HONEYWELL SILENT KNIGHT RA-2000 installation involves the following steps:
1. Make sure power is off at the panel.
2. Mount the RA-2000 in the desired location.
3. Connect the RA-2000 to the panel.
4. Use the dipswitches on the back of the RA-2000 to assign an ID# to the RA-2000.
5. The RA-2000 module must be added to the system through programming. JumpStart Auto Programming will add the module automatically.
What are the specifications for the HONEYWELL SILENT KNIGHT RA-2000?
| Parameter | Value |
|---|---|
| Operating Voltage | 24 VDC |
| Current Standby | 25 mA |
| Current Alarm | 50 mA |
| Operating Temperature | 0° to 49° C (32° to 120° F) |
| Dimensions (Flush Mount) | Overall: 12-1/4” W x 11.5” H x 7/8” D 31.1 cm W x 29.2 cm H x 2.2 cm D |
| Dimensions (Surface Mount) | Including trim ring: 12-1/4” W x 11.5” H x 3” D 31.1 cm W x 29.2 cm H x 7.6 cm D |
How do I flush mount the HONEYWELL SILENT KNIGHT RA-2000?
Follow these steps to flush mount the HONEYWELL SILENT KNIGHT RA-2000:
1. The back box dimensions are 9-3/8” w x 8-3/8” h. The minimum depth is 2″. The back box can be mounted prior to the complete installation of the RA-2000 using any of the mounting holes.
2. Remove knockout holes as needed for wires.
3. Wire the Annunciator board to the main control panel.
4. Attach the annunciator and door assembly to back box using the supplied screws.
How do I surface mount the HONEYWELL SILENT KNIGHT RA-2000?
The Model RA-2000TR red trim ring and RA-2000GRAYTR gray trim ring kits are available for use when surface mounting.
1. Remove the desired knock out.
2. To properly mount the back box, insert a single screw into the key shaped mounting hole. Do not tighten all the way.
3. Place a level on top of the back box, with the back box level insert the rest of the mounting screws.
4. Run wires to the control panel.
5. Place the trim ring over the back box.
6. Attach the Door assembly to the back box using screws provided.
7. After the annunciator wiring to the panel has been completed, replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel.
How is the HONEYWELL SILENT KNIGHT RA-2000 added to the system programming?
The RA-2000 module must be added to the system through programming. JumpStart Auto Programming will add the module automatically.