means the unit is under central control. In this state, the air conditioner operation cannot be started or stopped using the local remote controller.
Why won’t my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 restart immediately after being stopped?
This is a protective feature. The operation has stopped to protect the air conditioner’s components. Please wait approximately three minutes, and it should be able to restart.
Why does my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 operate or stop without the ON/OFF button being pressed?
This can be normal if the unit is connected to a central controller or if the auto-recovery feature after a power failure has been set.
• If the unit is connected to a central remote controller, consult the people who control the air conditioner.
• Check if “(CENTRAL)” appears on the remote controller display.
• If the auto recovery feature from power failures has been set, the unit may start automatically. Press the ON/OFF button to stop operation if desired.
What does ‘HO’ mean when it appears on the remote controller display of my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
When “HO” appears, it indicates that the initial settings are being performed. This is normal. Please wait approximately 3 minutes for the process to complete.
What should I do if an error code appears on the remote controller display of my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
An error code indicates that the protection devices have operated to protect the air conditioner. Do not attempt to repair the equipment yourself. Turn off the power switch immediately and consult your dealer. Be sure to provide the dealer with the model name and the information (error code) that appeared on the remote controller display.
Why do I hear a draining water or motor rotation sound from my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
This is normal. When the cooling operation stops, the drain pump operates to remove condensed water and then stops. The process takes approximately 3 minutes.
Why is the noise from my MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 louder than the specifications?
The specified noise level is measured in an echo-free (anechoic) room. The actual indoor operation sound level is affected by the acoustics of the room where it is installed and will likely be higher than the noise specification. The table below shows typical noise level increases based on room type.
| High sound absorbing rooms | Normal rooms | Low sound absorbing rooms | |
|---|---|---|---|
| Location examples | Broadcasting studio, music room, etc. | Reception room, hotel lobby, etc. | Office, hotel room |
| Noise levels | 3 to 7 dB | 6 to 10 dB | 9 to 13 dB |
What is the recommended range of application for the MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2?
Using the MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 outside of the specified working temperatures and humidity can result in serious failure. The recommended operating ranges are:
| Mode | Indoor unit | Outdoor unit | ||
|---|---|---|---|---|
| PUHY | PURY | PUMY | ||
| Cooling | 15 °C – 24 °C, 59 °F – 75 °F WB | -5 °C – 46 °C, 23 °F – 115 °F DB | -5 °C – 46 °C, 23 °F – 115 °F DB | -5 °C – 46 °C, 23 °F – 115 °F DB |
| Heating | 15 °C – 27 °C, 59 °F – 81 °F DB | -20 °C – 15.5 °C, -4 °F – 60 °F WB | -20 °C – 15.5 °C, 10 °F – 60 °F WB | -18 °C – 15.5 °C, 0 °F – 60 °F WB |
Note: For applicable humidity, it is recommended to use the unit within a range of 30 – 80% relative humidity for both indoors and outdoors.
What are the technical specifications for the MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 series?
| Model | PLFY-P30NBMU-E2 | |
| Power source | Single 208/230 V 60 Hz | |
| Capacity | Cooling <BTU/h> | 30,000 |
| Heating <BTU/h> | 34,000 | |
| Dimension | Height <inch> | 11-3/4 (1-3/8) |
| Width <inch> | 33-1/16 (37-3/8) | |
| Depth <inch> | 33-1/16 (37-3/8) | |
| Net weight | <lbs> | 60 (13) |
| Fan Airflow range (Low – Middle1 – Middle2 – High) | DRY <CFM> | 810-740-640-560 |
| WET <CFM> | 780-710-600-530 | |
| Noise level (Low – Middle2 – Middle1 – High) | <dB> | 28-32-35-37 |
Note:
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB, 81 °F DB/19 °C WB, 66 °F WB, Outdoor 35 °C DB, 95 °F DB
Heating: Indoor 20 °C DB, 68 °F DB, Outdoor 7 °C DB, 45 °F DB/6 °C WB, 43 °F WB
*2 This figure ( ) indicates panel’s.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
CLICK HERE TO DOWNLOAD MITSUBISHI ELECTRIC CITY MULTI PLFY-P30NBMU-E2 (01) PDF DOCUMENT