What are the control modes supported by the MOKWEIR MK100?
The MOKWEIR MK100 supports two control modes:
1. Sensorless vector control (SVC)
2. Voltage/Frequency (V/F) control
What is the startup torque specification for the MOKWEIR MK100?
The startup torque for the MOKWEIR MK100 is:
0.25 Hz/150% when using Sensorless Vector Control (SVC).
1.0 Hz/100% when using Voltage/Frequency (V/F) control.
What are the environmental requirements for installing the MOKWEIR MK100?
The MOKWEIR MK100 should be installed under the following conditions:
Installation Location: Indoors, protected from direct sunlight, dust, corrosive or combustible gases, oil smoke, vapour, ingress from water or any other liquid, and salt.
Altitude: Below 1000 m (de-rate if above 1000 m; maximum 3000 m for LVD directive requirement).
Operation Temperature: -10°C to +50°C (de-rate if outside this range).
Storage Temperature: -20°C to +60°C.
Humidity: Less than 95% RH non-condensing.
Vibration: Less than 5.9 m/s² (0.6 g).
Pollution Degree: PD2.
Overvoltage Category: OVC III.
What are the main loop terminal functions on the MOKWEIR MK100?
The main loop terminals of the MOKWEIR MK100 function as follows:
R, S, T / L, N: Three-phase AC input terminal / single-phase AC input terminal.
+DC, PB: Brake resistance connecting terminal.
U, V, W: Three-phase AC output terminal.
Earth terminal symbol: Earth connection.
How do the control board jumper switches function on the MOKWEIR MK100?
The jumper settings for the MOKWEIR MK100 control board are:
AI1 current / voltage input mode selection: Set to ‘I’ for 0 to 20mA current signal, or ‘V’ for 0 to +10V voltage signal (Factory default: 0 to +10V).
AI2 current / voltage input mode selection: Set to ‘I’ for 0 to 20mA current signal, or ‘V’ for 0 to +10V voltage signal (Factory default: 0 to +10V).
AO output current / voltage type selection: Set to 0/4 to 20mA for current output signal, or 0/2 to +10V for voltage output signal (Factory default: 0 to +10V).
485 terminal resistance selection: Set to ON for 120 ohm terminal resistor, or OFF for no terminal resistance (Factory default: No terminal resistance).
What are the functions of the control board terminals on the MOKWEIR MK100?
The control terminals for the MOKWEIR MK100 are defined as follows:
+485- : RS485 communication interface differential signal positive and negative ends.
AI1-GND: Analog input 1 (DC 0V to 10V or 0 to 20mA based on jumper; input impedance 22k ohm).
AI2-GND: Analog input 2 (DC 0V to 10V or 0 to 20mA based on jumper; input impedance 22k ohm).
AO1-GND: Analog output (voltage 0V to 10V or current 0mA to 20mA based on jumper).
X1 to X5: Multifunctional digital input terminals 1 to 5 (optical coupling isolation, bipolar input compatible, 2.4k ohm impedance, 9V to 30V level range; X5 supports high-speed pulse up to 100 kHz).
SEL: External power input terminal.
24V: +24V power supply output.
COM: +24V power supply common end (internally isolated from GND).
Y1-COM: Digital output 1 (open-collector optical coupling isolation, 0V to 24V, 0mA to 50mA).
10V-GND: External +10V power supply output (maximum 10mA, used for 1k ohm to 5k ohm potentiometer).
TA / TC: Programmable relay output contacts.
What are the functions of the operation panel keys on the MOKWEIR MK100?
The keys on the MOKWEIR MK100 operation panel provide the following operations:
PRG: Programming state entry and exit.
ENTER: Function code menu switch, data modification confirmation.
Up Arrow: Increment of data or function code.
Down Arrow: Decrement of data or functional codes.
Shift Key (Right Arrows): Selects which parameter digit is modified.
RUN: Starts operation when in keypad control mode.
STOP/RESET: In keypad control, stops running; resets fault alarm state in keypad or terminal control.
JOG: Multifunction selection key configured by parameter P7-01.
What do the keyboard indicator lights indicate on the MOKWEIR MK100?
The indicator states on the MOKWEIR MK100 keyboard signal the following:
RUN Always on: Frequency converter in operation.
