Free English MGC MIX-4042 (01) PDF Document. Free English MGC MIX-4042 (01) PDF User Guide. Free English MGC MIX-4042 (01) PDF User Manual. Free English MGC MIX-4042 (01) PDF Owner Guide. Free English MGC MIX-4042 (01) PDF Owner Manual. Free English MGC MIX-4042 (01) PDF Reference Guide. Free English MGC MIX-4042 (01) PDF Instruction Guide. Free English MGC MIX-4042 (01) PDF Reference Manual. Free English MGC MIX-4042 (01) PDF Instruction Manual. Free English MGC MIX-4042 (01) PDF Operating Instructions.


CLICK HERE TO DOWNLOAD MGC MIX-4042 (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

What is the purpose of the MGC MIX-4042 Analog Interface module?

The MGC MIX-4042 Analog Interface module is designed to operate with a listed compatible intelligent fire system control panel. It can be configured to work with conventional two-wire or 4-20mA devices. The module monitors the current used by the connected devices and reports alarms and troubles accordingly.


What precautions must be taken before installing the MGC MIX-4042?

You must disconnect power from the system before installing the MGC MIX-4042 module. If the unit is being installed in a system that is currently operational, it is necessary to inform the operator and the local authority that the system will be temporarily out of service.


How do I mount the MGC MIX-4042 module?

The MGC MIX-4042 module is intended to be mounted in a standard 4″ square back-box. The box must have a minimum depth of 2 1/8 inches. Surface mounted electrical boxes (BB-400) are also available.


What are the steps for wiring and installing the MGC MIX-4042?

Note: This device should be installed as per applicable requirements of the authorities having jurisdiction and connected to power-limited circuits only.

1. Install the module wiring as indicated by the job drawings and appropriate wiring diagrams.

2. Use the MIX-4090 programmer tool to set the address on the module as indicated on the job drawings.

3. Mount the module in the electrical box.

Note: Any external power source used shall be Listed for use in a fire alarm system and must have ground fault detection capability.


How is the operational mode of the MGC MIX-4042 configured?

The operational mode of the MGC MIX-4042 is set through the panel configuration tool. This tool also allows for setting other parameters, such as the reset time for conventional devices or alarm levels for 4-20mA operation.


How does the MGC MIX-4042 handle Class A and Class B wiring for conventional devices?

When set for conventional devices, the MGC MIX-4042 module will automatically handle Class A or Class B lines. The module has an internal EOL (End-of-Line) resistor for Class A lines. For Class B wiring, an MP-300 end-of-line resistor must be used.


What does the LED indicator on the MGC MIX-4042 signify?

The module has a panel-controlled LED indicator. It will blink during normal standby operation and will be steady ON when the device has detected an off-normal condition.


What information is needed when using the MGC MIX-4042 with alarm verification?

When using the MGC MIX-4042 as a conventional Zone module with alarm verification, the FACP panel door label must be completed with the relevant delay information. The Control Unit Alarm Delay is 25 seconds for the MGC MIX-4042. The specific delay for smoke detectors can be found in the installation instructions supplied with those devices. You must enter the detector data in the following table on the FACP panel door label:

Circuit (Zone)
(MIX-4042 Zone #)
Control Unit Delay
Seconds
Smoke Detector
Model
(MFG + Model)
Delay, Seconds (1)
(Device delay)
25

What are the technical specifications for the MGC MIX-4042?

SLC SIDE

Normal Operating Voltage: 15 to 30VDC

Alarm Current: 3mA

Standby Current: 1.6mA

DEVICES SIDE

EOL Resistance (conventional zone): 3900 Ohms

Max Wiring Resistance (4-20mA): 200 Ohms

Max Wire Resistance (conventional zone): 100 Ohms total

External Power Supply: 24VDC nominal (18 to 30 V)

External Supply Current: 23mA maximum at 30 VDC (E.O.L. only)

EOL Current (conventional Only): 5mA maximum

Connected devices current: 3mA total or less

Max Short Circuit Current: 70mA (55mA on devices line)

GENERAL

Temperature Range: 32F to 120F (0C to 49C)

Humidity: 10% to 93% Non-condensing

Dimensions: 4 5/8″H x 4 1/4″ W x 1 1/8″ D

Mounting: 4″ square by 2 1/8″ deep box

Wiring range on all terminals: 22 to 12 AWG