TOSHIBA RAV-GV1601ATP-E (01) Image

FREE ENGLISH TOSHIBA RAV-GV1601ATP-E (01) PDF DOCUMENT.
FREE ENGLISH TOSHIBA RAV-GV1601ATP-E (01) PDF USER GUIDE.
FREE ENGLISH TOSHIBA RAV-GV1601ATP-E (01) PDF USER MANUAL.
FREE ENGLISH TOSHIBA RAV-GV1601ATP-E (01) PDF OWNER GUIDE.
FREE ENGLISH TOSHIBA RAV-GV1601ATP-E (01) PDF OWNER MANUAL.
FREE ENGLISH TOSHIBA RAV-GV1601ATP-E (01) PDF REFERENCE GUIDE.
FREE ENGLISH TOSHIBA RAV-GV1601ATP-E (01) PDF INSTRUCTION GUIDE.
FREE ENGLISH TOSHIBA RAV-GV1601ATP-E (01) PDF REFERENCE MANUAL.
FREE ENGLISH TOSHIBA RAV-GV1601ATP-E (01) PDF INSTRUCTION MANUAL.
FREE ENGLISH TOSHIBA RAV-GV1601ATP-E (01) PDF OPERATING INSTRUCTIONS.


CLICK HERE TO DOWNLOAD TOSHIBA RAV-GV1601ATP-E (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

What type of refrigerant does the TOSHIBA RAV-GV1601ATP-E air conditioner use?

The TOSHIBA RAV-GV1601ATP-E air conditioner adopts the HFC refrigerant (R32), which does not destroy the ozone layer. This outdoor unit is designed exclusively for use with R32 refrigerant and must be used in combination with an R32 refrigerant indoor unit.


Are there any specific electrical supply requirements for the TOSHIBA RAV-GV1601ATP-E?

Yes, this equipment complies with IEC 61000-3-12, provided that the short-circuit power Ssc is greater than or equal to 1,600 kVA at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user to ensure, by consulting with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to this value.

The required Ssc (kVA) values are as follows:

Model Ssc (kVA)
Single system Twin system
RAV-GV1601ATP-E 1,600 1,600

What are the safety cautions for the installation space of the TOSHIBA RAV-GV1601ATP-E outdoor unit?

To prevent fire hazards from refrigerant leaks, please adhere to the following installation space instructions:

• If the outdoor unit is installed in a small space, a refrigerant leak could lead to an accumulation of highly concentrated refrigerant, creating a fire hazard. Always follow the installation space instructions in the manual and provide open space on at least one of the four sides of the outdoor unit.

• If both the discharge and intake sides face walls, and obstacles are present on the other two sides, you must provide a space wide enough for a person to pass (600 mm or more) on one side. This is to prevent the accumulation of leaked refrigerant.


How should the TOSHIBA RAV-GV1601ATP-E be disconnected from the main power supply?

The TOSHIBA RAV-GV1601ATP-E appliance must be connected to the main power supply by means of a switch that has a contact separation of at least 3 mm.

Additionally, do not wash the air conditioner with pressure washers, as electric leaks may cause electric shocks or fires.


What accessory parts are included with the TOSHIBA RAV-GV1601ATP-E outdoor unit?

The following accessory parts are supplied with the outdoor unit:

Part name Q’ty Shape Usage
Installation Manual 1 Booklet For hand this directly to the customer.
Drain nipple 1 Component
Waterproof rubber cap 5 Cap
Protective bush 1 Ring For protecting wires (pipe cover)
Guard material for passage part 1 Material For protecting passage part (pipe cover)
Safety Manual 1 Booklet For hand over directly to the customer.

What precautions should be taken when installing an R32 refrigerant air conditioner like the TOSHIBA RAV-GV1601ATP-E?

When installing the TOSHIBA RAV-GV1601ATP-E, please observe the following precautions:

• This air conditioner uses HFC refrigerant (R32). During installation, ensure that water, dust, former refrigerant, or refrigerant oil does not enter the R32 refrigerant cycle.

