AZBIL MGG14C (01) Image

FREE ENGLISH AZBIL MGG14C (01) PDF DOCUMENT.
FREE ENGLISH AZBIL MGG14C (01) PDF USER GUIDE.
FREE ENGLISH AZBIL MGG14C (01) PDF USER MANUAL.
FREE ENGLISH AZBIL MGG14C (01) PDF OWNER GUIDE.
FREE ENGLISH AZBIL MGG14C (01) PDF OWNER MANUAL.
FREE ENGLISH AZBIL MGG14C (01) PDF REFERENCE GUIDE.
FREE ENGLISH AZBIL MGG14C (01) PDF INSTRUCTION GUIDE.
FREE ENGLISH AZBIL MGG14C (01) PDF REFERENCE MANUAL.
FREE ENGLISH AZBIL MGG14C (01) PDF INSTRUCTION MANUAL.
FREE ENGLISH AZBIL MGG14C (01) PDF OPERATING INSTRUCTIONS.


CLICK HERE TO DOWNLOAD AZBIL MGG14C (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

What do the safety conventions and icons in the user manual mean?

The safety precautions explained in the manual aim to prevent injury and property damage.

WARNING: Warnings are indicated when mishandling this product may result in death or serious injury.

CAUTION: Cautions are indicated when mishandling this product may result in minor injury or property damage only.

The manual also uses the following icons:

Triangle with exclamation mark: Indicates that caution is required in handling.

Circle with a diagonal line: The indicated action is prohibited.

Solid circle with exclamation mark: Be sure to follow the indicated instructions.


What are the key safety messages for installing and operating this device?

WARNING

ELECTRIC SHOCK HAZARD! Turn the power supply OFF before opening the converter cover.


CAUTION

Switch the control equipment to manual control before terminating flowmeter operation and shutting off the output to the control equipment. This action prevents the power shut-off from directly affecting the control equipment.

Install the flowmeter in a location with an ambient temperature of -25 °C to 60 °C (-13 °F to 140 °F) and an ambient humidity of 5 to 100% RH to prevent equipment malfunction or output errors.

Do not install the flowmeter near high-current power lines, motors or transformers to prevent damage from electromagnetic induction, which can cause equipment malfunction or output errors.

Do not install the flowmeter in a location subject to direct sunlight, wind, rain, severe vibration, or in a highly corrosive atmosphere. The converter and detector can be damaged.

Be sure to ground the welding power transformer when welding near the flowmeter to avoid output errors.

DO NOT use the flowmeter to ground a welder. It can damage the flowmeter.


What are the cautions for disposal of this equipment?

Disposal of Electrical and Electronic Equipment (for Environmental Protection)

This is an industrial product subject to the WEEE Directive.

Do not dispose of electrical and electronic equipment in the same way as household waste.

Old products contain valuable raw materials and must be returned to an authorized collection point for correct disposal or recycling.


What are the CE Conformity specifications for the flowmeter?

This product is in conformity with the protection requirements of the following European Council Directive: 2014/30/EU, the EMC Directive and 2014/35/EU, Low Voltage Directive. Conformity of this product with any other “CE Mark” Directive(s) shall not be assumed.

Performance Criteria: Immunity includes the tests and severity levels specified in EN 61326-1-2013 and EN 61326-2-3-2013.

Notes:

1. Twist pair cables required for all I/O interface circuits.

In case of remote model, two core double shield cable in metal conduit pipe is required for the input line in connection with detector.

EMC Directive/Standard PC Conformity Notes
ELECTROMAGNETIC COMPATIBILITY: 2014/30/EU, EMC Directive
EMISSIONS: EN61326-1:2013, Gr.1 Class A, Electrical equipment for measurement, control and laboratory use
EN 55011:2009/A1: 2010, Gr.1, Class A, Industrial Control Equipment, Radiated electromagnetic disturbances 30MHz – 1000MHz, 30MHz-230MHz quasi-peak limit 40dB(uV/m) at 10m
230MHz-1000MHz quasi-peak limit 47dB(uV/m) at 10m
1
IMMUNITY: EN61326-1:2013, Electrical equipment for measurement, control and laboratory use, EN 61326-2-3:2013, Particular requirements PERFORMANCE: Unless otherwise noted, the performance of this product, at the specified levels of electromagnetic interference, is within the specifications for for “Performance Under Rated Conditions.”
EN 61000-4-2: 2009, ESD, Electrostatic Discharge B
B
4 kV Contact
8kV Air
EN 61000-4-3:2006 + A2:2010, Radio-frequency electromagnetic field, amplitude modulated 80 – 2700 MHz A 1kHz, AM80%
10 V/m (80 -1000 MHz)
3V/m (1.0 -2.0 GHz)
1V/m (2.0 -2.7 GHz)
1
EN 61000-4-4:2012, Electrical Fast Transients/Burst B 1kV 1
EN 61000-4-5: 2006, Surge B 1kV 1
EN 61000-4-6:2009, Conducted Radio-frequency, 150 KHz – 80 MHz A 3V 1
EN 61000-4-8: 2010, Power frequency magnetic field A 30A/m
50Hz
1
EN 61000-4-11:2004, Voltage Dip/short interruptions B
C
C
C
0.5, 1cycle 0% (100%)
10/12 cycle 40% (60%)
25/30 cycle 70% (30%)
250/300 cycle 0% (100%)
LV Directive Conformity
LOW VOLTAGE DIRECTIVE: 2014/35/EU EN 61010-1: 2010+A1: 2019, Safety requirements for electrical equipment for measurement, control and laboratory use Part 1: General requirements

