Free English HUNTER 44132 (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.
CLICK HERE TO DOWNLOAD HUNTER 44132 (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
What tools and batteries are required to install the HUNTER 44132 thermostat?
To complete the installation of your HUNTER 44132 thermostat, you will need the following:
• Phillips Screwdriver (#2)
• Two 1.5V (AA) size alkaline batteries
What important warnings should I be aware of before installing my HUNTER 44132 thermostat?
Please take note of these warnings and cautions before proceeding with the installation of your HUNTER 44132 thermostat:
• Read all installation instructions before beginning installation.
• Do not disconnect the wires from your old thermostat until all wires have been properly labeled. You must label all wires properly because wire color may not indicate the function of the wire.
• All wiring must be done in accordance with local code and ordinances.
• Always turn power off to your furnace/compressor before the installation process. Failure to do so could result in damage to your thermostat and/or your heating and cooling system. Do not restore power until your installation is complete.
• This thermostat is designed for use with 24V AC/millivolt systems with a maximum of 1 amp. Higher amp or line voltage systems will cause damage to your system and increase the risk of fire.
How do I remove my old thermostat before installing the HUNTER 44132?
1. Turn off power to your compressor and furnace.
2. Remove the cover to your existing thermostat. Some thermostats may have screws or other locking devices that must first be removed. Once the wallplate is exposed, locate the wire terminals and try to identify the wire designations. If the wire terminals are not visible, they may be connected to the back of the wallplate. Look for any additional screws, tabs, or locking devices to remove the wallplate. If you are still unable to find the terminals for the wires, it may be necessary to contact the manufacturer of the original thermostat.
How should I label the wires from my old thermostat for the HUNTER 44132 installation?
Before disconnecting any wires, use the table below to write down your wire colors and the letter designations from the old thermostat. This will help you keep a record of your old thermostat’s wiring configuration. After writing down the wire colors and letters, use the provided terminal stickers to label the wires. To ensure wires do not fall back into the wall hole, you may tape them to the wall, or wrap them around a pencil.
| Wire Color | Wire letter |
|---|---|
What are some general wiring tips for installing the HUNTER 44132 thermostat?
Here are some tips to help you in wiring your HUNTER 44132 thermostat:
• Only 1 reversing valve is needed to run a heat pump. If both “O” and “B” are present, “B” may be a common wire.
• Often, 2-wire heat only systems do not have terminal labels. Connect 1 wire to the Rh terminal and the other to W.
• If you have a 3-wire hot water system, the damper valve control wire will be labeled and attached to the “A” terminal.
How do I mount the wallplate for my HUNTER 44132 thermostat?
1. Remove the mounting plate by pulling it straight off the back of the Thermostat.
2. Pull the wires through the back of the mounting plate, ensuring none of the wire labels are removed.
3. Using a Phillips Screwdriver, partially install 1 screw into the top hole of the thermostat. Ensure the thermostat is level using the bubble level on the mounting plate, then install the other screw. Tighten both screws until secure.
How do I connect the wires to the HUNTER 44132 wallplate?
1. First, check the charts provided in the PDF to identify your system type (Conventional or Heat Pump).
2. Raise all of the levers on the terminals you will be using. Heat Pump installation labels are on the left of the terminal blocks, and Conventional labels are on the right. If your installation does not call for the jumper (located between the RH and RC terminals), remove it now.
3. If one of the terminals you need has a tab in front of it, use your finger to break the tab away. Only break tabs you know you will be using.
4. Insert the bare end of each wire all the way into the appropriate hole in the terminal block that matches the wire label, then lower the lever. This will lock each wire in place. Do not insert wires into the holes in the top of the mounting block; they should be inserted into the front. Tuck excess wire back into the wall after they have been locked in the mounting plate.
How do I set the system and furnace type switches on the HUNTER 44132 thermostat?
Before mounting the thermostat onto the wallplate, turn it over to find the 2 switches located on the circuit board next to the battery compartment.
1. Set the system switch to “Conv” if you have a conventional HVAC system or “HP” if you have a heat pump system.
2. Set the furnace type switch to “Elc” if you have an electric conventional system or a heat pump. “Gas/Oil” will be used if you have a gas or oil-based conventional system.