• To prevent mixing of refrigerant or oil, the connecting sections of the charge port on the main unit and installation tools are different from those of conventional refrigerant units.

• Special tools are required for R32 or R410A refrigerant units.

• For connecting pipes, use new and clean piping materials with high-pressure fittings made for R32 or R410A only, to prevent water and/or dust from entering.

• If you are using existing piping, refer to the “Existing piping” section in the appendix.


What tools and equipment are required to install the TOSHIBA RAV-GV1601ATP-E?

The following tools and equipment are required for installation. Newly prepared tools must be used exclusively for R32 refrigerant.

Tools / equipment Use How to use tools / equipment
Gauge manifold Vacuuming / charging refrigerant and operation check Conventional tools (R410A)
Charging hose Conventional tools (R410A)
Charging cylinder Can not be used Unusable (Use the electronic refrigerant charging scale)
Gas leak detector Charging refrigerant Conventional tools (R32 or R410A)
Vacuum pump Vacuum drying Conventional tools (R32 or R410A). Usable if the backflow prevention adapter is installed.
Vacuum pump with backflow prevention function Vacuum drying Conventional tools (R32 or R410A)
Flare tool Flare machining of pipes Conventional tools (R410A)
Bender Bending pipes Conventional tools (R410A)
Refrigerant recovery equipment Refrigerant recovery Conventional tools (R32 or R410A)
Torque wrench Tightening flare nuts Conventional tools (R410A)
Pipe cutter Cutting pipes Conventional tools (R410A)
Refrigerant cylinder Charging refrigerant Prepared newly (Use for R32 only)
Welding machine and nitrogen cylinder Welding pipes Conventional tools (R410A)
Electronic refrigerant charging scale Charging refrigerant Conventional tools (R32 or R410A)

What are the requirements for refrigerant piping for the TOSHIBA RAV-GV1601ATP-E?

For refrigerant piping, please adhere to the following requirements:

Material: Use seamless phosphorous deoxidized copper pipe.

Wall Thickness:

• Ø6.35, Ø9.52, Ø12.7: Wall thickness 0.8 mm or more

• Ø15.88: Wall thickness 1.0 mm or more

Flaring:

• Incomplete flaring can cause refrigerant gas leakage.

• Do not re-use flares. Use new flares to prevent refrigerant gas leakage.

• Use flare nuts that are included with the unit. Using different flare nuts may cause refrigerant gas leakage.

Support: If the refrigerant pipe is long, provide support brackets at intervals of 2.5 to 3 m to clamp the refrigerant pipe to prevent abnormal sounds.

Pipe Length:

• The length of the refrigerant pipe connected to the indoor/outdoor unit should be between 5 to 30 m.

• Do not connect a refrigerant pipe that is shorter than 5 m, as this may cause a malfunction of the compressor or other devices.


How do I perform an airtight test and air purge for the TOSHIBA RAV-GV1601ATP-E?

Airtight test:

1. Before starting, further tighten the spindle valves on the gas and liquid sides.

2. Pressurize the pipe with nitrogen gas charged from the service port to the design pressure of 4.15 MPa to conduct the test.

3. After the airtight test is complete, evacuate the nitrogen gas.

Air purge:

• To purge air, use a vacuum pump.

• Do not use refrigerant charged in the outdoor unit to purge air. (The air purge refrigerant is not contained in the outdoor unit.)


What are the requirements for electrical wiring and earthing for the TOSHIBA RAV-GV1601ATP-E?

Electrical wiring:

• Fix the power wires and system interconnection wires with clamps to prevent them from contacting the cabinet, etc.

Earthing (Grounding):

• WARNING: Make sure that proper earthing is provided. Improper earthing may cause an electric shock. Contact the dealer or a professional installation company for details on how to check earthing.

• Proper earthing prevents charging of electricity on the outdoor unit surface and prevents electric shock. If the outdoor unit is not properly earthed, you may be exposed to an electric shock.

