COPELAND XM750D (01) Image

Free English COPELAND XM750D (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.


CLICK HERE TO DOWNLOAD COPELAND XM750D (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

What are the electrical pin connections for the COPELAND XM750D?

The following table details the pin connections for the COPELAND XM750D:

PIN Label Description
1 Line Digital output 4: Common
2 Alarm/AUX Digital output 4: normally closed
3 NC Digital output 4: normally open
4 Not Used
5 Not Used
6 Not Used
7 N 100-240V power supply: Neutral
8 Line 100-240V power supply: Line
9 Not Used
10 Not Used
11 Comp Digital output 5: Common
12 Comp Digital output 5: normally open
13 Def Digital output 2: Common
14 Def Digital output 2: normally open
15 Light Digital output 1: Common
16 Light Digital output 1: normally open
17 Fan Digital output 3: Common
18 Fan Digital output 3: normally open
19 Not Used
20 Not Used
21 Not Used
22 Not Used
23 Not Used
24 Pb4-In Analogue input 4 (temperature only)
25 Ground for analogue input 3 and 4
26 Pb3-In Analogue input 3 (temperature only)
27 Pb2-In Analogue input 2 (temperature only)
28 Ground for analogue input 1 and 2
29 Pb1-In Analogue input 1 (temperature only)
30 DI2-In Digital input 2 (free voltage)
31 Ground for digital input 1 and 2
32 DI1-In Digital input 1 (free voltage)
33 LAN – Digital output 1: normally open
34 LAN + High voltage power supply: Neutral
35 RS485 (GND) Ground terminal for RS485 serial port
36 RS485 (-) Negative terminal for RS485 (-) serial port
37 RS485 (+) Positive terminal for RS485 (+) serial port
38 Remote key (-) Negative terminal for Remote keyboard (-)
39 Remote key (+) Positive terminal for Remote keyboard (+)
40 Remote key (VNR) Supply for remote keyboard
41 AnOUT2 (-) Analog output 2 ground
42 AnOUT2 (+) Analog output 2 Signal (+)
43 AnOUT1 (-) Analog output 1 ground
44 AnOUT1 (+) Analog output 1 Signal (+)

What are the safety instructions for operating the COPELAND XM750D?

Please adhere to the following safety instructions when using the COPELAND XM750D:

• This manual is part of the product and should be kept near the instrument for easy and quick reference.

• The instrument shall not be used for purposes different from those described. It cannot be used as a safety device.

• In case of failure or faulty operation, contact the local distributor with a detailed description of the fault.

• Strictly follow the safety instructions before opening the box.

• Check the application limits and the correct power supply voltage before proceeding.

• Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to avoid condensation.

• Warning: disconnect the power supply and all other electrical connections before any kind of maintenance.

• Observe the maximum current value which can be applied to each relay (see Technical Data).

• Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining.


What are the different screens on the COPELAND XM750D user interface?

SCREEN NAME DESCRIPTION
Home Show temperature value, measurement unit and active alarms only. It is the first screen after power on or after exit from other status.
Status Visualization This screen shows activated functions and regulation outputs (compressor, ventilators) overlapped with temperature and/or humidity value.
Virtual Keyboard This screen shows available functions. Activated function will blink when this screen is visualized.
Temperature Setpoint This screen enables the modification of the Temperature Set Point value.
Programming Mode This screen enables the modification of parameters: ALL, GrP or “X9” mode can be used.
Hotkey Management UPL = upload parameters from device to HOTKEY, doL = download parameters from HOTKEY to device.
Info Menu To scroll all I/O variables and status (probes, digital inputs, digital outputs, etc.).
Device Locked V-Swipe from Home screen to lock or unlock the device.

How do I use the touch gestures to operate the COPELAND XM750D?