RUN Always off: Frequency converter stop output.
Hz Always on: Displaying frequency.
L/R Always on: Operating under keypad control.
L/R Always off: Operating under terminal control.
L/R Twinkles: Operating under communication control.
A Always on: Displaying current.
V Always on: Displaying voltage.
Hz and A both always on: Displaying speed in rpm.
Hz and V both always on: Displaying percentage (%).
How is the command source selected using parameter P0-02 on the MOKWEIR MK100?
Parameter P0-02 selects the command source for the MOKWEIR MK100:
0: Keypad control (Default)
1: Terminal control
2: Communication control
What are the available settings for main frequency source X via parameter P0-03 on the MOKWEIR MK100?
Parameter P0-03 sets the main frequency reference channel on the MOKWEIR MK100:
0: Digital setting P0-08 (non-retentive at power down)
1: Digital setting P0-08 (retentive at power down)
2: AI1
3: AI2
4: Keyboard knob
5: Pulse reference (X5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication reference
How do you configure the acceleration and deceleration time unit via parameter P0-19 on the MOKWEIR MK100?
Set parameter P0-19 on the MOKWEIR MK100 as follows:
0: 1 second unit (setting range: 0 to 65000 seconds)
1: 0.1 second unit (setting range: 0.0 to 6500.0 seconds, default setting)
2: 0.01 second unit (setting range: 0.00 to 650.00 seconds)
How do you perform motor auto-tuning using parameter P1-37 on the MOKWEIR MK100?
To perform auto-tuning on the MOKWEIR MK100, set parameter P1-37 to one of the following:
0: No auto-tuning (Default)
1: Static auto-tuning 1
2: Complete dynamic auto-tuning
3: Static auto-tuning 2
Ensure motor parameters P1-00 to P1-05 are entered accurately prior to tuning.
What V/F curves are available in parameter P3-00 on the MOKWEIR MK100?
Parameter P3-00 on the MOKWEIR MK100 provides the following curve options:
0: Linear V/F
1: Multi-point V/F
2: Square V/F
3: 1.2-power V/F
4: 1.4-power V/F
6: 1.6-power V/F
8: 1.8-power V/F
9: Reserved
10: V/F complete separation
11: V/F half separation
What terminal command modes are configured by parameter P4-11 on the MOKWEIR MK100?
Parameter P4-11 selects the terminal control mode on the MOKWEIR MK100:
0: Two-wire control mode 1 (Default)
1: Two-wire control mode 2
2: Three-wire control mode 1
3: Three-wire control mode 2
What are the default terminal functions for digital inputs X1 through X5 on the MOKWEIR MK100?
The default terminal functions for the MOKWEIR MK100 are:
X1 (P4-00): 1 (Forward RUN – FWD)
X2 (P4-01): 2 (Reverse RUN – REV)
X3 (P4-02): 4 (Forward JOG – FJOG)
X4 (P4-03): 12 (Multi-reference terminal 1)
X5 (P4-04): 13 (Multi-reference terminal 2)
How do you set the digital input active mode (high level or low level) in parameter P4-38 on the MOKWEIR MK100?
Parameter P4-38 uses a 5-digit number to configure active polarities for X1 through X5 on the MOKWEIR MK100:
0: High level active
1: Low level active
The individual digit positions correspond to:
Units position: X1 active mode
Tens position: X2 active mode
Hundreds position: X3 active mode
Thousands position: X4 active mode
Ten thousands position: X5 active mode
Default value: 00000.
What start modes can be selected using parameter P6-00 on the MOKWEIR MK100?
Parameter P6-00 determines the start mode of the MOKWEIR MK100:
0: Direct startup (Default)
1: Reserved
2: Pre-excited startup (asynchronous motor)
What stop modes are configurable with parameter P6-10 on the MOKWEIR MK100?
Parameter P6-10 on the MOKWEIR MK100 provides two stop mode options:
0: Decelerate to stop (Default)
1: Coast to stop
How is the JOG key configured using parameter P7-01 on the MOKWEIR MK100?
