FREE ENGLISH BLUETTI EP2000 (01) PDF DOCUMENT.
FREE ENGLISH BLUETTI EP2000 (01) PDF USER GUIDE.
FREE ENGLISH BLUETTI EP2000 (01) PDF USER MANUAL.
FREE ENGLISH BLUETTI EP2000 (01) PDF OWNER GUIDE.
FREE ENGLISH BLUETTI EP2000 (01) PDF OWNER MANUAL.
FREE ENGLISH BLUETTI EP2000 (01) PDF REFERENCE GUIDE.
FREE ENGLISH BLUETTI EP2000 (01) PDF INSTRUCTION GUIDE.
FREE ENGLISH BLUETTI EP2000 (01) PDF REFERENCE MANUAL.
FREE ENGLISH BLUETTI EP2000 (01) PDF INSTRUCTION MANUAL.
FREE ENGLISH BLUETTI EP2000 (01) PDF OPERATING INSTRUCTIONS.
CLICK HERE TO DOWNLOAD BLUETTI EP2000 (01) PDF DOCUMENT
If this is not the document you want for this product, click here to see if we have any other documents for this product.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
What are the important notes for using the BLUETTI EP2000 quick guide?
1. This document is for quick guidance installation only. For details, please refer to the User Manual.
2. The warranty does not cover any damage to the equipment caused by violation of the guide.
What are the components of the BLUETTI EP2000 Inverter?
The components of the BLUETTI EP2000 Inverter are identified as follows:
| No. | Name | No. | Name | No. | Name |
|---|---|---|---|---|---|
| 1 | Grounding Terminals (To PV) | 9 | PV4- Input | 17 | COM2 Port |
| 2 | PV1+ Input | 10 | Grounding Terminal (To HV800) | 18 | DRMs Port |
| 3 | PV1- Input | 11 | COM1 Port | 19 | COM3 Port |
| 4 | PV2+ Input | 12 | BAT- Terminal | 20 | USB Port |
| 5 | PV2- Input | 13 | BAT+ Terminal | 21 | GRID Block |
| 6 | PV3+ Input | 14 | AC Output | 22 | BACKUP Block |
| 7 | PV3- Input | 15 | PV Input Switch | 23 | System Grounding Terminal |
| 8 | PV4+ Input | 16 | Bleed Valve |
What are the components of the BLUETTI EP2000 HV800 Battery Controller?
The components of the HV800 Battery Controller, used with the BLUETTI EP2000 system, are as follows:
| No. | Name | No. | Name | No. | Name |
|---|---|---|---|---|---|
| 1 | Grounding Terminal 1 | 8 | Bleed Valve | 15 | AC Output (To Battery) |
| 2 | EP2000 COM Port | 9 | Reserved Port | 16 | BAT- Terminal |
| 3 | Third-party Inverter COM Port | 10 | Battery Signal Port | 17 | SoC Indicators |
| 4 | Grounding Terminal 2 | 11 | Circuit Breaker | 18 | High Voltage Power-on Indicator |
| 5 | Negative Terminal (To PCS) | 12 | BAT+ Terminal | 19 | Low Voltage Power-on Indicator |
| 6 | Positive Terminal (To PCS) | 13 | Power Button | ||
| 7 | AC Input (To PCS) | 14 | Reserved Port |
What are the components of the BLUETTI EP2000 B700 Battery?
The components of the B700 Battery, used with the BLUETTI EP2000 system, are as follows:
| No. | Name | No. | Name | No. | Name |
|---|---|---|---|---|---|
| 1 | Grounding Terminal 1 | 4 | BAT+ Terminal | 7 | Pack LINK OUTPUT |
| 2 | Bleed Valve | 5 | AC Input | 8 | AC Output |
| 3 | Grounding Terminal 2 | 6 | Pack LINK INPUT | 9 | BAT- Terminal |
What are the installation location requirements for the BLUETTI EP2000 system?
When installing the BLUETTI EP2000 system, please adhere to the following location requirements:
Prohibited Locations:
• Do not install near fire or flammable materials.
• Do not install outdoors exposed to direct sun, rain, or snow.
• Do not install where it can be submerged in water.
Approved Locations:
• Install indoors in a dry, well-ventilated area.
• Install against a solid brick or concrete wall.
• The system must be installed vertically, with a maximum tilt angle of 5 degrees.
What are the reserved space requirements for installing the BLUETTI EP2000?
