What are the electrical pin connections for the COPELAND XM750D?
The following table details the pin connections for the COPELAND XM750D:
| PIN | Label | Description |
|---|---|---|
| 1 | Line | Digital output 4: Common |
| 2 | Alarm/AUX | Digital output 4: normally closed |
| 3 | NC | Digital output 4: normally open |
| 4 | Not Used | |
| 5 | Not Used | |
| 6 | Not Used | |
| 7 | N | 100-240V power supply: Neutral |
| 8 | Line | 100-240V power supply: Line |
| 9 | Not Used | |
| 10 | Not Used | |
| 11 | Comp | Digital output 5: Common |
| 12 | Comp | Digital output 5: normally open |
| 13 | Def | Digital output 2: Common |
| 14 | Def | Digital output 2: normally open |
| 15 | Light | Digital output 1: Common |
| 16 | Light | Digital output 1: normally open |
| 17 | Fan | Digital output 3: Common |
| 18 | Fan | Digital output 3: normally open |
| 19 | Not Used | |
| 20 | Not Used | |
| 21 | Not Used | |
| 22 | Not Used | |
| 23 | Not Used | |
| 24 | Pb4-In | Analogue input 4 (temperature only) |
| 25 | Ground for analogue input 3 and 4 | |
| 26 | Pb3-In | Analogue input 3 (temperature only) |
| 27 | Pb2-In | Analogue input 2 (temperature only) |
| 28 | Ground for analogue input 1 and 2 | |
| 29 | Pb1-In | Analogue input 1 (temperature only) |
| 30 | DI2-In | Digital input 2 (free voltage) |
| 31 | Ground for digital input 1 and 2 | |
| 32 | DI1-In | Digital input 1 (free voltage) |
| 33 | LAN – | Digital output 1: normally open |
| 34 | LAN + | High voltage power supply: Neutral |
| 35 | RS485 (GND) | Ground terminal for RS485 serial port |
| 36 | RS485 (-) | Negative terminal for RS485 (-) serial port |
| 37 | RS485 (+) | Positive terminal for RS485 (+) serial port |
| 38 | Remote key (-) | Negative terminal for Remote keyboard (-) |
| 39 | Remote key (+) | Positive terminal for Remote keyboard (+) |
| 40 | Remote key (VNR) | Supply for remote keyboard |
| 41 | AnOUT2 (-) | Analog output 2 ground |
| 42 | AnOUT2 (+) | Analog output 2 Signal (+) |
| 43 | AnOUT1 (-) | Analog output 1 ground |
| 44 | AnOUT1 (+) | Analog output 1 Signal (+) |
What are the safety instructions for operating the COPELAND XM750D?
Please adhere to the following safety instructions when using the COPELAND XM750D:
• This manual is part of the product and should be kept near the instrument for easy and quick reference.
• The instrument shall not be used for purposes different from those described. It cannot be used as a safety device.
• In case of failure or faulty operation, contact the local distributor with a detailed description of the fault.
• Strictly follow the safety instructions before opening the box.
• Check the application limits and the correct power supply voltage before proceeding.
• Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to avoid condensation.
• Warning: disconnect the power supply and all other electrical connections before any kind of maintenance.
• Observe the maximum current value which can be applied to each relay (see Technical Data).
• Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining.
What are the different screens on the COPELAND XM750D user interface?
| SCREEN NAME | DESCRIPTION |
|---|---|
| Home | Show temperature value, measurement unit and active alarms only. It is the first screen after power on or after exit from other status. |
| Status Visualization | This screen shows activated functions and regulation outputs (compressor, ventilators) overlapped with temperature and/or humidity value. |
| Virtual Keyboard | This screen shows available functions. Activated function will blink when this screen is visualized. |
| Temperature Setpoint | This screen enables the modification of the Temperature Set Point value. |
| Programming Mode | This screen enables the modification of parameters: ALL, GrP or “X9” mode can be used. |
| Hotkey Management | UPL = upload parameters from device to HOTKEY, doL = download parameters from HOTKEY to device. |
| Info Menu | To scroll all I/O variables and status (probes, digital inputs, digital outputs, etc.). |
| Device Locked | V-Swipe from Home screen to lock or unlock the device. |
How do I use the touch gestures to operate the COPELAND XM750D?