Parameter P7-01 allows the JOG key on the MOKWEIR MK100 keypad to perform the following actions:
0: JOG key disabled
1: Switchover from remote control (terminal or communication) to keypad control
2: Switchover between forward rotation and reverse rotation
3: Forward jog
4: Reverse jog
5: Individualized parameter display (Default)
How do you control STOP/RESET key behavior across control modes using parameter P7-02 on the MOKWEIR MK100?
Parameter P7-02 on the MOKWEIR MK100 sets the STOP/RESET key functionality:
0: STOP/RESET key enabled only in keypad control
1: STOP/RESET key enabled in any operation mode (Default)
How is parameter initialization or factory reset performed via parameter PP-01 on the MOKWEIR MK100?
Parameter PP-01 on the MOKWEIR MK100 provides the following reset functions:
0: No operation
1: Restore factory settings except motor parameters
2: Clear records
3: Restore factory settings, including motor parameters
How is a user password set using parameter PP-00 on the MOKWEIR MK100?
A password can be configured via parameter PP-00 on the MOKWEIR MK100 by setting a numerical value from 0 to 65535. When set to a non-zero value, parameter protection is enabled. The default value is 0 (disabled).
What causes an Err02 fault on the MOKWEIR MK100 and how is it resolved?
An Err02 fault indicates overcurrent during acceleration on the MOKWEIR MK100.
Possible causes:
1. The output circuit is short circuited.
2. The acceleration time is too short.
3. Manual torque boost or V/F curve is not appropriate.
4. The power supply is too low.
5. The startup operation is performed on a rotating motor.
6. A sudden load is added during acceleration.
7. The AC drive model is of too small power class.
Solutions:
1. Eliminate short circuit.
2. Increase the acceleration time (P0-17).
3. Adjust the manual torque boost (P3-01) or V/F curve (P3-00).
4. Check that the power supply is normal.
5. Select speed tracking restart (P6-01) or start the motor after it completely stops.
6. Remove the added load.
7. Select a drive of higher power class.
What causes an Err03 fault on the MOKWEIR MK100 and how is it resolved?
An Err03 fault indicates overcurrent during deceleration on the MOKWEIR MK100.
Possible causes:
1. The output circuit is short circuited.
2. The deceleration time is too short.
3. The power supply is too low.
4. A sudden load is added during deceleration.
5. The braking resistor is not installed.
Solutions:
1. Eliminate short circuit.
2. Increase the deceleration time (P0-18).
3. Check the power supply and ensure it is normal.
4. Remove the added load.
5. Install the braking resistor across terminals +DC and PB.
What causes an Err04 fault on the MOKWEIR MK100 and how is it resolved?
An Err04 fault indicates overcurrent at constant speed on the MOKWEIR MK100.
Possible causes:
1. The output circuit is short circuited.
2. The power supply is too low.
3. A sudden load is added during operation.
4. The AC drive model is of too small power class.
Solutions:
1. Eliminate short circuit.
2. Adjust power supply to normal range.
3. Remove the added load.
4. Select a drive of higher power class.
What causes an Err05 fault on the MOKWEIR MK100 and how is it resolved?
An Err05 fault indicates overvoltage during acceleration on the MOKWEIR MK100.
Possible causes:
1. The DC bus voltage is too high.
2. An external force drives the motor during acceleration.
3. The acceleration time is too short.
4. The braking resistor is not installed.
Solutions:
1. Replace with a proper braking resistor.
2. Cancel the external force or install a braking resistor.
3. Increase the acceleration time.
4. Install a braking resistor.
What causes an Err06 fault on the MOKWEIR MK100 and how is it resolved?
An Err06 fault indicates overvoltage during deceleration on the MOKWEIR MK100.
Possible causes:
1. The DC bus voltage is too high.
2. An external force drives the motor during deceleration.
3. The deceleration time is too short.
4. The braking resistor is not installed.
Solutions:
1. Replace with a proper braking resistor.
2. Cancel the external force or install a braking resistor.
3. Increase the deceleration time.
4. Install a braking resistor.
What causes an Err07 fault on the MOKWEIR MK100 and how is it resolved?
An Err07 fault indicates overvoltage at constant speed on the MOKWEIR MK100.
Possible causes:
1. The DC bus voltage is too high.
2. An external force drives the motor during deceleration or operation.
Solutions:
1. Replace with a proper braking resistor.
2. Cancel the external force.
What are the DC bus voltage thresholds for different voltage classes of the MOKWEIR MK100?