Note: Conventional systems use the compressor for air conditioning and a separate furnace for heat. Heat pump systems use the compressor for both heating and cooling.
How do I install the batteries and attach the HUNTER 44132 thermostat to the wallplate?
Lay the ribbon across the battery compartment and install 2 (AA) batteries into the back of the thermostat over it. Then, snap the thermostat on to the mounting plate. Refer to the “Setup” section of your owner’s manual to continue setup, scheduling, and daily use.
How can I cross-reference my old thermostat’s wire labels with the HUNTER 44132 terminals?
If your old thermostat is a heat pump from one of the listed manufacturers and your wire labels do not match, you can use the following cross-reference chart:
| Hunter | Carrier | Coleman | Comfortmaker | Bryant, Payne | Rheem Ruud | Trane, Weathertron | York | Lennox (1) | Lennox (2) |
|---|---|---|---|---|---|---|---|---|---|
| R | R | R | R | R | R | R | R | R | V-VR |
| Y | Y or Y1 | Y | Y | Y | Y | Y | Y | Y | M |
| E | W2 | W2 | W1 | W2 | W2 | W | W | W1 | Y |
| E | E | Jumper to W2 | E | E | X2 | Jumper to W2 | E | E | |
| O | O | O | O | O | O | O | O | R | |
| B | B | B | |||||||
| G | G | G | G | G | G | G | G | G | F |
| L | L or F | L | L or X | L | X | L | |||
| C | C | X | C, X, X1 | C, X, X1 | X | B | B | C | X |
What are the terminal connections for various system types with the HUNTER 44132 thermostat?
CONVENTIONAL SYSTEMS
4 Wire Heat / Cool
• RH: Heat Power (Jumper to RC)
• Y: Cool Contactor
• G: Fan Relay
• W: Heat Contactor
5 Wire Heat / Cool
• RH: Heat Power
• RC: Cool Power
• Y: Cool Contactor
• G: Fan Relay
• W: Heat Contactor
3 Wire Cool Only
• RC: Cool Power (Jumper to RH)
• Y: Cool Contactor
• G: Fan Relay
3 Wire Heat Only
• RH: Heat Power (Jumper to RC)
• G: Fan Relay
• W: Heat Contactor
2 Wire Heat Only
• RH: Heat Power (Jumper to RC)
• W: Heat Contactor
3 Wire Hot Water with Damper Valve
• RH: Heat Power (Jumper to RC)
• W: Heat Contactor
• A: Damper Valve
4 Wire with Common
• RH: Heat Power (Jumper to RC)
• Y: Cool Contactor
• G: Fan Relay
• W: Heat Contactor
• C: Common
Conventional Multi-Stage
• RH: Heat Power (Jumper to RC)
• Y: Cool Contactor
• G: Fan Relay
• W: Heat Contactor
• W2: Second Stage Heat
• Y2: Second Stage Cool
• C: Common
HEAT PUMP SYSTEMS
Single Stage Heat Pump
• R: Heat 24V Supply (Jumper to RC)
• Y: Compressor Contact
• G: Fan Relay
• O: Cool Relay / Valve
Single Stage Heat Pump W/Aux Heat
• R: Heat 24V Supply (Jumper to RC)
• Y: Compressor Contact
• G: Fan Relay
• L: System Monitor (may not be present)
• O: Cool Relay / Valve
• Aux/E: Auxiliary Heat
• C: Common (may not be present)
Single Stage Heat Pump W/Heat Reversing
• R: Heat 24V Supply (Jumper to RC)
• Y: Compressor Contact
• G: Fan Relay
• L: System Monitor (may not be present)
• B: Heat Relay / Valve
• Aux/E: Auxiliary Heat
• C: Common (may not be present)
Multi-Stage Heat Pump
• R: Heat 24V Supply (Jumper to RC)
• Y: Compressor Contact
• G: Fan Relay
• L: System Monitor (may not be present)
• O: Cool Relay / Valve
• Aux/E: Auxiliary Heat
• W2: Second Stage Heat
• Y2: Second Stage Cool
• C: Common (may not be present)
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
CLICK HERE TO DOWNLOAD HUNTER 44132 (01) PDF DOCUMENT