What do the power supply symbols on the name plate mean?

The symbol for a.c. or d.c. on the name plate is as follows:

~ (tilde): for a.c. power supply

— (dashed line): for d.c. power supply


What are the fuse specifications and can it be replaced?

The fuse cannot be replaced by the operator.

Fuse rating and electric characteristics are as follows:

Fuse rating: Voltage 250V

Current: 3A

Manufacturer type: 239003 (LITTEL FUSE)


How should the grounding (earthing) be connected?

Protective grounding (earthing) should be connected as shown in the Operator’s Manual. The MagneW FLEX+/PLUS+ has protective grounding (earthing) terminals in the terminal box and on the external surface of its casing.

An external switch or circuit-breaker must be installed near the MagneW FLEX+/PLUS+ on the power line.


What is the warning regarding equipment operation?

The power line is connected to commercial power. The terminal cover must not be opened when power is on.


What are the main components and types of the MagneW FLEX+/PLUS+ Flowmeter?

The model MGG10C/MGG14C MagneW FLEX+/PLUS+ Flowmeter consists of a detector and a converter which operate on the principles of Faraday’s law. There are two main configurations:

Integral: The converter is mounted directly on the detector and they are installed as an integrated unit on the fluid pipe.

Remote: The converter and detector are installed separately and connected together via cables.


What are the different output modes of the flowmeter?

The choice of either an analog output or digital output system configuration depends on whether you want to use the digitally enhanced (DE) communication mode.

Analog output (4 to 20 mA DC output): In analog mode, the flowmeter sends the instantaneous flow rate as a proportional 4 to 20 mA output signal to a controller or a recorder in the control system.

Digital output (DE output): A flowmeter in the DE mode can communicate in a direct digital fashion with Azbil Corporation or Honeywell DCS system. The digital signal can include flow rate, flowmeter database, and self-diagnostics.

Switching output mode: The analog/digital output mode is selectable.


How do I configure the system for analog output (4 to 20 mA DC)?

In analog mode, the flowmeter can be configured with or without SFC communications.

WITHOUT the communication function

The DC power supply that transmits the analog output is built into the product. The analog output signal is transmitted directly to the host control system.

• Analog output range: 0.8 to 22.4 mA (-20 to +115%)

• Resistive load: 0 to 600 Ω

WITH HART communication function

The DC power supply that transmits the analog output and HART communication is built into the product.

• Analog output range: 3.2 to 22.4 mA (-5 to +115%)

• Resistive load: 0 to 600 Ω

WITH the communication function (SFC or HART)

When using SFC communications, an external power supply (DC power) and external resistive load (minimum 250 Ω) are required. HART communication is also available with the external power supply and resistive load.

• Analog output range: 3.2 to 22.4 mA (-5 to +115%)

• DC power: 16 to 45V DC

• Maximum value of external resistive load is calculated as: (External power supply for communication – 8.5V) / 0.025

CAUTION: For systems WITH the SFC communication function, failure to install the external power supply and the external resistive load will prevent the analog output from being accepted on the receiving instrument side. Be sure to install the external power supply and the external resistive load as specified.


What are the main parts of the converter?

The converter consists of the following components:

Converter:

• Converts electromotive force by the detector to the flow rate signal.

• Transmits the analog output or the digital output as the flow rate signal.

Data setting device (A):

• Displays the flow rate and the totalized value.

• The Data can be configured through the four infrared sensor keys.

Terminal box (B):

• Encloses the inputs/outputs terminals.