The DC bus thresholds for the MOKWEIR MK100 are defined as follows:
Single-phase 220 V: DC Bus Overvoltage is 400 V; DC Bus Undervoltage is 200 V; Braking Unit Operation Level is 381 V.
Three-phase 220 V: DC Bus Overvoltage is 400 V; DC Bus Undervoltage is 200 V; Braking Unit Operation Level is 381 V.
Three-phase 380 V: DC Bus Overvoltage is 810 V; DC Bus Undervoltage is 350 V; Braking Unit Operation Level is 700 V.
What causes an Err09 undervoltage fault on the MOKWEIR MK100 and how is it resolved?
An Err09 fault indicates undervoltage on the MOKWEIR MK100.
Possible causes:
1. Instantaneous power failure occurs.
2. The input voltage exceeds the allowed range (too low).
3. The DC bus voltage is too low.
4. The rectifier bridge and buffer resistor are faulty.
5. The driver board is faulty.
6. The control board is faulty.
Solutions:
1. Reset the fault.
2. Adjust the input voltage to within the allowed range.
3. Seek maintenance for internal components (driver board, control board, rectifier bridge, or buffer resistor).
What causes an Err10 drive overload fault on the MOKWEIR MK100 and how is it resolved?
An Err10 fault on the MOKWEIR MK100 indicates drive overload.
Possible causes:
1. The load is too heavy or the rotor is locked.
2. The drive is of too small power class.
Solutions:
1. Reduce the load, check the motor, or check the machine whether it is locking the rotor.
2. Select a drive of higher power class.
What causes an Err11 motor overload fault on the MOKWEIR MK100 and how is it resolved?
An Err11 fault indicates motor overload on the MOKWEIR MK100.
Possible causes:
1. Parameter P9-01 (Motor overload protection gain) is set too small.
2. The load is too heavy or the rotor is locked.
3. The drive is of too small power class.
Solutions:
1. Set parameter P9-01 correctly.
2. Reduce the load, or check the motor/machine to confirm whether the rotor is locked.
3. Select a drive of larger power class.
What causes an Err12 power input phase loss on the MOKWEIR MK100 and how is it resolved?
An Err12 fault indicates power input phase loss on the MOKWEIR MK100.
Possible causes:
1. The three-phase power supply is abnormal.
2. The driver board is faulty.
3. The lightning protection board is faulty.
4. The control board is faulty.
Solutions:
1. Check the power supply.
2. Seek maintenance for the driver board, lightning protection board, or control board.
What causes an Err13 power output phase loss on the MOKWEIR MK100 and how is it resolved?
An Err13 fault indicates power output phase loss on the MOKWEIR MK100.
Possible causes:
1. The cable between the drive and motor is faulty.
2. The drive’s three-phase output is unbalanced when the motor is running.
3. The driver board is faulty.
4. The IGBT is faulty.
Solutions:
1. Check the motor cable.
2. Check the motor windings.
3. Seek maintenance for the driver board or IGBT.
What causes an Err14 IGBT overheat fault on the MOKWEIR MK100 and how is it resolved?
An Err14 fault indicates IGBT overheat on the MOKWEIR MK100.
Possible causes:
1. The ambient temperature is too high.
2. The air filter is blocked.
3. The cooling fan is damaged.
4. The thermal sensor of the IGBT is damaged.
5. The IGBT is damaged.
Solutions:
1. Reduce the ambient temperature.
2. Clean the air filter.
3. Reduce carrier frequency parameter P0-15.
4. Replace the cooling fan or seek maintenance.
What causes an Err16 communication fault on the MOKWEIR MK100 and how is it resolved?
An Err16 fault indicates communication abnormal on the MOKWEIR MK100.
Possible causes:
1. The host controller is abnormal.
2. The communication cable is faulty.
3. The communication parameters in group PD are set improperly.
Solutions:
1. Check cabling of the host controller.
2. Check the communication cabling.
3. Set the communication parameters (Group PD) properly.
What causes an Err23 short circuit to ground on the MOKWEIR MK100 and how is it resolved?
An Err23 fault indicates the motor or output lines are short-circuited to ground on the MOKWEIR MK100.