| GESTURE | HOW-TO | DESCRIPTION |
|---|---|---|
| ONE TAP | Press a specific area of the screen with a finger for 1 sec. | Switch ON / Switch OFF: when in Virtual Keyboard, use this to turn on/off a specific function. When in Programming mode, use this to select a parameter or a parameter value. |
| TAP and HOLD | Press anyplace of the surface with a finger for more than 3 sec. | Enter / Save: use this to enter programming mode or parameter menu and to save modifications. When in Virtual Keyboard, use this on the “ONOFF” to switch OFF and ON the device. |
| H-SWIPE | Drag a finger across surface, from left to right or from right to left. | Browse: use horizontal swipe (right to left or left to right) to browse through HOME, Virtual Keyboard and Info View. When in Programming menu: use horizontal swipe to browse through parameter menu. |
| V-SWIPE | Drag a finger across surface, from top to bottom or from bottom to top (overlapping only one of the digits). | Modify: use vertical swipe (from top to bottom or bottom to top) to change a parameter value. |
How do I navigate the menus on the COPELAND XM750D?
Follow these steps to navigate the menus:
Home Navigation to Set Point Temperature:
1. From the Home screen (e.g., showing “SEE”), perform a horizontal swipe (H-SWIPE) to enter the Set Point Temperature screen (e.g., showing “14.0”).
2. Tap anywhere on the screen to enable modification. The value will start blinking (e.g., “15.0”).
3. Perform a vertical swipe (V-SWIPE) up or down to change the value.
4. Tap “SET” to save the new value.
Home Navigation to Programming Menu:
1. From the Home screen (e.g., showing “SEE”), perform two horizontal swipes (H-SWIPE) to reach the Programming Menu (showing “PrG”).
2. Tap anywhere on the screen. The display will show “ALL” for the All Parameters menu, “GrP” for the Groups menu, or “PAS” if a password is required.
Home Navigation to Programming Menu – ALL:
1. From the Home screen, perform three horizontal swipes (H-SWIPE) to reach the “ALL” parameters screen.
2. Tap anywhere to enter the parameter list. The first parameter will be displayed (e.g., “-4.0”).
3. Use vertical swipes (V-SWIPE) to modify the parameter value (e.g., to “-24.0”).
4. Tap “SET” to save the new value.
What are the technical specifications for the CT760 Keyboard used with the COPELAND XM750D?
| Housing | Self-extinguishing polycarbonate |
| Dimensions | Front 80x38mm, case depth 26mm |
| Mounting device | Panel, 71×29 mm panel cut-out; panel thickness 0.7 ÷ 1.0mm; Insertion force: 40-60N |
| Degree of Protection | EN 60529 Rear Housing: IP20 Front panel: IP54 |
| Power Supply | From XM750D power module, 3 wires, 0.5-2.5mm² |
| Display | 3 digits, red LED, 20.4 mm high |
| Buzzer | Internal, always present |
| Max distance between controller and keyboard | 10m |
What are the technical specifications for the COPELAND XM750D main controller?
| Housing | Self-extinguishing polycarbonate |
| Dimensions | 140x110x48mm (w x h x d) |
| Mounting device | DIN Rail |
| Degree of Protection | EN 60529 IP20 (whole controller) |
| Power Supply | 12VAC/DC SELV (class 2) source; 230VAC or 115VAC or 100 to 240VAC ±10%, 50/60Hz |
| Overvoltage Category | III |
| Rated Power | 12VAC/DC SELV (class 2) source: 5VA 230VAC 50/60 Hz or 110VAC 50/60 Hz: 10VA 100-240VAC 50/60 Hz: 10VA |
| Rated Impulse Voltage | 2500V |
| Software Class | A |
| Data Storing | Real Time Clock: data maintenance up to 6 months with removable non-rechargeable lithium battery Other parameters: internal flash |
| Type of Action | 1.B |
| Pollution Degree | 2, non-condensing humidity |
| Ambient Operating Temperature and Humidity | IEC/EN: 0T60°C; 20-85 rH% (non-condensing humidity) UL/CSA: -10T60°C; 20-85 rH% (non-condensing humidity) |
| Shipping and storage temperature | -40T85°C; 20-85 rH% (non-condensing humidity) -20T70°C; 20-85 rH% (non-condensing humidity) – controller with RTC |
| Resistance to heat | UL 94 V-0 |
| Measurement range | NTC, NTC_US: -40T110°C, resolution 0.1°C or 1°C (selectable) PTC: -50T150°C, resolution 0.1°C or 1°C (selectable) PT1000: -100T150°C, resolution 0.1°C or 1°C (selectable) |
| Accuracy | NTC, PTC, PT1000: ±1% compared to the full scale |
| Inputs | Up to 6 NTC, NTC_US, PTC or PT1000 (configurable); max distance 10m Up to 2 voltage free contacts; max distance 10m 1 4-20mA or 0-5V; max distance 10m |
What are the relay output ratings for the COPELAND XM750D?