To ensure proper ventilation and access, maintain the following minimum clearances around the BLUETTI EP2000 system:
• Above: ≥300mm
• Front: ≥1000mm
• Sides (Left and Right): ≥300mm
• From Ground: The unit should be placed on its base on the ground.
What should I know before installing the BLUETTI EP2000 system?
1. Please ensure that the distance from the BLUETTI EP2000 energy storage system to the distribution box is less than 2500mm.
2. Place the base on the ground and adjust the height of leveling feet so that the base stands stably on the ground. Don’t forget to tighten the nuts to secure the leveling feet.
3. To ensure a smooth installation of your energy storage system, secure each layer from the bottom up before proceeding to the next. When installing three or more battery packs, please use sturdy and reliable supports with dimensions of 1500mm in length, 1000mm in width, and 300mm in height.
Note: For safety, secure the system to the wall after stacking.
What are the different stacking configurations for the BLUETTI EP2000 system?
The BLUETTI EP2000 system can be configured with one EP2000 inverter, one HV800 controller, and a varying number of B700 batteries from 2 to 7. The stacking arrangement varies with the number of batteries:
• 1 EP2000 + 1 HV800 + 2 B700: Single stack.
• 1 EP2000 + 1 HV800 + 3 B700: Single stack.
• 1 EP2000 + 1 HV800 + 4 B700: Two stacks. Left stack: EP2000, HV800, B700, B700. Right stack: B700, B700.
• 1 EP2000 + 1 HV800 + 5 B700: Two stacks. Left stack: EP2000, HV800, B700, B700. Right stack: B700, B700, B700.
• 1 EP2000 + 1 HV800 + 6 B700: Two stacks, with 3 B700 batteries on the left side and 3 B700 batteries on the right side.
• 1 EP2000 + 1 HV800 + 7 B700: Two stacks. The left stack contains the EP2000, HV800 and multiple B700s, and the right stack contains the remaining B700s.
How do I connect the ground cables for the BLUETTI EP2000?
Use a 10mm² yellow-green grounding cable. Connect the ground cables for the EP2000 inverter and the HV800 controller to the corresponding grounding terminals (marked PE). The connection is made on the left side of the stacked units. Ensure the wire is properly stripped and secured in the terminal block. The stripped wire end (L2) should be 3mm longer than the insulation (L1). The visible wire should be even or bulge up to 1 mm in the terminal lug. The right side of the stack is grounded through the inter-unit connections.
How do I connect the power cables for the BLUETTI EP2000 system?
The batteries in the BLUETTI EP2000 system are connected in series. For example, in a system with an EP2000, HV800, and 2 B700 batteries, the power cables are connected as follows:
1. Connect the (EP2000) BAT+ cable to the corresponding (HV800) P+ terminal.
2. Connect the (EP2000) BAT- cable to the corresponding (HV800) P- terminal.
3. The power connections between the HV800 and the B700 batteries, and between the B700 batteries themselves, are made through their respective BAT+/BAT- and AC INPUT/OUTPUT ports as shown in the electrical connection diagrams.
How do I connect the communication cables between the BLUETTI EP2000 and the HV800?
Connect the communication cable from the COM1 port on the BLUETTI EP2000 inverter to the PCS1 port on the HV800 Battery Controller. This is done on the left side of the unit. Communication between other units like the B700 batteries is handled via Pack LINK cables on the right side.
How do I connect the AC power cables for the BLUETTI EP2000 system?
The AC power cables link the HV800 Battery Controller to the B700 batteries. Connect the AC OUTPUT cable from the HV800 to the AC INPUT of the first B700 battery. Then, connect the AC OUTPUT of the first B700 to the AC INPUT of the second B700, and so on, creating a daisy chain.
How do I connect the GRID and BACKUP cables to the BLUETTI EP2000?
1. Use a 5-core 10mm² copper power cable. The maximum current is 50A for installation in an electrical conduit and 60A for installation in air.
2. Connect the L1, L2, L3, N, and PE wires for both the GRID input and the BACKUP output to the corresponding terminal blocks on the BLUETTI EP2000 inverter.
3. When connecting these cables, do not use electric tools. Use a manual H3 hex screwdriver to tighten the locking screws. The recommended torque is 2 Nm.
How do I connect and operate the transfer switch with the BLUETTI EP2000?
The transfer switch is used to switch your essential loads between the public grid and the BLUETTI EP2000 backup power.