Solutions:
1. Measure insulation resistance of the motor and output cables.
2. Replace damaged motor or output cables.
3. If the drive itself is damaged, seek maintenance.
How do you clear an Err26 or Err29 fault on the MOKWEIR MK100?
Err26 indicates the accumulative running time has reached the threshold set in P8-17. Err29 indicates the accumulative power-on time has reached the threshold set in P8-16.
To clear the record and fault condition on the MOKWEIR MK100, set parameter PP-01 to 2 (Clear records).
What does Err31 mean on the MOKWEIR MK100 and how do you resolve it?
Err31 indicates PID feedback lost during running, which happens when the PID feedback signal is lower than the value set in PA-26.
To resolve this, check the PID feedback wiring and signal sensor, or adjust parameter PA-26 to a proper threshold value.
What causes an Err41 fault on the MOKWEIR MK100?
An Err41 fault occurs when the motor switchover is triggered through a digital input terminal while the AC drive is still running. To resolve this, switch over the motor only after the MOKWEIR MK100 has completely stopped.
What should be checked if there is no display on the MOKWEIR MK100 at power-on?
If the display fails to turn on upon powering the MOKWEIR MK100:
1. Check if there is power supply voltage and verify that it is not too low.
2. Re-connect the 4-core and 28-core flat cables between the control board, driver board, and keypad.
3. If the switching power supply, rectifier bridge, buffer resistor, control board, or keypad is faulty, seek maintenance.
What causes “HF” to be displayed on the MOKWEIR MK100 at power-on or startup?
If “HF” is displayed at power-on or after startup:
1. The ribbon cable between the driver board and control board is in poor contact (reconnect the 4-core and 28-core flat cables).
2. The control board is damaged.
3. The motor winding or cable is short-circuited to ground.
4. The power supply voltage is too low.
5. The cooling fan is damaged, or the rotor is locked.
6. A control terminal is short-circuited.
What should be checked if the motor does not rotate when the MOKWEIR MK100 outputs a non-zero reference?
Perform the following diagnostics on the MOKWEIR MK100:
1. Check the motor and cable between drive and motor.
2. Check and re-set the motor parameters (Group P1).
3. Check and reconnect the internal 4-core and 28-core flat cables.
4. Verify the mechanical system is not locking the motor rotor.
5. Seek maintenance if the driver board is faulty.
What should be checked if digital input (DI) terminals are disabled on the MOKWEIR MK100?
If DI terminals fail to respond on the MOKWEIR MK100:
1. Check and reset the DI parameters in Group P4.
2. Verify input signal voltage levels and check input cables.
3. Check the wire jumper between SEL and +24V terminals to ensure good contact.
4. Seek maintenance if the control board is faulty.
What communication protocol and supported commands are used for Modbus on the MOKWEIR MK100?
The MOKWEIR MK100 supports Modbus-RTU communication using an RS485 bus. It supports word-type reading and writing:
Reading command: 0x03 (Read slave parameters)
Writing command: 0x06 (Write slave parameters)
It does not support reading or writing individual bits or bytes.
How are communication parameter addresses defined for parameter groups on the MOKWEIR MK100?
Communication addresses on the MOKWEIR MK100 are expressed in hexadecimal format where high-order bytes define the group and low-order bytes define the parameter index:
P0 to PE parameter groups: F0 to FE (EEPROM visited address range: 0xF000 to 0xFEFF).
A0 to AC parameter groups: A0 to AF (EEPROM visited address range: 0xA000 to 0xACFF).
U0 monitoring group: 70 to 7F (Visited address range: 0x7000 to 0x70FF, read-only).
For example, parameter P3-12 has the communication address 0xF30C.
How do you write parameters into RAM instead of EEPROM via Modbus on the MOKWEIR MK100?
To avoid reducing EEPROM service life, change the high-order byte of the parameter address on the MOKWEIR MK100 to save to RAM:
For Group P parameters: Change the high order ‘F’ to ‘0’ (RAM address range 0x0000 to 0x0EFF). For example, P3-12 is addressed as 030C.
For Group A parameters: Change the high order ‘A’ to ‘4’ (RAM address range 0x4000 to 0x4CFF). For example, A0-05 is addressed as 4005.
