RAKO WRA-232 (01) PDF MANUAL


Post questions, comments, reviews or errors in the comment box below.

Your File is Ready … Download PDF

CLICK HERE TO DOWNLOAD RAKO WRA-232 (01) PDF MANUAL


PDF Content Summary: WRA-232 User Manual What is WRA-232 WRA-232 will send and receive RS-232 messages with Rako systems. WRA-232 works with Rako Wired or Wireless systems. WRA-232 has Ethernet port for configuration only. Power supply * Power supply is not required if WRA-232 is used with a Rako Wired system * Note: WRA-232 will operate with Wired and Wireless systems. However, it cannot be used to link a Wired System to a Wireless system. Use WA-Bridge or WTC-Bridge for that function. Send & receive RS232 messages Send Wireless messages to dimmers Receive Wireless messages from Wall plates Send & receive messages from Rako Wired system Use a Web Browser to view the WRA-232 control panel. Getting started with WRA-232 Some initial setup of WA-Bridge is needed. • First, Plug the Power Supply into the WRA-232 and apply power. The Blue LED on the WRA- 232 circuit board will start to blink. • Plug the Ethernet patch cable from the WA-Bridge to a spare port on a wireless router. • Use a normal web browser (eg Internet Explorer) to connect to the RTC-Bridge via the router.

Use a laptop to connect to the RTC-Bridge The WRA-232 URL is rako232bridge Or rako232bridge.local

Basic Configuration of the WRA-232 For WRA-232 to operate correctly with a RAKO system some initial setup must be performed. This is done using a PC and the RJ45 configuration connector. Set Wireless House Number Click the Configuration button on the WRA-232 control panel. Login User Name = admin Password = microchip Set the House number to match Rako Wireless system If the WRA-232 is used on a Rako WIRED system then change this Device Number. See Notes on next page This option can be used to Disable the Wireless transmitter & receiver on the WRA-232. See notes on next page. WRA-232 Device Numbers This setting is important when the WRA-232 is used with a Rako Wired system. In the Wired system all Bridges, Wall Controllers, RAK-Links etc have unique identifiers. It is important that no two items in the same logical Room have the same Device numbers. The WRA-232 default room is Room 1000. This room number is also used by WRA-Bridges and WA- Bridges. If there is a WA or WRA Bridge on the system then be sure that the WRA-232 and the other Bridge have different device numbers. Disabling the WRA-232 Wireless Do not have two Bridges on the same system which both have Wireless enabled. This will cause messages from one Bridge to be received by the other causing several repeats of the same message to occur. It is common for a WRA-232 to be in the same system as a RA-Bridge, RTC-Bridge, WA-Bridge or WTC-Bridge. If this is the case, then disable the WRA-232 wireless. Using WRA-232 with RS-232 The Rako WRA-232 uses the following configuration: 9600 baud, No Parity, 8 Data bits, 1 stop bit The flow control should be set to Xon/Xoff or None. Command Line Interface The interface indicates it is waiting for a command by issuing the “>” character. Characters sent to the interface are echoed. The interface interprets text commands and, where necessary, encodes and transmits the appropriate message via the radio link. The interface is not case sensitive. Each command consists of the following: [COMMAND] <VALUE> The command is terminated with a carriage-return character and, depending of the command, has an additional argument. The argument is delimited by one or more white-spaces, tabs or colons. If the Command is valid, the interface responds with: OK If the command is invalid, the interface responds with: Invalid Command! It is not necessary to enter the full text of the command. A shortened non-ambiguous version can be used. For example the command HOUSE:1 can be shortened to HO:1. Command Summary Command Notes ROOM [<room_number>] Sets the ROOM address to <room_number>. The Room number must be between 0 and 255. Room 0 controls all units with the same House address. If <room_number> is omitted, the room is set to 0. The Room address is stored in non-volatile memory. CHANNEL [<Channel_Number>] Selects the Channel address. The <channel_number> must be between 0 and 15. Channel 0 controls all channels within the current Room. If <Channel_Number> is omitted the channel is set to 0. SCENE <scene number> Sets the scene for the current House/Room/Channel. The <scene number> must be between 1 and 4, which correspond to the buttons on a control panel. OFF Turns off the lights in the current House/Room/Channel. LEVEL <Power_level> Sets the power level for the current House/Room/Channel. The <power_level> must be between 0 and 255, with 255 representing 100% power. STORE Stores the current power level to the current Scene. This will only apply to dimmers addressed by the current House/Room/Channel. RESET Resets the microcontroller. VER Displays version information STATUS Displays current House, Room and Channel in the form: HO:nnn RO:nnn CH:nnn nnn is 3 digit decimal number with leading zeros. nnn is between 0 and 255.