GESTURE HOW-TO DESCRIPTION
ONE TAP Press a specific area of the screen with a finger for 1 sec. Switch ON / Switch OFF: when in Virtual Keyboard, use this to turn on/off a specific function. When in Programming mode, use this to select a parameter or a parameter value.
TAP and HOLD Press anyplace of the surface with a finger for more than 3 sec. Enter / Save: use this to enter programming mode or parameter menu and to save modifications. When in Virtual Keyboard, use this on the “ONOFF” to switch OFF and ON the device.
H-SWIPE Drag a finger across surface, from left to right or from right to left. Browse: use horizontal swipe (right to left or left to right) to browse through HOME, Virtual Keyboard and Info View. When in Programming menu: use horizontal swipe to browse through parameter menu.
V-SWIPE Drag a finger across surface, from top to bottom or from bottom to top (overlapping only one of the digits). Modify: use vertical swipe (from top to bottom or bottom to top) to change a parameter value.

How do I navigate the menus on the COPELAND XM750D?

Follow these steps to navigate the menus:

Home Navigation to Set Point Temperature:

1. From the Home screen (e.g., showing “SEE”), perform a horizontal swipe (H-SWIPE) to enter the Set Point Temperature screen (e.g., showing “14.0”).

2. Tap anywhere on the screen to enable modification. The value will start blinking (e.g., “15.0”).

3. Perform a vertical swipe (V-SWIPE) up or down to change the value.

4. Tap “SET” to save the new value.

Home Navigation to Programming Menu:

1. From the Home screen (e.g., showing “SEE”), perform two horizontal swipes (H-SWIPE) to reach the Programming Menu (showing “PrG”).

2. Tap anywhere on the screen. The display will show “ALL” for the All Parameters menu, “GrP” for the Groups menu, or “PAS” if a password is required.

Home Navigation to Programming Menu – ALL:

1. From the Home screen, perform three horizontal swipes (H-SWIPE) to reach the “ALL” parameters screen.

2. Tap anywhere to enter the parameter list. The first parameter will be displayed (e.g., “-4.0”).

3. Use vertical swipes (V-SWIPE) to modify the parameter value (e.g., to “-24.0”).

4. Tap “SET” to save the new value.


What are the technical specifications for the CT760 Keyboard used with the COPELAND XM750D?

Housing Self-extinguishing polycarbonate
Dimensions Front 80x38mm, case depth 26mm
Mounting device Panel, 71×29 mm panel cut-out; panel thickness 0.7 ÷ 1.0mm; Insertion force: 40-60N
Degree of Protection EN 60529
Rear Housing: IP20
Front panel: IP54
Power Supply From XM750D power module, 3 wires, 0.5-2.5mm²
Display 3 digits, red LED, 20.4 mm high
Buzzer Internal, always present
Max distance between controller and keyboard 10m

What are the technical specifications for the COPELAND XM750D main controller?

Housing Self-extinguishing polycarbonate
Dimensions 140x110x48mm (w x h x d)
Mounting device DIN Rail
Degree of Protection EN 60529 IP20 (whole controller)
Power Supply 12VAC/DC SELV (class 2) source; 230VAC or 115VAC or 100 to 240VAC ±10%, 50/60Hz
Overvoltage Category III
Rated Power 12VAC/DC SELV (class 2) source: 5VA
230VAC 50/60 Hz or 110VAC 50/60 Hz: 10VA
100-240VAC 50/60 Hz: 10VA
Rated Impulse Voltage 2500V
Software Class A
Data Storing Real Time Clock: data maintenance up to 6 months with removable non-rechargeable lithium battery
Other parameters: internal flash
Type of Action 1.B
Pollution Degree 2, non-condensing humidity
Ambient Operating Temperature and Humidity IEC/EN: 0T60°C; 20-85 rH% (non-condensing humidity)
UL/CSA: -10T60°C; 20-85 rH% (non-condensing humidity)
Shipping and storage temperature -40T85°C; 20-85 rH% (non-condensing humidity)
-20T70°C; 20-85 rH% (non-condensing humidity) – controller with RTC
Resistance to heat UL 94 V-0
Measurement range NTC, NTC_US: -40T110°C, resolution 0.1°C or 1°C (selectable)
PTC: -50T150°C, resolution 0.1°C or 1°C (selectable)
PT1000: -100T150°C, resolution 0.1°C or 1°C (selectable)
Accuracy NTC, PTC, PT1000: ±1% compared to the full scale
Inputs Up to 6 NTC, NTC_US, PTC or PT1000 (configurable); max distance 10m
Up to 2 voltage free contacts; max distance 10m
1 4-20mA or 0-5V; max distance 10m