• WARNING: Be sure to connect the earth wire. Incomplete grounding can cause an electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods, or ground wires for telephone wires.


What are the ideal installation locations for the TOSHIBA RAV-GV1601ATP-E outdoor unit?

Install the outdoor unit in a location that meets the following conditions, after obtaining the customer’s consent:

• A well-ventilated location free from obstacles near the air intakes and air discharge.

• A location that is not exposed to rain or direct sunlight.

• A location that does not increase the operating noise or vibration of the outdoor unit.

• A location that does not produce any drainage problems from discharged water.

• When the outdoor unit is installed in an elevated position, be sure to secure its feet.

• A location in which drain water poses no problems.

CAUTION: Do not install the outdoor unit in a location that is subject to combustible gas leaks. Accumulation of combustible gas around the outdoor unit may cause a fire.


Where should the TOSHIBA RAV-GV1601ATP-E outdoor unit NOT be installed?

Do not install the outdoor unit in the following locations:

• A location with a saline atmosphere (coastal area) or one that is full of sulfide gas (hot-spring area), as special maintenance is required.

• A location subject to oil, vapor, oily smoke, or corrosive gases.

• A location in which organic solvent is used.

• Places where iron or other metal dust is present. If metal dust collects on the interior of the air conditioner, it may spontaneously combust and start a fire.

• A location where high-frequency equipment (e.g., inverter equipment, private power generator, medical equipment) is used, as it may cause malfunction or problems due to noise.

• A location in which the discharged air of the outdoor unit blows against the window of a neighboring house.

• A location where the operating noise of the outdoor unit is transmitted.


What are the space requirements for installing the TOSHIBA RAV-GV1601ATP-E outdoor unit?

The following are the necessary space requirements (in mm) for installation:

Obstacle at rear side only (Upper side is free):

• At least 150 mm from the rear side.

Obstacles on both right and left sides:

• At least 150 mm from the rear side.

• At least 300 mm from the side with the service connections.

• The height of the obstacle should be lower than the height of the outdoor unit.

Serial installation of two or more units (side-by-side):

• At least 150 mm from the rear side.

• At least 300 mm between units.

• At least 300 mm on the end units’ outer sides.

• The height of the obstacle should be lower than the height of the outdoor unit.

Obstacle also above unit:

• At least 150 mm from the rear side.

• At least 500 mm from the top.

Obstacle in front (Upper side is free):

• At least 500 mm from the front for a single unit.

• At least 1,000 mm from the front for serial installation.

Obstacles in both front and rear of unit (Standard installation):

• Single unit: At least 150 mm from the rear, 1,000 mm from the front.

• Serial installation: At least 200 mm from the rear, open above and to the sides. For front obstacles, maintain 1,000 mm, 1,500 mm, or 2,000 mm depending on configuration, with 300 mm space between units.

The height of an obstacle in both the front and rear of the unit should be lower than the height of the outdoor unit.


How do I properly flare the copper pipes for the TOSHIBA RAV-GV1601ATP-E?

Follow these steps for flaring:

1. Cut the pipe with a pipe cutter. Be sure to remove any burrs, as they may cause a gas leak.

2. Insert a flare nut (supplied with the air conditioner or one for R32/R410A) onto the pipe, and then flare the pipe.

CAUTION:

• Do not scratch the inner surface of the flared part when removing burrs. Scratches can cause refrigerant gas leaks.

• Check that the flared part is not scratched, deformed, stepped, or flattened, and has no chips adhered to it.

• Do not apply refrigerating machine oil to the flare surface.

The tables below show the required projection margin (B) and final flaring diameter (A).

Projection margin in flaring: B (Unit: mm)

Outer dia. of copper pipe R32/R410A tool used Conventional tool used
9.5 0 to 0.5 1.0 to 1.5
15.9

Flaring dia. size: A (Unit: mm)

Outer dia. of copper pipe A (+0 / -0.4)
9.5 13.2
15.9 19.7

How do I tighten the connecting pipe flare nuts on the TOSHIBA RAV-GV1601ATP-E?

