What is the SCHIER CA2?
The SCHIER CA2 is an adapter designed for a 24″ corrugated pipe riser system.
What is the unit weight of the SCHIER CA2?
The unit weight of the SCHIER CA2 is 22 lbs.
What is the part number for the SCHIER CA2?
The part number for the SCHIER CA2 is 8010-011-01.
What are the outer dimensions of the SCHIER CA2 riser adapter?
The SCHIER CA2 riser adapter side view specifications indicate the following dimensions:
Top outer diameter: 29″
Inner opening diameter: 23-1/2″
Bottom inner lip diameter: 26″
Total adapter height: 5-1/4″
What components make up the SCHIER CA2 riser adapter system according to the engineer specifications?
The SCHIER CA2 24″ corrugated pipe riser adapter system consists of:
1. A rotomolded polyethylene riser adapter.
2. Butyl mastic sealant for tank-riser and riser-adapter joints.
3. Corrosion resistant steel fastening hardware.
4. Heavy-duty nylon cable ties.
What are the minimum and maximum height requirements for a SCHIER CA2 corrugated riser system installation?
The corrugated riser system must be installed with a minimum height of 6″ and must not exceed a maximum height of 94″.
Does the SCHIER CA2 riser system compromise access to internal components?
No, access to internal components will not be compromised when using the SCHIER CA2.
Can the SCHIER CA2 riser be used to hold or retain water?
No, the riser is not designed to hold or retain water.
Is air testing allowed on the SCHIER CA2 unit or riser system?
No. Do not air test the unit or riser system. Doing so may result in property damage, personal injury, or death.
Can lubricant be applied to the riser tube during installation of the SCHIER CA2?
No, do not add any form of lubricant to the riser tube during installation.
Can backfill be compacted around the SCHIER CA2 system?
No, do not compact backfill around the unit.
What condition must parts be in when applying mastic sealant to the SCHIER CA2?
Make sure all parts are clean when applying the mastic sealant.
What concrete slab thickness is required for below-grade pedestrian traffic or greenspace areas when installing the SCHIER CA2?
For pedestrian traffic or greenspace areas, a concrete slab with rebar having a minimum thickness of 4″ is required to finished grade.
What concrete slab thickness is required for below-grade vehicular traffic areas when installing the SCHIER CA2?
For vehicular traffic areas, a concrete slab with rebar having a minimum thickness of 8″ is required to finished grade.
What are the special precautions for high water table installations involving the SCHIER CA2?
Interceptors and risers are not designed to withstand water table height in excess of the top of the unit when buried. If it is possible for this to occur, install the interceptor and risers in a watertight concrete vault or backfill with concrete or flowable fill (wet concrete and flowable backfill should be poured in stages to avoid crushing the interceptor). Direct buried units in high water table scenarios must be installed with an anchor kit.
What areas are considered at-risk for high water tables when installing the SCHIER CA2?
At-risk areas include, but are not limited to, tidal surge areas, floodplains, and areas that receive storm water.
What is required if the SCHIER CA2 is installed under a hydrostatic or pressure slab?
When installed under a hydrostatic slab (a slab designed to withstand upward lift, usually caused by hydrostatic pressure), the interceptor must be enclosed in a watertight concrete vault.
What items and parts are included in the SCHIER CA2 package?
The SCHIER CA2 package includes:
1. #12 x 4″ self-tapping screws (quantity: 4)
2. Riser adapter (quantity: 1)
3. 1″ square x 80″ block butyl mastic sealant (quantity: 2)
4. Heavy-duty 18″ – 120 lb. cable ties (quantity: 4)
5. 1/4″-20 x 5/8″ hexhead bolts (quantity: 4)
6. 1/4″ ID oversize washers (quantity: 4)
7. 90 degree angle brackets (quantity: 4)
What additional items are required for the SCHIER CA2 installation that are not included?