• Equipped with lightning arrestor.

Name plate (C):

• Indicates model numbers, product numbers and the detector factor (EX).

Tag number plate (D):

• Indicates the tag number as specified in the product order.

CAUTION: Do not apply over-voltage that exceeds the following lightning arrestor specification. The converter may be damaged.

• Power supply terminal: series mode 1kV, common mode 2kV

• Input/Output terminal: series mode 1kv, common mode 1kV


What are the installation standards for the FM Nonincendive model?

If the basic model number is MGG14C, 1/2 NPT wiring connection is selected, and style code is selected as “N”, this device functions as an FM, non-incentive-approved model. The installation standards must be followed.

Installation of this device

FM Nonincendive model

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS(A, B, C, D), CLASS II/III, DIVISION 2, GROUPS (F, G), OR NON-HAZARDOUS LOCATIONS ONLY.

CAUTION

• Power supply and internal voltage of ordinary equipment to the earth shall not exceed AC250V 50/60HZ, DC250V in case of normal/formal conditions.

• Ambient temperature is from -25 to 60C.

• Process temperature is from -40 to 160C (Remote model).

• Process temperature is from -40 to 120C (Integral model).


Can an MGG18/19 detector be used with an MGG14C converter as an FM-approved nonincendive product?

If an MGG18/19 detector is used with an MGG14C converter as an FM-approved nonincendive product, both the detector and the converter should be FM-approved nonincendive products.

If they are not, the MGG18/19 detector cannot be used as an FM-approved nonincendive product.


What precautions should be taken when selecting an installation site?

WARNING: ELECTRIC SHOCK HAZARD! DO NOT perform wiring work while the power is ON!

CAUTION:

• Install the flowmeter in a location with an ambient temperature of -25 °C to 60 °C (-13 °F to 140 °F) and an ambient humidity of 5 to 100% RH to prevent equipment malfunction or output errors.

• Do not install the flowmeter near high-current power lines, motors or transformers to prevent damage from electromagnetic induction, which can cause equipment malfunction or output errors.

• Be sure to ground the welding power transformer when welding near the flowmeter to avoid output errors.

• DO NOT use the flowmeter to ground a welder. It can damage the flowmeter.

• Do not install the flowmeter on the bridge or deck of the ship.

• When installing the flowmeter, follow the instructions before and install it appropriately. Otherwise, the flow meter may be damaged.

• When installing a flowmeter for trial operation or inspection work, install it appropriately as described above. Otherwise, the flow meter may be damaged.

• Check the polarity of each wire before starting trial operation or inspection. Read the Note in the wiring section carefully before you start working. If the polarity of wiring is incorrect, it may damage the equipment.

• Be sure to return the flowmeter to an appropriate installation condition after installation of the flowmeter in trial operation or inspection work. Otherwise, the flow meter may be damaged.

• Both integral and separate detectors become heavier as the aperture increases. Please be careful when carrying or lifting. Otherwise, there is a risk of injury or damage to the flow meter.


How should the flowmeter be unpacked and stored?

The flowmeter is a precision instrument and should be handled with care. After unpacking, verify the following items are included:

• Model MGG10C/MGG14C converter

• Standard accessories

• MagneW setting data sheet

• Test report

Storage

When storing the flowmeter before use:

• Store indoors at room temperature (77 °F or 25 °C) within a humidity level of approximately 65%.

• Store away from vibration or shock.

• Store the converter and detector in the original packaging.

In addition, when storing the converter after use:

• Attach the display cover, Terminal box cover and Waterproof gland(s) to prevent moisture ingression into the device.


How can the orientation of the converter display be changed?

The display orientation can be changed from horizontal to vertical or vice versa.

To change the orientation of the converter:

1. Remove the four screws holding the display cover to the main body and remove the cover.

2. Remove the four screws holding the display panel to the main body.

3. Remove and rotate the display panel to the required orientation.

4. Replace the four screws and tighten.

5. Rotate the display cover so that the openings for the LEDs are correctly aligned with the Display Panel.

6. Replace the four screws and tighten.


What are the general precautions for wiring the flowmeter?

CAUTION

• Use electrical tube and duct to prevent water entry and protect the cable from external damage.

• Be sure to use a waterproof gland at the conduit connection to prevent water entry inside of the terminal box and prevent output errors.

• Turn off the power supply before connecting the cables to the converter. The converter can be damaged. This type of damage is not covered by the warranty.

• Be sure to plug all unused conduit connections with a water tight plug.

• In case that a remote model is installed in a ship, the cables between the converter and detector must be covered with a flexible metal conduit.