1. Align the centers of the connecting pipes and fully tighten the flare nut with your fingers. Then, fix the nut with a wrench and tighten it with a torque wrench to the specified torque.

2. For the valve on the gas side, you must use two wrenches to loosen or tighten the flare nut. For the liquid side, you can use a single crescent wrench.

CAUTION:

• Do not put the crescent wrench on the valve cap or cover, as the valve may break.

• If you apply excessive torque, the nut may break.

• After installation, check for gas leaks at the pipe connections using nitrogen.

• Do not apply refrigerating machine oil to the flared surface.

Tightening torque (Unit: N•m)

Outer dia. of copper pipe Tightening torque
9.5 mm (dia.) 34 to 42 (3.4 to 4.2 kgf•m)
15.9 mm (dia.) 63 to 77 (6.3 to 7.7 kgf•m)

What are the allowable pipe lengths and height differences for a single system TOSHIBA RAV-GV1601ATP-E?

Allowable pipe length (m) Height difference (Indoor-outdoor H) (m)
Total length L Indoor unit: Upper Outdoor unit: Lower
30 30 30
Pipe diameter (mm) Number of bent portions
Gas side Liquid side
Ø15.9 Ø9.5 10 or less

How do I perform an airtight test and check for gas leaks on the TOSHIBA RAV-GV1601ATP-E?

After completing the refrigerant piping work, perform an airtight test by connecting a nitrogen gas cylinder and pressurizing the pipes.

CAUTION: Never use oxygen, flammable gas, or noxious gas for the airtight test.

Gas leak check steps:

Step 1: Pressurize to 0.5 MPa (5 kg/cm²G) for 5 minutes or longer. Major leaks can be discovered.

Step 2: Pressurize to 1.5 MPa (15 kg/cm²G) for 5 minutes or longer. Major leaks can be discovered.

Step 3: Pressurize to 4.15 MPa (42 kg/cm²G) for 24 hours. Micro leaks can be discovered.

Note: If the ambient temperature changes, the pressure will change by approximately 0.01 MPa per 1°C. This should be compensated for. If pressure drops, check connections for leakage with foaming liquid, fix any leaks, and repeat the airtight test.

After the airtight test is completed, evacuate the nitrogen gas.


How do I perform an air purge using a vacuum pump on the TOSHIBA RAV-GV1601ATP-E?

Use a vacuum pump to evacuate air from the connecting pipes. Be sure to use a vacuum pump with a backflow preventer.

1. Connect the charge hose from the manifold valve (closed) to the charge port of the set.

2. Open the Handle Low on the manifold fully.

3. Turn ON the vacuum pump.

4. Loosen the flare nut of the packed valve (Gas side) slightly to check that air passes through.

5. Retighten the flare nut.

6. Continue vacuuming until the compound pressure gauge indicates -101 kPa (-76 cmHg).

7. Close the Handle Low on the manifold completely.

8. Turn OFF the vacuum pump.

9. Leave it for 1-2 minutes and check that the indicator of the compound pressure gauge does not return (rise).

10. Fully open the valve stem or valve handle (first at liquid side, then gas side).

11. Disconnect the charge hose from the charge port.

12. Securely tighten the valve and caps of the charge port.


What is the pump down process for the TOSHIBA RAV-GV1601ATP-E?

The pump down process is used to recover refrigerant into the outdoor unit.

1. Turn off the Air Conditioner system.

2. Connect the charge hose from the manifold valve to the service port of the packed valve on the gas side.

3. Turn on the Air Conditioner system in cooling operation for more than 10 minutes.

4. Check that the operating pressure is normal.

5. Release the valve rod cap of both service valves.

6. Use a hexagon wrench to fully close the valve rod of the liquid side.

7. Continue operating the air conditioner until the manifold gauge drops into the range of 0.5 – 0 kgf/cm².

8. Use a hexagon wrench to fully close the valve rod of the gas side and immediately turn off the Air Conditioner system.