Connection:
1. Connect the L1/L2/L3/N wires from the BLUETTI EP2000 BACKUP terminal and the Public Grid to the top side of the transfer switch.
2. Connect the essential loads to the bottom side of the transfer switch.
3. The neutral cable from the BACKUP terminal of the EP2000 cannot be connected to the neutral cable of the public grid.
The wiring connections are as follows:
| Source | Wire | Transfer Switch Terminal |
|---|---|---|
| Public grid | L1 | 1L1 |
| L2 | 3L2 | |
| L3 | 5L3 | |
| N | N | |
| EP2000 BACKUP terminal | L1 | 1L1 |
| L2 | 3L2 | |
| L3 | 5L3 | |
| N | N | |
| Essential loads | L1 | 2T1 |
| L2 | 4T2 | |
| L3 | 6T3 | |
| N | N |
Operation:
• Position “I” (ON): Use this position when the grid is stable. The BLUETTI EP2000 and public grid will power the loads. If the EP2000 ESS fails, you can still use the utility grid by turning the switch to “I”.
• Position “II” (ON): Use this position during a power outage. The EP2000 will power the essential loads in Backup mode.
• Position “OFF”: Disconnects the loads.
How do I connect PV cables to the BLUETTI EP2000?
Connecting PV (solar panel) cables to the BLUETTI EP2000 involves preparing the cables and connecting them to the correct terminals.
Cable Preparation and Connection:
1. Use cables with a cross-sectional area of 2.5-4mm².
2. Strip the ends of the positive and negative wires (about 7-9mm).
3. Crimp the positive and negative metal cores onto the corresponding wires using crimping pliers.
4. Assemble the MC4 connectors, ensuring the positive and negative connectors are correctly placed.
5. Tighten the connectors using an MC4 wrench.
Terminal Assignment:
The BLUETTI EP2000 has four PV inputs (PV1, PV2, PV3, PV4). For each input:
• PE: Connects to the Solar panel ground.
• PV+: Connects to the solar panel positive wire.
• PV-: Connects to the solar panel negative wire.
Important Note: Please check the open circuit voltage of the PV arrays, which should be between 240V and 1000V.
How do I connect and operate the EMS for the BLUETTI EP2000?
The Energy Management System (EMS) controller must be installed and connected to the BLUETTI EP2000 for system monitoring and control.
Installation:
1. Drill holes in the wall using the provided dimensions (136 mm apart horizontally, 663.8 mm apart vertically).
2. Insert expansion plugs into the holes.
3. Secure the mounting bracket to the wall with self-tapping screws.
4. Mount the EMS Controller onto the bracket and secure it with the fixing screw.
Connection:
1. Connect the EMS communication cable to the COM2 port on the BLUETTI EP2000 inverter.
2. The EMS also communicates with the grid meter via RS485. The connections are as follows:
| Connector Pin (COM2) | Function | Note (Meter RS485 communication) |
|---|---|---|
| 3 | RS485-B1 | Connects to grid meter and meter RS485-B- (black) |
| 4 | RS485-A1 | Connects to grid meter and meter RS485-A+ (red) |
Note: Make sure the router is set to IEEE 802.11 b/g/n 2.4GHz for wireless communication.
How do I connect the METER for the BLUETTI EP2000?
To connect the grid meter (METER) to your BLUETTI EP2000 system, follow these steps:
1. The Current Transformers (CTs) must be installed with the arrow inside the CT pointing towards the grid.
2. Ensure the correct phase sequence: connect the CT on grid line L1 to the meter’s GRID-L1 input, L2 to GRID-L2, and L3 to GRID-L3.
3. The CTs should be tied to the L1, L2, and L3 cables of the main circuit breaker of the grid.
4. For the communication cable between the meter and the EMS controller, connect the red wire (pin 4) to pin A on the meter and the black wire (pin 3) to pin B on the meter. Use a shielded twisted pair cable.
What are the typical application scenarios for the BLUETTI EP2000?
The BLUETTI EP2000 supports several application scenarios:
• DC coupling: Solar panels (PV) are directly connected to the EP2000’s DC inputs. The system manages power from the grid, PV, and the B700 battery to supply loads connected to a sub-panel.
• AC Coupling: An existing grid-tied PV system with its own PV inverter is connected to the main panel. The BLUETTI EP2000 is also connected to the main panel and provides backup power from the B700 battery to loads on a sub-panel.