What are the relay output ratings for the COPELAND XM750D?

OUTPUT TERMINALS RATING UL 60730 RATING IEC/EN 60730 RATING IEC/EN 60335
oA5 11-12 Resistive load 1A, 230Vac, 30K cycles
Pilot duty C300, 30K cycles
Motor load 1FLA/6LRA, 230Vac, 30K cycles
1(1)A, 230Vac, 100K cycles 1(1)A, 230Vac, 100K cycles
oA3 17-18 Resistive load 5A, 230Vac, 30K cycles
Pilot duty B300, 6K cycles
5A, 230Vac, 60K cycles 5A, 230Vac, 100K cycles
oA4 (NO) 1-2 Resistive load 8A, 230Vac, 30K cycles
Motor load 1/2HP, 230Vac, 30K cycles
Pilot duty B300, 6K cycles
8A, 230Vac, 60K cycles
2(2)A, 250Vac, 100K cycles
8A, 230Vac, 100K cycles
2(2)A, 250Vac, 100K cycles
oA4 (NC) 1-3 Resistive load 3A, 230Vac, 30K cycles
Pilot duty C300, 6K cycles
3A, 230Vac, 30K cycles 3A, 230Vac, 30K cycles
oA2 13-14 Resistive load 10A, 230Vac, 100K cycles
Motor Load 10FLA/60LRA, 230Vac, 30K cycles
Pilot Duty B300, 30K cycles
10(4)A, 230Vac, 100K cycles 10(4)A, 230Vac, 100K cycles
oA1 (standard relay) 15-16 Resistive load 8A, 230Vac, 100K cycles
Motor Load 8FLA/48LRA, 230Vac, 30K cycles
Pilot Duty B300, 30K cycles
8(4)A, 230Vac, 100K cycles 8(4)A, 230Vac, 100K cycles
oA1 (inrush relay) 15-16 Resistive load 8A, 230Vac, 50K cycles
Motor Load 8FLA/48LRA, 230Vac, 30K cycles
Pilot Duty B300, 30K cycles
8(2)A, 230Vac, 100K cycles 8(2)A, 230Vac, 100K cycles

What are the analogue output specifications for the COPELAND XM750D?

Analogue Output 1 (1Ao)

• Frequency output: Supply voltage 12Vdc; Max supply current=5mA; duty cycle 50%; 0 to 166 Hz. Accuracy: ±1Hz compared to the full scale.

• Current output: 4-20mA; Max load 100 ohm.

• Voltage output: 0-10Vdc; Max supply current=5mA; Min load 2 K ohm.

• Accuracy: ±2% compared to the full scale.

Analogue Output 2 (2Ao)

• Frequency output: Supply voltage 12Vdc; Max supply current=5mA; duty cycle 50%; 0 to 166 Hz. Accuracy: ±1Hz compared to the full scale.

• Voltage output: 0-10Vdc; Max supply current=5mA; Min load 2 K ohm.

• Accuracy: ±2% compared to the full scale.

HOT-KEY (I/O port)

• Output voltage is 5 VDC. DO NOT CONNECT ANY EXTERNAL POWER SUPPLY.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

CLICK HERE TO DOWNLOAD COPELAND XM750D (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.