WARNING

• ELECTRIC SHOCK HAZARD! The AC POWER and XY terminals of the converter terminal block are high-voltage terminals. Turn off the power supply before connecting the cables to these terminals. When connecting, lift the protective cover which indicates “WARNING” sign. After connecting, return the protective cover to its original position.


CAUTION

• When connecting wires, check the polarity of each wire. If the polarity of wiring is incorrect, it may damage the equipment.

• Check the polarity of each wire before starting trial operation or inspection. If the polarity of wiring is incorrect, it may damage the equipment.

• Be sure to return to the correct wiring for the normal use after the trial operation or inspection. If the wiring is incorrect, it may damage the equipment.


What are the terminal descriptions for Integral wiring?

Note: In case of DC24V and DC110V power supply, the symbol of the “L” and “N” of the power supply become “+” and “–”.

Table: Remote converter terminal descriptions (1-contact input & 1-contact output)

SymbolDescription
I. OUT (+, -)Analog output
P. OUT (+, -)Pulse output
STATUS IN (+, -)Contact input
STATUS OUT (+, -)Contact output
ENot used
Ground SymbolGrounding (grounding resistance must be <100Ω)

Table: Remote converter terminal descriptions (2-contact input)

SymbolDescription
I. OUT (+, -)Analog output
P. OUT (+, -)Pulse output
STATUS IN 1 (+, -)Contact input 1
STATUS IN 2 (+, -)Contact input 2
ENot used
Ground SymbolGrounding (grounding resistance must be <100 Ω)

Table: Remote converter terminal descriptions (2-contact output)

SymbolDescription
I. OUT (+, -)Analog output
P. OUT (+, -)Pulse output
STATUS OUT 1 (+, -)Contact output 1
STATUS OUT 2 (+, -)Contact output 2
ENot used
Ground SymbolGrounding (grounding resistance must be <100 Ω)

What are the terminal descriptions for Remote wiring?

Note: In case of DC24V and DC110V power supply, the symbol of the “L” and “N” of the power supply become “+” and “–”.

Table: Remote converter terminal descriptions (1-contact input & 1-contact output)

SymbolDescription
A, B, C, SA, SBFlow rate signal input
I. OUT (+, -)Analog output
P. OUT (+, -)Pulse output
STATUS IN (+, -)Contact input
STATUS OUT (+, -)Contact output
X, YExcitation
ENot used
Ground SymbolGrounding (grounding resistance must be <100Ω)

Table: Remote converter terminal descriptions (2-contact input)

SymbolDescription
A, B, C, SA, SBFlow rate signal input
I. OUT (+, -)Analog output
P. OUT (+, -)Pulse output
STATUS IN 1 (+, -)Contact input 1
STATUS IN 2 (+, -)Contact input 2
X, YExcitation
ENot used
Ground SymbolGrounding (grounding resistance must be <100 Ω)

Table: Remote converter terminal descriptions (2-contact output)

SymbolDescription
A, B, C, SA, SBFlow rate signal input
I. OUT (+, -)Analog output
P. OUT (+, -)Pulse output
STATUS OUT 1 (+, -)Contact output 1
STATUS OUT 2 (+, -)Contact output 2
X, YExcitation
ENot used
Ground SymbolGrounding (grounding resistance must be <100 Ω)

What are the specifications for signal and excitation cables in remote installations?

Grounding CAUTION: ELECTRIC SHOCK HAZARD! Grounding is essential for accurate measurement. The grounding resistance must be less than 100 Ω.

For remote installations, the converter and detector are connected using dedicated cables (Model MGA12W) or commercially available cables. The cables between the detector and converter should be no longer than 300 m (984 ft.), but the actual length depends on the conductivity of the fluid being measured.

Cable Diameters:

Signal cable: 11.4 mm (0.45 in.), 0.75 mm² (.0011625 sq. in.) or equivalent commercially available cable (CVVS or CEEV, for example).

Excitation cable: 10.5 mm (0.41 in.), 2 mm² (.0031 sq. in.) or equivalent commercially available cable (CVV, for example).

Note: Strip the conductive tubing (black) down to the ends of the inner shields on the conductive wires for terminals A and B of the signal cable.


How should the wiring cable be selected and installed?

Selecting the cable:

• The recommended wiring cable is a 600V vinyl sheath electrical wire CVV (JIS C 3401) with a conductor section of 2 mm² (0.0031 inch²), or a twisted cable with an equivalent or higher capacity.

• Shielded wire is recommended for wiring at locations subject to electromagnetic noise interference.