• AC + DC Coupling: This is a hybrid setup that combines both DC-coupled solar panels connected directly to the EP2000 and an existing AC-coupled PV inverter system.
What are the specifications and notes for a DC coupling connection with the BLUETTI EP2000?
For a new solar panel installation connected in DC coupling mode with the BLUETTI EP2000, please note the following:
• Cables: Grid and Backup electric cables are recommended to be 10 mm² (AWG 6#).
• Grounding: In Australia, New Zealand, and South Africa, N and PE are connected together in the power distribution box. In this case, the PE of the BACKUP port of the EP2000 does not need to be connected.
• 1. Photovoltaic Inputs: The system has four inputs (PV1, PV2, PV3, PV4), with a maximum power of 9 kWp each.
• 2. MPPT Configuration:
– PV1 & PV2 share one MPPT; PV3 & PV4 share another.
– Each MPPT supports up to two strings, with a total maximum current of 30A, and each string up to 20A.
• 3. Y-Type Connectors:
– For photovoltaic arrays that are connected in parallel, Y-type connectors need to be selected.
– The parallel photovoltaic arrays must ensure the following consistency: same model, same number of panels, same tilt angle, same orientation angle.
What are the specifications and notes for an AC coupling connection with the BLUETTI EP2000?
For an existing solar roof connected in AC coupling mode with the BLUETTI EP2000, please note the following:
• Cables: Grid and Backup electric cables are recommended to be 10 mm² (AWG 6#).
• Grounding: In Australia, New Zealand, and South Africa, N and PE are connected together in the power distribution box. In this case, the PE of the BACKUP port of the EP2000 does not need to be connected.
• 1. Photovoltaic Inputs: The system has four inputs (PV1, PV2, PV3, PV4), with a maximum power of 9 kWp each (if used).
• 2. MPPT Configuration:
– PV1 & PV2 share one MPPT; PV3 & PV4 share another.
– Each MPPT supports up to two strings, with a total maximum current of 30A, and each string up to 20A.
• 3. Y-Type Connectors:
– For photovoltaic arrays that are connected in parallel, Y-type connectors need to be selected.
– The parallel photovoltaic arrays must ensure the following consistency: same model, same number of panels, same tilt angle, same orientation angle.
What are other typical application scenarios for the BLUETTI EP2000?
Beyond standard coupling, the BLUETTI EP2000 can be used in these scenarios:
• Backup power: The EP2000 is connected to the main panel and provides backup power from the B700 battery to essential loads on a sub-panel during a grid outage. It does not use solar input in this configuration.
• Off-grid: The EP2000 and B700 battery are charged by solar panels (PV) to power loads on a sub-panel completely independently of the utility grid.
• Parallel connection on the backup side: Two EP2000 systems can be connected in parallel to increase power output. Each system can have its own PV input and battery storage, and they work together to power the loads on a sub-panel.
• Integration with Manual Diesel Generator: A fuel generator can be integrated into the system as an additional power source for charging the battery and powering loads via the main panel, alongside the grid and PV input.
How do I power on the BLUETTI EP2000 system?
Follow these steps to safely power on your BLUETTI EP2000 system:
Step 1: Switch on the PV input switch on the EP2000 inverter.
Step 2: Switch the circuit breaker on the HV800 to “ON”. Press and hold the power button on the HV800 till the indicator on the button lights up green.
Step 3: Wait about 40 seconds for the inverter indicator to stay steady green.
Step 4: Switch on the AC circuit breakers for the inverter’s GRID block.
Step 5: Turn on “System Switch” in the BLUETTI app.
Step 6: Check the output voltage of the BACKUP block.
Step 7: Switch on the AC circuit breakers for the inverter’s BACKUP block.
Step 8: Monitor EP2000 system status using the BLUETTI app.
How do I interpret the indicator lights on the BLUETTI EP2000?
The indicator lights on the BLUETTI EP2000 show the system’s operational status. The panel has three lights: RUN (green), ALARM (orange), and FAULT (red).
| Situation | Run (Green Light) | Alarm (Orange Light) | Fault (Red Light) |
|---|---|---|---|
| Normal | ON | / | / |
| Alarm | ON | ON | / |
| Fault | / | / | ON |
| Alarm and fault | / | ON | ON |
CLICK HERE TO DOWNLOAD BLUETTI EP2000 (01) PDF DOCUMENT