The following items are not included with the SCHIER CA2:
A. Cover adapter (with cover)
B. Cover adapter gasket assembly
C. 24″ corrugated pipe riser (supplied by others)
D. Interceptor accessway
What tools are needed to install the SCHIER CA2?
The tools required for installation are:
1. Tape measure
2. #2 Phillips head screwdriver
3. Reciprocating saw, circular saw, or jigsaw
4. Drill with 1/2″ chuck
5. 3/8″ drill bit
6. Level
7. 5/16″ socket driver
8. 7/16″ nut driver bit (included with interceptor)
How do you determine the riser height needed for the SCHIER CA2?
With the cover adapter in the factory set position, measure dimension X from the top of the interceptor accessway to finished grade to determine the riser height needed.
How do you calculate the trim height for the 24″ corrugated pipe used with the SCHIER CA2?
Subtract 4″ from the riser height needed (dimension X – 4″) to determine the corrugated pipe trim height. Then mark and cut the corrugated pipe.
Why is the 24″ corrugated pipe cut 4″ shorter than the total riser height needed?
Trimming the riser using these guidelines results in a riser that is roughly 1-1/2″ shorter than the exact riser height needed, allowing cover adapter adjustability for final adjustments to grade.
What tool is used to loosen the cover adapter lower band clamps?
A 7/16″ nut driver bit is used to loosen the cover adapter lower band clamps.
How are the angle brackets attached to the interceptor accessway for the SCHIER CA2?
First, remove the plugs from the 4 threaded inserts around the interceptor accessway. Then, use a 7/16″ nut driver to attach the 4 angle brackets using the 1/4″-20 hexhead bolts and oversize 1/4″ washers.
Where is the butyl mastic sealant placed on the interceptor accessway?
Lay the butyl mastic sealant into the channel surrounding the accessway, aligned on center with the inner wall of the riser.
How is the 24″ corrugated pipe riser initially positioned on the interceptor?
Place the riser into position over the accessway and press it firmly into the mastic seal.
What holes must be drilled into the corrugated riser pipe for securing it with the SCHIER CA2 hardware?
Using a drill with a 3/8″ bit, drill 4 pairs of 3/8″ holes in the outer wall of the riser above each angle bracket: one hole in the sidewall and one hole on the top edge of the first rib above the angle brackets.
How are cable ties installed through the corrugated pipe riser and angle brackets?
Loop the heavy-duty cable ties through the drilled holes in the riser rib and through the angle brackets, leaving them loose initially without tightening.
What tightening procedure and pattern should be used for the cable ties on the SCHIER CA2?
Tighten the cable ties a little bit at a time going around the riser following the tightening pattern (1, then opposite side 2, then perpendicular 3, then opposite side 4) to evenly force the riser into the mastic sealant. Do not tighten completely right away to allow room for final adjustments.
Where do you place the butyl mastic sealant when installing the SCHIER CA2 riser adapter onto the riser?
Lay the butyl mastic sealant onto the top rib of the corrugated riser pipe, aligned on center with the bottom edge of the riser adapter.
How is the SCHIER CA2 riser adapter set onto the corrugated pipe?
Place the riser adapter into position on top of the corrugated pipe and press firmly into the mastic sealant.
How is the SCHIER CA2 riser adapter secured to the corrugated riser pipe?
Secure the riser adapter to the riser pipe using four #12 x 4″ self-tapping screws. Insert the screws into the pre-drilled holes in the riser adapter and drill/screw them into the riser rib using a 5/16″ socket driver.
When are final adjustments made to ensure the riser is level?
After securing the riser adapter to the riser pipe, check with a level and make final tightening adjustments to the lower cable ties to ensure the riser is level.
How is the cover adapter and gasket assembly installed onto the SCHIER CA2?
Place the cover adapter / gasket assembly onto the top of the riser adapter system.
What is the required torque for the cover adapter lower band clamp?
Tighten the lower band clamp to 5 to 8 ft. lbs. of torque using a 7/16″ nut driver bit.
What is the minimum insertion depth required when adjusting the cover adapter to grade?