Alternatively, use command code 07H to write to RAM.
What are the Modbus command word functions sent to address 2000H on the MOKWEIR MK100?
Writing to address 2000H provides the following control operations on the MOKWEIR MK100:
0001: Forward run
0002: Reverse run
0003: Forward jog
0004: Reverse jog
0005: Coast to stop
0006: Decelerate to stop
0007: Fault reset
What values indicate the AC drive status at Modbus address 3000H on the MOKWEIR MK100?
Reading from command address 3000H provides the drive run state on the MOKWEIR MK100:
0001: Forward RUN
0002: Reverse RUN
0003: Stop
How are the baud rates configured via parameter PD-00 on the MOKWEIR MK100?
The baud rate in parameter PD-00 of the MOKWEIR MK100 is selected using the units position:
0: 300 bps
1: 600 bps
2: 1200 bps
3: 2400 bps
4: 4800 bps
5: 9600 bps (Default is 5005)
6: 19200 bps
7: 38400 bps
8: 57600 bps
9: 115200 bps
What data formats are supported by parameter PD-01 on the MOKWEIR MK100?
Parameter PD-01 sets the communication data format on the MOKWEIR MK100:
0: No check <8,N,2> (Default)
1: Even parity check <8,E,1>
2: Odd parity check <8,O,1>
3: No check, data format <8,N,1>
What are the monitoring parameters U0-00 through U0-06 on the MOKWEIR MK100?
The basic status monitoring parameters on the MOKWEIR MK100 include:
U0-00: Running frequency (Hz)
U0-01: Set frequency (Hz)
U0-02: Bus voltage (V)
U0-03: Output voltage (V)
U0-04: Output current (A)
U0-05: Output power (kW)
U0-06: Output torque (%)
What does parameter P0-15 configure on the MOKWEIR MK100?
Parameter P0-15 sets the carrier frequency of the MOKWEIR MK100 in the range of 0.8 kHz to 16.0 kHz. The default value is model dependent.
How does the automatic voltage regulation (AVR) function operate on the MOKWEIR MK100?
The MOKWEIR MK100 automatic voltage regulation (AVR) maintains a constant output voltage automatically when the input grid voltage fluctuates within the permissible range.
What is the function of the power dip ride-through feature on the MOKWEIR MK100?
On the MOKWEIR MK100, the power dip ride-through function uses the motor’s load feedback energy to compensate for voltage reduction during instantaneous power dips, allowing the drive to continue operating for a short period without tripping.
What are the single-phase and three-phase rated input/output specifications for the MOKWEIR MK100?
The rating specifications for the MOKWEIR MK100 are:
Single-phase 200-240V models:
0.4 kW: Rated capacity 1.0 kVA, Rated input current 5.1 A, Rated output current 2.5 A
0.75 kW: Rated capacity 1.5 kVA, Rated input current 8.2 A, Rated output current 4.5 A
1.5 kW: Rated capacity 3.0 kVA, Rated input current 14.0 A, Rated output current 7.5 A
2.2 kW: Rated capacity 4.0 kVA, Rated input current 23.0 A, Rated output current 10.0 A
3.0 kW: Rated capacity 5.3 kVA, Rated input current 26.2 A, Rated output current 14.0 A
Three-phase 340-480V models:
0.75 kW: Rated capacity 1.5 kVA, Rated input current 3.4 A, Rated output current 2.3 A
1.5 kW: Rated capacity 3.0 kVA, Rated input current 5.0 A, Rated output current 3.7 A
2.2 kW: Rated capacity 4.0 kVA, Rated input current 5.8 A, Rated output current 5.0 A
4.0 kW: Rated capacity 6.2 kVA, Rated input current 10.5 A, Rated output current 9.0 A
How do you set the maximum frequency on the MOKWEIR MK100 using parameter P0-10?
Parameter P0-10 sets the maximum operating frequency of the MOKWEIR MK100. It can be adjusted within the range of 50.00 Hz to 500.00 Hz, with a default setting of 50.00 Hz.
How do you change the rotation direction parameter P0-09 on the MOKWEIR MK100?
Parameter P0-09 specifies the motor rotation direction on the MOKWEIR MK100:
0: Same direction (Default)
1: Reverse direction
What are the settings for parameter P8-14 when running frequency is lower than the lower limit on the MOKWEIR MK100?