| OUTPUT | TERMINALS | RATING UL 60730 | RATING IEC/EN 60730 | RATING IEC/EN 60335 |
|---|---|---|---|---|
| oA5 | 11-12 | Resistive load 1A, 230Vac, 30K cycles Pilot duty C300, 30K cycles Motor load 1FLA/6LRA, 230Vac, 30K cycles |
1(1)A, 230Vac, 100K cycles | 1(1)A, 230Vac, 100K cycles |
| oA3 | 17-18 | Resistive load 5A, 230Vac, 30K cycles Pilot duty B300, 6K cycles |
5A, 230Vac, 60K cycles | 5A, 230Vac, 100K cycles |
| oA4 (NO) | 1-2 | Resistive load 8A, 230Vac, 30K cycles Motor load 1/2HP, 230Vac, 30K cycles Pilot duty B300, 6K cycles |
8A, 230Vac, 60K cycles 2(2)A, 250Vac, 100K cycles |
8A, 230Vac, 100K cycles 2(2)A, 250Vac, 100K cycles |
| oA4 (NC) | 1-3 | Resistive load 3A, 230Vac, 30K cycles Pilot duty C300, 6K cycles |
3A, 230Vac, 30K cycles | 3A, 230Vac, 30K cycles |
| oA2 | 13-14 | Resistive load 10A, 230Vac, 100K cycles Motor Load 10FLA/60LRA, 230Vac, 30K cycles Pilot Duty B300, 30K cycles |
10(4)A, 230Vac, 100K cycles | 10(4)A, 230Vac, 100K cycles |
| oA1 (standard relay) | 15-16 | Resistive load 8A, 230Vac, 100K cycles Motor Load 8FLA/48LRA, 230Vac, 30K cycles Pilot Duty B300, 30K cycles |
8(4)A, 230Vac, 100K cycles | 8(4)A, 230Vac, 100K cycles |
| oA1 (inrush relay) | 15-16 | Resistive load 8A, 230Vac, 50K cycles Motor Load 8FLA/48LRA, 230Vac, 30K cycles Pilot Duty B300, 30K cycles |
8(2)A, 230Vac, 100K cycles | 8(2)A, 230Vac, 100K cycles |
What are the analogue output specifications for the COPELAND XM750D?
Analogue Output 1 (1Ao)
• Frequency output: Supply voltage 12Vdc; Max supply current=5mA; duty cycle 50%; 0 to 166 Hz. Accuracy: ±1Hz compared to the full scale.
• Current output: 4-20mA; Max load 100 ohm.
• Voltage output: 0-10Vdc; Max supply current=5mA; Min load 2 K ohm.
• Accuracy: ±2% compared to the full scale.
Analogue Output 2 (2Ao)
• Frequency output: Supply voltage 12Vdc; Max supply current=5mA; duty cycle 50%; 0 to 166 Hz. Accuracy: ±1Hz compared to the full scale.
• Voltage output: 0-10Vdc; Max supply current=5mA; Min load 2 K ohm.
• Accuracy: ±2% compared to the full scale.
HOT-KEY (I/O port)
• Output voltage is 5 VDC. DO NOT CONNECT ANY EXTERNAL POWER SUPPLY.