• Select a sheath material suitable for the cable installation environment (consider ambient temperature, corrosive gas, corrosive fluid, etc.).

• Run the cable into the terminal block through the conduit connection (G1/2 internal thread, CM20 external thread, Pg13.5 or 1/2NPT internal thread). An outer diameter of φ11(0.433 inch) is optimum.

• A crimp terminal (M4 screw) with an insulation sleeve is recommended for the terminal connections.

• The maximum length of the wiring cable is 1500 m (4921 ft). However, the maximum length between converter and detector is 300 m (984 ft).

Wiring the cable:

• Run the wiring away from equipment that may generate noise, such as high-capacity transformers, motors, or power supplies. DO NOT install the cable in the same tray or duct as other power cables. Output errors may result.

• For water proofing and damage prevention of the wire, we recommend cabling work using conduits and ducts. Use a water proof cable gland.


How do I wire the analog, pulse, and contact I/O?

Analog Output Wiring:

The current output wiring method depends on HART or SFC communication. An external power supply is required to communicate with the SFC. Change dip switch settings only after turning the power supply OFF.

• Note: Check and confirm that the polarity of the wiring is correct. Incorrect polarity may cause damage to the equipment.

• In case of not using a communication function, the position of dip switch pins should be set as for HART communication. HART Communication works with the wiring for the SFC communication.

• The communication type (HART or SFC) must be specified when ordering. If changing the communication type, you must: 1) Change the switch position according to the communication type. 2) Change the communication type in the “COM SELECT” screen in the “Shipping Info” screen.


Pulse Output Wiring:

The pulse output is an open collector output. Pay close attention to voltage and polarity when wiring.

• Note: Check and confirm that the polarity of the wiring is correct. Incorrect polarity may cause damage. Use an external power supply that meets the voltage and capacity specifications. Pulse may be output when the power is turned ON or OFF. Pulse output protection circuit causes a voltage drop; some counters may not pick up the pulses due to this. In such a case, turn On S6 switch.


Contact Input Wiring:

Either a semi-conductive contact or a no-voltage contact can be used. The contact input terminals are not available when a 2-contact output model has been selected.


Contact Output Wiring:

Pay close attention to voltage and polarity when wiring for an open collector output.

• Note: Check and confirm that the polarity of the wiring is correct. Incorrect polarity may cause damage. Use an external power supply that meets the voltage and capacity specifications.


How do I set the write protection level?

Write protection settings control the level at which data confirmation and manipulation are possible. The system has four modes:

Basic setup mode: used to run the flowmeter on a day-to-day basis.

Engineering mode: used by those who are responsible for flowmeter configuration.

Maintenance mode: used when system maintenance is required.

Advanced mode: used to apply some specific noise immunity functions, and other advanced functions.

Settings are changed by setting the switch positions of the write protection switch on the main card. The following table shows the available levels:

Table 2-7 Write Protection Levels
Level Basic setup/Engineering mode Advanced mode Maintenance mode Remarks
0 Default setting
1 X
2 X
3 X

✓ – Both data confirmation and manipulation are possible.

– – Only data confirmation is possible.

X – Neither data confirmation nor manipulation are possible.

To set the write protection level:

1. Remove the four screws holding the display cover to the main body of the converter and remove the cover.

2. Locate the write protection switch.

3. Set the write protection switch positions to the required level of protection.


How do I set up communication via HART or SFC?

To set communication via HART:

1. Remove the four screws holding the display cover to the main body of the converter and remove the cover.

2. Locate the communication switch.

3. Make sure that position of the I switch (1-4) are ON and positions of the SFC switch (5-8) are OFF.

Note: Refer to the wiring diagram for current output for the wiring.


To set communication via SFC:

1. Remove the four screws holding the display cover to the main body of the converter and remove the cover.

2. Locate the communication switch.

3. Make sure that position of the I switch (1-4) are OFF and positions of the SFC switch (5-8) are ON.


How do I set the empty detection function?

This function fixes the analog output and latches the display to zero when the detector is empty.

To set the empty detection function:

1. Remove the four screws holding the display cover to the main body of the converter and remove the cover.

2. Locate the empty detection function switch.

3. Set the empty detection function switch positions to the required setting (ON or OFF).


How do I start up and shut down the flowmeter?

To start operation of the flowmeter:

1. Confirm that the detector is correctly installed on the pipe.

2. Confirm that the wiring between the converter and the detector has been properly completed. In case of using a HART/SFC communication function, verify an appropriate wiring.