9. Remove the gauge manifold from the service port.

10. Securely tighten the valve rod cap to both service valves.

CAUTION: During the pump down process, check the compressor operating condition. If any abnormal sound or vibration occurs, turn off the Air Conditioner immediately.


How do I open the service valves on the TOSHIBA RAV-GV1601ATP-E?

Fully open the valves of the outdoor unit. First, fully open the valve on the liquid side, and then fully open the valve on the gas side.

• Do not open or close the valves when the ambient temperature is -20°C or less, as this may damage the valve O-rings and result in refrigerant leakage.

Liquid side: Open the valve with a 4 mm hexagon wrench.

Gas side: Open the valve with a 5 mm hexagon wrench.

Valve handling precautions:

• Open the valve stem until it strikes the stopper.

• Securely tighten the cap with a torque wrench.

Cap tightening torque:

Valve size Tightening Torque
Ø9.5 mm 34 to 42 N•m (3.4 to 4.2 kgf•m)
Ø15.9 mm 34 to 42 N•m (3.4 to 4.2 kgf•m)
Charge port 14 to 18 N•m (1.4 to 1.8 kgf•m)

What are the power supply specifications and wire requirements for the TOSHIBA RAV-GV1601ATP-E?

Model RAV- GV1601
Power supply 220-240 V~, 50 Hz
220 V~, 60 Hz
Maximum running current 27.40 A
Installation fuse rating 32 A (all types can be used)
Power supply wire H07 RN-F or 60245 IEC 66 (4 mm² or more)
Indoor/Outdoor connecting wires H07 RN-F or 60245 IEC 66 (1.5 mm² or more)

The stripping length for the power cord and connecting wires should be 10mm for the conductors, with overall specified lengths as shown in the manual diagrams.


What are the operating temperature conditions for the TOSHIBA RAV-GV1601ATP-E?

For proper performance, operate the air conditioner under the following temperature conditions. If used outside of these conditions, safety protection may activate.

Cooling operation Dry bulb temp. -15 °C to 46 °C
Heating operation Wet bulb temp. -15 °C to 15 °C

How should I handle annual maintenance for the TOSHIBA RAV-GV1601ATP-E?

For an air conditioning system that is operated on a regular basis, cleaning and maintenance of the indoor/outdoor units are strongly recommended.

As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor/outdoor units will need to be cleaned at least once every 3 months. This cleaning and maintenance should be carried out by a qualified service person.

Failure to clean the indoor/outdoor units regularly will result in poor performance, icing, water leaking, and even compressor failure.


How do I perform a refrigerant recovery on the TOSHIBA RAV-GV1601ATP-E?

DANGER: The P.C. board is a high-voltage area. When operating the service switches with power on, wear electrically insulated gloves. Operate the switches with the electric parts cover in place.

Follow these steps to recover the refrigerant:

1. Operate the indoor unit in fan mode.

2. Check that the LED displays are in their initial status (D805 is ON). If not, hold down SW01 and SW02 simultaneously for at least 5 seconds to return them to the initial status.

3. Hold down SW01 for at least 5 seconds, and check that D804 flashes slowly.

4. Press SW01 once to set the LED displays to the “refrigerant recovery LED display” (D800, D801, D802, D803 are OFF; D804 is slow flashing; D805 is ON).

5. Press SW02 to set D805 to rapid flashing. (Each press switches D805 between rapid flashing and OFF).

6. Hold down SW02 for at least 5 seconds. When D804 flashes slowly and D805 lights up, the forced cooling operation starts (Max. 10 minutes).

7. After operating the system for at least 3 minutes, close the valve on the liquid side.

8. After the refrigerant has been recovered, close the valve on the gas side.

9. Hold down SW01 and SW02 simultaneously for at least 5 seconds. The LED displays will return to the initial status, and the cooling and indoor fan operations will stop.

