What are the electrical specifications for the HEATFLO KUH-C-12-83?

According to Table A in the specifications, the electrical data for the HEATFLO KUH-C-12-83 is as follows:

Model Volts kW Phase Amps Standard Contactor Rating (Qty.)
KUH-C-12-83 208 12.5 3 34.8 50A (1)

How do I prepare the HEATFLO KUH-C-12-83 for the installation of a disconnect switch?

To prepare the HEATFLO KUH-C-12-83 for installation:

Step 1. Ensure the amperage rating of the disconnect is equal to or greater than the amperage rating on Table A and as marked on the nameplate located on the bottom access door.

Step 2. The power disconnect kit is to be installed in the rectangular knockout located in the bottom right corner on the back of the heater. The knockout can be removed using a hammer and chisel or other appropriate means.

Step 3. For easier access to terminal screws to wire pigtail leads supplied on the heater, it is suggested that these connections be made before installing.


How is the KDS-1 disconnect switch installed on the HEATFLO KUH-C-12-83?

The KDS-1 disconnect switch installation procedure is as follows:

Step 1. The Disconnect switch, with its mounting bracket, should be inserted into the heater cabinet by opening the bottom service door and positioned behind the opening created during preparation.

Step 2. Insert the four self-tapping screws into the four holes in the rear panel. They should engage the holes in the mounting plate and then be tightened until they are secure.

Step 3. Mount the switch faceplate to the switch using the two provided screws. Mount with the “OFF” position to “0” to the left and the “ON” position “1” to the top.

Step 4. Slide the handle over the shaft and tighten the screw to secure.


How are the KDS-2 and KDS-3 disconnect switches installed on compatible Heatflo units?

For units utilizing KDS-2 and KDS-3 kits:

Step 1. The cover plate should be placed over the rectangular opening with its four mounting holes lined up with the four holes in the cabinet and the four holes in the mounting bracket.

Step 2. Insert the four self-tapping screws into the four holes until they engage the holes in the mounting bracket and tighten until they are secure.

Step 3. Place the plastic bezel over the installed switch and push towards the switch until the tabs snap into place.


How do I operate the power disconnect switch on the HEATFLO KUH-C-12-83?

The operation depends on the specific switch kit installed:

For KDS-1 (40 and 50 Amp Kits): This switch disconnects the power to power leads when the handle is rotated to the “0” position (left). The power is on when the switch handle is rotated to the “1” position (top) position.

For KDS-2 and KDS-3 (80 and 100 Amp Kits): This switch disconnects power to the power leads when the handle is placed in its full lower position. The power is on when the switch handle is in its full upper position.


What wiring instructions must be followed for the HEATFLO KUH-C-12-83 disconnect switch?

The wiring instructions are as follows:

Step 1. Use the three pigtail leads supplied with the kit (40 & 80 Amp) when connecting to the power line. Use No. 4GA Copper conductor wire only for 100 Amp disconnect when wiring to the power line.

Step 2. The power disconnect wiring to the heater is to be made using the pigtail leads supplied on the heaters up to and including 25 kW. On larger heaters, the installer should supply 105°C type AWM 600V wire.

Notes:

1. Remove lead wires marked L2 and AL2 when using one-phase power service (for applicable units).

2. For units without contactors, the disconnect switch is to be wired to lead wires on heater power.

3. Use copper supply wire only with this switch.


What safety warnings are associated with installing the disconnect switch on the HEATFLO KUH-C-12-83?

ELECTRIC SHOCK HAZARD. Disconnect all power before installing the disconnect switch. Failure to do so could result in personal injury or property damage. The disconnect switch must be installed by a qualified person and must be effectively grounded in accordance with the National Electrical Code, NFPA 70.


How should the HEATFLO KUH-C-12-83 nameplate be labeled after installing a disconnect kit?

For future replacement parts, the model number should be modified on the nameplate to show that a disconnect kit has been field installed on the heater.

A label kit (P/N 170-302788-002) has been included in the plastic envelope located in the disconnect kit. Cut off the appropriate number for the size disconnect being installed:

1 = 40 Amp

2 = 80 Amp

3 = 100 Amp

The label has a pressure-sensitive adhesive back so that the number can be placed over the “0” at the end of the Catalog Number on the nameplate.


What are the replacement parts for the disconnect kits compatible with the HEATFLO KUH-C-12-83?

The replacement parts list for the disconnect kits is as follows:

Disconnect Size Kit Model # Disconnect Cover Plate Mounting Bracket
50 Amp KDS-1 292-303472-001 220-303485-010
80 Amp KDS-2 292-303472-002 220-303485-003 220-303484-003
100 Amp KDS-3 292-303472-008 220-303485-003 220-303484-003