3. Begin and then stop fluid flow through the detector so that fluid is present in the detector in a static condition.

4. Confirm that there is no leakage at the flanges of the detector.

5. Apply power to the converter.

6. The start-up display appears seven seconds after the power is ON.

7. Zero the flowmeter using the procedure on page 4-14 of the PDF.

The flowmeter is now on and operational.


To shut down the flowmeter:

CAUTION: Switch the control equipment to manual control before terminating flowmeter operation and shutting off the output to the control equipment. This action prevents the power shut-off from directly affecting the control equipment and causing the valve positioner to malfunction.

1. Switch the control equipment connected to the flowmeter to manual control.

2. Turn off power to the converter.


What are the functions of the display panel and infrared touch sensor keys?

Display Panel Features:

Main display: Indicates the flow rate selected in basic setup mode.

Auxiliary display: Shows supplementary values like a different flow rate, totalized value, or parameter setting procedures.

Percent flow display: When lit, indicates the percent flow rate is displayed on the Main display.

Actual flow rate display: When lit, indicates the actual flow rate is displayed on the Main display.

Totalized value display: When lit, indicates the totalized value is displayed on the Main display.

LCD display: Shows all values and settings.


Using the Infrared Touch Sensor Keys:

For best results, approach the key from below and completely cover the circle. Then move your finger straight down to its original position. Moving sideways across the keys can accidentally activate the wrong control.

Table: Touch Sensor key Functions

key Function
MODE key Touching and holding this key for more than three seconds opens Basic setup MODE. Writes data into memory after changing parameters in engineering, maintenance, or advanced mode.
RIGHT SHIFT key Shifts the cursor in the display to the right.
DOWN key When the cursor is on the Mode Indicator, it displays the next screen. When the cursor is on a number, it decrements the number. When the cursor is on a decimal point, it moves the decimal point to the right.
UP key When the cursor is on the Mode Indicator, it displays the next screen. When the cursor is on a number, it increments the number. When the cursor is on a decimal point, it moves the decimal point to the left. When the cursor is at READY, it starts the operation.

What are the default settings of the flowmeter?

Table 3-2 Default settings
Parameter Default Parameter Default
TAG XXXXXXXX HI-ALM +115%
DAMPING 3.0s LO-ALM -115%
SPAN as specified FALL SAFE MODE LOW
DISPLAY SELECT as specified ST. OUT MODE CLOSE
HYSTERESIS 0 AVERAGING OFF
GRAVITY 1.0000 COEFFICIENT 1.0000
PLS SCL (PULSE SCALE) as specified or 1.0000 l/p DROP OUT 2%
PLS WID (PULSE WIDTH) DUTY 50 LOW FLOW CUT OFF

What are the different modes of operation and their functions?

The flowmeter has five modes of operation. CAUTION: The CALIBRATION MODE and ADVANCED MODE contain adjustments and operations that are very important for proper flow rate measurement. Improper settings in these modes will prevent measurement.

Table 4-1 Mode functions
Mode Description
MEASURING MODE This is the normal operational mode. Each time this mode is selected, data is written into memory. Settings entered in other modes are held in temporary memory for two minutes but will revert unless MEASURING MODE is selected to save.
BASIC SETUP MODE
(Mode indicator: *)
Used to change data settings that must be recorded or changed frequently. Includes: TAG NO., Damping time constant, Display select, Auto zero, Flow rate range, Detector data, Built-in counter reset/preset.
ENGINEERING MODE
(Mode indicator: #)
Used to change data settings that are used less frequently. Includes: Function setting, Flow rate range, Pulse data, Fail safe mode setting.
MAINTENANCE MODE
(Mode indicator: >)
Used when adjustment or verification is required for regular maintenance or troubleshooting. Includes: Shipping information, Output adjustment, Gain adjustment. This mode is further divided into OUTPUT CHECK MODE and CALIBRATION MODE.
ADVANCED MODE
(Mode indicator: &)
Used to apply some specific noise immunity functions. Includes: Damping, Manual zero, Averaging, Auto spike Cut, Coefficient, Drop out, Low-flow cut off, Flow direction change.

How do I perform an auto zero calibration?

This function adjusts the flowmeter so that the measured flow rate is zero when the fluid is in a static condition inside the detector.

CAUTION:

• Before operating the flowmeter for the first time, be sure to carry out auto zero. Zero adjustment is very important for accurate flow measurement.

• Before performing auto zero calibration, make sure the detector is properly grounded (resistance < 100 Ω), filled with the fluid to be measured, and the fluid is in static condition. Zero adjustment is possible with a flow speed of 0.2 m/s or less, but 0.0 m/s is required for accurate adjustment. If conditions cannot be guaranteed, the auto zero function should be ignored.