10. Turn off the power.

If you doubt the success of the recovery, hold down SW01 and SW02 simultaneously for at least 5 seconds to return to the initial status, then repeat the steps.


How do I interpret the LED display and check codes for troubleshooting the TOSHIBA RAV-GV1601ATP-E?

You can perform fault diagnosis using the LEDs (D800-D805) on the outdoor unit’s P.C. board. The display patterns correspond to specific errors. (● = ON, ○ = OFF, ● = Rapid flashing)

No. Error D800 D801 D802 D803 D804 D805
1 Normal
2 Discharge temperature sensor (TD) error
3 Heat exchanger temperature sensor (TE) error
4 Heat exchanger temperature sensor (TL) error
5 Outside air temperature sensor (TO) error
6 Suction temperature sensor (TS) error
7 Heat sink temperature sensor (TH) error
8 Heat exchanger sensor (TE, TS) connection error
9 EEPROM error
10 Compressor breakdown
11 Compressor lock
12 Current detection circuit error
13 Case thermostat operation
14 Model data not set
15 Discharge temperature error
16 Power supply error
17 High pressure SW error
18 Heat sink overheating error
19 Gas leak detected
20 4-way valve reverse error
21 High pressure release operation
22 Fan system error
23 Drive device short-circuiting
24 Position detection circuit error
25 Compressor IPDU or other (not specifically identified)

Can I reuse existing R22 or R410A piping for the TOSHIBA RAV-GV1601ATP-E?

Yes, existing R22 and R410A piping can be reused for the R32 TOSHIBA RAV-GV1601ATP-E, but only if specific conditions are met. You must confirm there are no scratches or dents and verify the pipe strength.

Basic conditions needed to reuse existing pipes:

1. Dry: There is no moisture inside the pipes.

2. Clean: There is no dust inside the pipes.

3. Tight: There are no refrigerant leaks.

Restrictions for use of existing pipes (Do not reuse if any of the following apply):

• Scratches or dents are heavy.

• Pipe thickness is thinner than specified below.

• The outdoor unit was left with pipes disconnected for a long period.

• Refrigerant cannot be recovered using a recovery unit (indicating dirty oil or moisture).

• A commercially available dryer is attached to the pipes.

• Refrigerant oil is discolored (e.g., green copper rust), has a large quantity of residue, or a bad smell.

• The previous air conditioner had a compressor failure and replacement.

• The previous system was used for temporary installations (e.g., leased).

• The refrigerator oil of the existing system is not Suniso, Freol-S, MS, alkyl benzene, ester series, or PVE of ether series.

Pipe diameter and thickness (mm)

Pipe outer diameter Ø6.4 Ø9.5 Ø12.7 Ø15.9 Ø19.0
Thickness R32/R410A 0.8 0.8 0.8 1.0 1.0
R22

What are the specifications of the TOSHIBA RAV-GV1601ATP-E?

Model Sound power level (dBA) Weight (kg)
Cooling Heating
RAV-GV1601ATP-E 74 76 64

How do I fill out and affix the Fluorinated Greenhouse Gases Label for the TOSHIBA RAV-GV1601ATP-E?

1. Stick the enclosed refrigerant label adjacent to the service ports for charging/recovering or next to the existing nameplate.

2. Using indelible ink, clearly write the charged refrigerant quantity on the label in the designated fields:

• **①:** Pre-charged refrigerant at factory [kg] (found on the nameplate).

• **②:** Additional charge on installation site [kg].

• **①+②:** Total refrigerant quantity [kg].

• **③:** Total quantity in tonnes of CO2 equivalent, calculated as (GWP x kg) / 1000. For R32, the GWP is 675.

3. Place the included transparent protective sheet over the label to protect the writing.


CLICK HERE TO DOWNLOAD TOSHIBA RAV-GV1601ATP-E (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.