Command Notes COMMAND [<command_number>] Issues <command_number> to the lights in the current House/Room/Channel. The <command_number> must be between 0 and 15. ADDRESS <EEPROM_address> Sets the EEPROM address within the dimmers. The (EEPROM_address> must be between 0 and 127. DATA <EEPROM_data> Transmits <EEPROM_data> to the address set using the ADDRESS command. The <EEPROM_data> must be between 0 and 255. NOECHO Turns off character echoing. This command is only available on the Bi-directional RS232 interface. The current echo mode is stored in non-volatile memory. ECHO Turns on character echoing. This command is only available on the Bi-directional RS232 interface. The current echo mode is stored in non-volatile memory. Table 1 – Command Line Interface Command Number Summary Using the COMMAND instruction, a literal command can be sent to the addressed controllers. Table 2 details the meanings of the various instructions. Instruction Number Instruction Program mode instruction 0 off 1 light+ light+ 2 light- light- 3 ps1 Store + Ident 4 ps2 ch+ 5 ps3 ch- 6 ps4 7 program mode 8 ident ident 9 10 low battery low battery 11 eeprom write eeprom write 12 level set level set 13 store Store 14 exit 15 STOP STOP Table 2- Command Instructions To fade the lights the command light+ or light- must be issued. This fades the lights at the rate determined by the value stored within the dimmer. To stop the lights fading the STOP command needs to be issued. EEPROM Addresses Information is stored in the dimmers in non-volatile or EEPROM memory. This memory can be written to using the RS232 interface. The EEPROM consists of 128 bytes of storage, some of which is used internally by the dimmer to remember the current state. ONLY THE ADDRESSES DETAILED BELOW SHOULD BE WRITTEN TO. To write data to the EEPROM area it if first necessary to set the HOUSE,ROOM and CHANNEL address of the dimmer(s). Next, the address should be set using the ADDRESS command and finally, the data should be written using the DATA command. ADDRESS EEPROM Action Notes 1 Scene 1 preset value 2 Scene 2 preset value 3 Scene 3 preset value 4 Scene 4 preset value 9 Start Mode (After power failure) 0=0ff 1-4 = Scene 5=Memory 6-255=Absolute power level 22 Ignore Program Mode >0= Ignore 23 Ignore Group Commands >0 = Ignore 24 Ignore House Commands >0 = Ignore 26 Use Profile >0 = use profile 34 Scene Fade Rate 0=fast 36 Scene Fade Decay Rate 0=no decay 40 Manual Fade Rate Max Sets the maximum rate 48 Manual Fade Rate Acceleration Sets the acceleration to maximum rate 50 Manual Fade Rate Start Sets the starting fade rate 63-127 Profile Data Determines the dimmers profile These values should only be changed using the RASOFT software. Table 3- EEPROM Addresses Care should be taken when changing values if the channel or room number is set to zero as this will change the values on all the dimmers. Bi-Directional operation The Rako® Bi-directional RS232 interface works as both a transmitter and receiver of Rako coded messages. Using this module it is possible to interface a Rako lighting installation to an external system where the system can both control the lighting and be aware of buttons being pressed on Rako devices. In addition to accepting the commands defined in Table 1, the Rako® Bi-directional RS232 interface will output received commands in the following format: <RRR:CC:IN Where RRR represents the decimal room number from 0-255, CC indicates the channel number 0-15 (0 being ‘all channels’) and IN indicates the instruction as set out in Table 2- Command Instructions. The string will always be on a separate line, start with a “<” and terminate with a CR LF. The unit will only output messages for the current house. The house address must first be set using as described in the “Table 1Basic Configuration” section. The following sequence represents a controller in room 4. Note: the text in italics is for explanation and does not appear on the output. <004:00:03 Scene 1 button pressed. > <004:00:10 Battery low indication. > <004:00:01 Fade up button pressed. > <004:00:15 Fade up button released. > <004:00:10 Battery low indication. > Command Examples: This section details some typical command line examples. The ‘>’ character is issued by the interface as is the ‘OK’ response. Note that the commands are not case sensitive, shortened versions of the commands and various delimiters can be used. The house and room address are stored in EEPROM within the WRA-232 and do not require resetting should a power failure occur. To set the dimmers in room 4 to scene 1 >RO:4 OK >CH:0 OK >SC:1 OK For all the dimmers in room4, set the Start-Mode such that the lights will be at 50% following a power failure. >ro 4 OK >ch 0 OK ADD 9 OK Dat 127 OK


FREE ENGLISH PDF

OPERATING INSTRUCTIONS

USER GUIDE - USER MANUAL

OWNER GUIDE - OWNER MANUAL

REFERENCE GUIDE - REFERENCE MANUAL

INSTRUCTION GUIDE - INSTRUCTION MANUAL

Leave a Reply