Procedure:

1. Enter the BASIC SETUP MODE.

2. Use the UP or DOWN key to cycle through the screens until the AUTO ZERO screen appears.

3. Touch the RIGHT SHIFT key once to move the cursor to READY, indicating the system is ready for zeroing.

4. Touch the UP key once to select READY and start the auto zero adjustment. The large numerical display flashes and READY changes to ON. When complete, flashing stops and ON changes back to READY. The adjustment takes approximately 60 to 100 seconds.

5. Touch the RIGHT SHIFT key until the cursor is back at the mode indicator. Touch the MODE key and hold for three seconds to return to MEASUREMENT MODE to save the zero setting.


How to perform function checks like analog output, pulse output, and contact I/O loop checks?

Function checks use the electromagnetic flowmeter as a constant-current or pulse generator to check the output signal loop and other instruments like recorders and controllers.

Note: If no operation is done for ten minutes, the output check mode automatically finishes and returns to the Measuring mode.

Analog output check (000.0 to 115.0%):

1. Enter MAINTENANCE MODE. Cycle screens until “OUTPUT CHECK” appears. Touch RIGHT SHIFT to move cursor to “OFF”. Touch UP key to switch to ON screen.

2. Touch RIGHT SHIFT to move the cursor to the percent value.

3. Use UP or DOWN key to set the desired value (e.g., 100% for 20mA).

4. Touch RIGHT SHIFT to move the cursor to “>”.

5. Use UP or DOWN key to move to another screen. The analog output will return to the measured flow rate value.

Pulse output check (000.0 to 115.0%):

1. Enter MAINTENANCE MODE. Navigate to “OUTPUT P. OUT” screen.

2. Touch RIGHT SHIFT to move the cursor to the percent value.

3. Use UP or DOWN key to set the desired value (e.g., 100% for the equivalent pulse rate).

4. Touch RIGHT SHIFT to move the cursor to “>”.

5. Use UP or DOWN key to move to another screen. The pulse output will return to the measured flow rate value.

Contact input/output loop check (“CLOSE”, “OPEN”):

1. Enter MAINTENANCE MODE and navigate to the “OUTPUT CHECK ST. IN/OUT” screen.

2. The display will show the current status of the contact input (e.g., OPEN/CLOSE).

3. To test the output, touch RIGHT SHIFT to move the cursor to the output status.

4. Use the UP key to select the desired output status (OPEN/CLOSE) and verify the loop responds correctly.


How do I check the excitation current?

This function is used to check the excitation current.

1. Enter MAINTENANCE MODE. Cycle to “OUTPUT CHECK” screen, turn it ON, and then cycle to “EX CHECK” screen. The excitation current will run from X to Y. Verify the current is 160mA.

2. Touch the UP key once to move the cursor at the “E” of “EXX”.

3. Touch the UP key once, then the excitation current runs from Y to X.

4. Touch the UP key once, then the excitation current stops.

5. Touch the RIGHT SHIFT key once to move the cursor to “>”.

6. Use the UP or DOWN key to move to the other screen. Then the excitation current is added to the coil to measure the flow rate.


How do I use a simulated signal from a calibrator?

The model MGZ14 and F1X calibrators can be used to input a simulated signal to check the converter function.

Preparation:

• Calibrator and cables

• Digital voltmeter

• Resister (250 Ω)

Check the converter by following the user’s manual of the calibrator.

CAUTION:

When using the MGZ calibrator (S/W version 1.6 or earlier) with converter models MGG10C-M… or MGG14C-M…, you must connect the cables as indicated in the drawings in the manual. If not, the calibrator may not work properly.

If the X,Y cable from the detector is not connected together with the X,Y cable of the MGZ calibrator, upgrade the S/W version of MGZ from the current version to 1.7 or later.


What should I do if errors occur at startup?

Table 5-1 Startup Errors
Symptom Check Points and Treatment
No display after power on. • Check the converter power supply specification and ensure that the power supply being supplied meets these requirements.
• Make sure the ambient temperature is not below -25 °C (13 °F).
No output after power-on. • Verify that the signal line is correctly connected.
Communication can not be done. • Check the switch position.
• Check if the wiring is properly completed.
• Check if the SFC is properly connected.
• Check if the S/W version of the SFC is Ver.7.0 or later.
• Check if the HART communicator is 375. Check if the DD file is downloaded.
No pulse output. • Check the wiring of the pulse output loop.
• Check the receiving device specifications (pulse width, frequency, voltage drop).
• Check if the pulse output is open collector type or Drive counter.
Output remains 0mA. • Verify that power source and power supply voltage.
• Verify the wiring.