A minimum insertion depth of 2-1/2″ must be maintained when adjusting the cover adapter height.
How do you adjust the cover adapter height to match finished grade?
Loosen the cover adapter upper band clamp using a 7/16″ nut driver bit, adjust the cover adapter height as needed to bring the cover flush to grade while maintaining at least a 2-1/2″ insertion depth, and then retighten the upper band clamp to 5 to 8 ft. lbs. of torque.
What is the required torque for the cover adapter upper band clamp on the SCHIER CA2?
Tighten the upper band clamp to 5 to 8 ft. lbs. of torque using a 7/16″ nut driver bit.
What are the complete step-by-step instructions for installing the SCHIER CA2?
Step 1: Determine riser height and cut 24″ corrugated pipe.
1a. With the cover adapter in the factory set position, measure dimension X to determine riser height needed.
1b. Subtract 4″ from the riser height needed to determine corrugated pipe trim height (X – 4″). Mark and cut the corrugated pipe.
Step 2: Install riser onto grease interceptor.
2a. Loosen the cover adapter lower band clamps using a 7/16″ nut driver bit.
2b. Remove cover adapters.
2c. Remove plugs from the 4 threaded inserts around the interceptor accessway. Use a 7/16″ nut driver to attach the angle brackets with the 1/4″-20 hex bolts and oversize 1/4″ washers.
2d. Lay butyl mastic sealant into the channel surrounding the accessway, aligned on center with the inner wall of the riser.
2e. Place riser into position and press firmly into mastic seal.
2f. Drill 4 pairs of 3/8″ holes in the outer wall of the riser above each angle bracket (one hole in the sidewall and one hole on the top edge of the first rib above the angle brackets).
2g. Loop cable ties through holes drilled in the riser rib and the angle brackets; do not tighten.
2h. Tighten cable ties a little bit at a time going around the riser (pattern 1-2-3-4) to evenly force the riser into the mastic sealant without tightening completely.
Step 3: Install riser adapter onto riser.
3a. Lay butyl mastic sealant onto the top rib of the corrugated riser pipe, aligned on center with the bottom edge of the riser adapter.
3b. Place riser adapter into position and press firmly into the mastic sealant.
3c. Secure riser adapter to riser pipe using four #12 x 4″ self-tapping screws into pre-drilled holes using a 5/16″ socket driver.
3d. Make final tightening adjustments to cable ties using a level to ensure riser is level.
Step 4: Install cover adapters onto risers.
4a. Place cover adapter / gasket assembly onto top of riser system.
4b. Tighten lower band clamp to 5 – 8 ft. lbs. of torque using a 7/16″ nut driver bit.
4c. Loosen the cover adapter upper band clamp using a 7/16″ nut driver bit.
4d. Adjust cover adapter height as needed to bring cover flush to grade, maintaining a minimum 2-1/2″ insertion depth.
4e. Tighten upper band clamp to 5 – 8 ft. lbs. of torque using a 7/16″ nut driver bit.
What are the specifications and components included with the SCHIER CA2?
The specifications and components are summarized in the following table:
| Component / Specification | Detail / Value |
|---|---|
| Product Model | SCHIER CA2 |
| Part Number | 8010-011-01 |
| Description | Adapter for 24″ Corrugated Pipe Riser |
| Unit Weight | 22 lbs. |
| Minimum Riser Height | 6″ |
| Maximum Riser Height | 94″ |
| Self-Tapping Screws | (4) #12 x 4″ |
| Riser Adapter | (1) Rotomolded polyethylene |
| Butyl Mastic Sealant | (2) 1″ square x 80″ blocks |
| Cable Ties | (4) Heavy duty 18″ – 120 lb. |
| Hexhead Bolts | (4) 1/4″-20 x 5/8″ |
| Washers | (4) 1/4″ ID oversize |
| Angle Brackets | (4) 90 degree brackets |
| Clamp Torque Spec | 5 – 8 ft. lbs. |
| Minimum Insertion Depth | 2-1/2″ |