Parameter P8-14 controls the behavior of the MOKWEIR MK100 when the set frequency falls below the lower limit:
0: Run at frequency lower limit (Default)
1: Stop
2: Run at zero speed
How is the cooling fan working mode controlled by parameter P8-48 on the MOKWEIR MK100?
Parameter P8-48 controls the cooling fan behavior on the MOKWEIR MK100:
0: Fan working during running (Default)
1: Fan working continuously
What are the available cycle options for the simple PLC running mode in parameter PC-16 on the MOKWEIR MK100?
Parameter PC-16 defines simple PLC execution behavior on the MOKWEIR MK100:
0: Stop after running one cycle (Default)
1: Keep final values after running one cycle
2: Repeat after running one cycle
How does the wake-up and hibernation frequency feature work on the MOKWEIR MK100?
The MOKWEIR MK100 uses parameters P8-49 to P8-52 to manage standby energy savings:
P8-49: Wakeup frequency (Dormant frequency P8-51 to max frequency P0-10, default 0.00 Hz).
P8-50: Wakeup delay (0.0 to 6500.0 s, default 0.0 s).
P8-51: Hibernating frequency (0.00 to wakeup frequency P8-49, default 0.00 Hz).
P8-52: Hibernating delay (0.0 to 6500.0 s, default 0.0 s).
What are the settings for PID feedback source selection in parameter PA-02 on the MOKWEIR MK100?
Parameter PA-02 configures the PID feedback source on the MOKWEIR MK100:
0: AI1 (Default)
1: AI2
2: Keyboard knob
3: AI1 – AI2
4: Pulse reference (X5)
5: Serial comms.
6: AI1 + AI2
7: Max. (|AI1|, |AI2|)
8: Min. (|AI1|, |AI2|)
How can the relay output terminal TA/TC be programmed on the MOKWEIR MK100?
The relay output function on the MOKWEIR MK100 is configured using parameter P5-02. Standard options include:
0: No output
1: AC drive running
2: Fault output (Default)
3: Frequency-level detection FDT1 output
4: Frequency reached
5: Zero-speed running (no output at stop)
6: Motor overload pre-warning
7: AC drive overload pre-warning
15: Ready for RUN
What is the default function assigned to parameter P5-04 (AO1 function selection) on the MOKWEIR MK100?
On the MOKWEIR MK100, parameter P5-04 is set by default to 1, which assigns AO1 to output the Running frequency.
What causes an Err08 control power fault on the MOKWEIR MK100?
An Err08 fault on the MOKWEIR MK100 indicates that the control power input voltage exceeds the allowed operating range. The solution is to adjust the input voltage back to within the specified range.
What causes an Err15 external equipment fault on the MOKWEIR MK100?
An Err15 fault indicates that an external fault signal was sent through a digital input (DI) terminal or virtual digital input (VDI). To clear the condition, verify and reset the external equipment, then perform a fault reset on the MOKWEIR MK100.
What causes an Err17 soft start contactor fault on the MOKWEIR MK100?
Err17 occurs when the internal soft start contactor is not closing properly. Check whether contactor wiring is loose, test whether the contactor or its 24V supply is faulty, or seek maintenance service.
What causes an Err42 overspeed error on the MOKWEIR MK100 and how is it fixed?
Err42 indicates an overspeed error on the MOKWEIR MK100.
Causes and checks:
1. Motor locked-rotor: check if machine is jammed, confirm motor auto-tuning was done, and ensure torque limit P2-10 is not set too small.
2. Improper settings: set overspeed parameters P9-69 and P9-70 properly.
3. Wiring fault: check whether wiring between AC drive and motor is loose or broken, and reconnect securely.
What does Err21 signify on the MOKWEIR MK100 and how is it repaired?
Err21 indicates an EEPROM read-write fault caused by a damaged EEPROM chip on the MOKWEIR MK100. The solution is to replace the main control board.
How do you read the heatsink temperature of the MOKWEIR MK100?
The heatsink temperature of the inverter IGBT on the MOKWEIR MK100 can be checked by viewing parameter P7-07, which displays values in degrees Celsius (°C) from 0 to 100°C.