What should I do if errors occur during operation?

Table 5-2 Operation Errors
Symptom Check Points and Treatment
Output fluctuates excessively beyond the estimated flow rate range. • Verify that the detector is properly grounded.
• Verify that the converter is properly grounded.
• Verify that the damping time constant is set correctly. If not, set an appropriate damping time constant.
• Clean the electrodes.
Flow rate exceeds the flow range • Check the flow range setting and make sure it is set to match the detector and process flow. If not, set an appropriate RANGE.
• Check that the flowmeter has been zeroed. If not, calibrate the flowmeter.
Output exceeds 100%. • Verify that the set range is set correctly.
• Verify that the span is set correctly.
• Verify that the zero point is correctly adjusted.
• Verify that the converter is correctly calibrated.
Output remains 0%. • The pipe may be empty. Use the empty detection function to check whether or not the pipe is empty. (If it is empty, the empty detection function will be functioning.)
• Verify that the signal cable is correctly connected.
• Verify that the valves are open on the upper and lower sides.
• Verify that the span is set correctly.
• Verify that the converter is set to the constant current mode.
• Verify that the flow rate is not in the low flow cutoff range.
Output is in the fail-safe mode. • Check the error code.
Pulse output is too large or too small. • Verify if the pulse weight and width are set correctly.
• Verify the converter is correctly calibrated.
• Verify the pulse counter is proper.
• Verify the dropout value is correctly set between 0 and 10%.

What are the critical error codes and their solutions?

Critical problems can disrupt flowmeter operation. An error message will appear, and the flowmeter will output the preset fail-safe value. If the problem persists after trying these solutions, contact technical support.

Table 5-3 Critical Errors
Error Screen Error Solution
Err-01 EX CHECK ERROR EX check Error (Excitation circuit is open.) • Check connection of terminal/wiring of X and Y.
• Check if the resistance of coil is less than 50 Ω. (Coil resistance is to be checked between X and Y terminal of a detector.)
• Cycle power.
Err-02 ROM CHECK ERROR ROM check error • Cycle power.
• Replace the ROM.
• Replace main card.
Err-03 RAM CHECK ERROR RAM read after write error • Cycle power.
• Replace main card.
Err-04 NUM CHECK ERROR NVM read after write error • Cycle power.
• Replace main card.
Err-05 ADC CHECK ERROR ADC error A/D change error • Cycle power.
• Replace main card.

What are the non-critical error codes and their solutions?

Non-critical problems do not seriously disrupt flowmeter operation; the flowmeter continues to output the flow rate. If the problem persists after trying these solutions, contact technical support.

Table 5-4 Non-critical
Error Screen Error Solution
Err-11 TYPE-DIA MATCHING ERROR Detector type and diameter do not match. • Check the setting for the detector diameter and enter the correct diameter.
Err-12 SETTING ERROR HI High/low limit alarm error. HI < LO • Set HI > LO.
Err-21 SPAN ERROR OVER 12m/s The span setting is greater than 12 m/s. • Check the SPAN setting.
• Check the DIA setting.
• Check the TYPE setting
• Check the DUMMY setting.
Err-22 PULSE WEIGHT SETTING ERROR The pulse frequency is either too high or too low. • Check the pulse weight setting.
• Check the pulse frequency setting.
• Check the engineering unit match span unit.
Err-23 PULSE WIDTH OVER DUTY 70% Pulse width too large. Duty 70% or more at pulse frequency output. • Check 1. Pulse width
2. Pulse weight and
3. Span setting
Err-24 HYSTERESIS SETTING ERROR Hysteresis exceeding 100% of range in normal/reverse automatic range • Check hysteresis setting.

What are the safety precautions when using the Smart Field Communicator (SFC)?

WARNING: Denotes a potentially hazardous situation, which if not avoided could result in death or serious injury.

CAUTION: Denotes a potentially hazardous situation which if not avoided could result in minor injury or damage to the device.


CAUTION

• Set the loop of the electromagnetic flow meter whose setting is to be changed to “manual” before starting communication with the SFC. Its output may change due to a communication signal, affecting the operation or control of the plant.

• Do not throw the battery for the SFC into fire. This may result in explosion.

• Be sure to remove the AC adapter for the SFC from the socket if it is not used. The AC adapter may be over heat.


CLICK HERE TO DOWNLOAD AZBIL MGG14C (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.