MITSUBISHI ELECTRIC MELSEC-F FX3U-4AD-TC-ADP (01) PDF MANUAL


Post questions, comments, reviews or page errors in the comment box below.

Your File is Ready … Download PDF

CLICK HERE TO DOWNLOAD MITSUBISHI ELECTRIC MELSEC-F FX3U-4AD-TC-ADP (01) PDF MANUAL


PDF Content Summary: JY997D14801M Side B

Side A Side B FX3U-4AD-TC-ADP JAPANESE ENGLISH Applicable standards FX3U-4AD-TC-ADP units made in June, 2005 or later comply with the EC Directive (EMC Directive) and UL standards (UL, cUL). Further information can be found in the following manual. → FX3S Series Hardware Manual (Manual No. JY997D48301) → FX3G Series Hardware Manual (Manual No. JY997D46001) → FX3GC Series Hardware Manual (Manual No. JY997D45201) [5] Direct mounting hole:2 holes of φ4.5 (0.18") (mounting screw: M4 screw) Not used when connecting to FX3GC/FX3UC Series PLC. [6] POWER LED (green): Lit while 24 V DC power is supplied properly to terminals '24+' and '24-'. [7] Terminal block (European type): Connect thermocouple sensor input, Type K or J changeover input, and 24 V DC 5) Connect the special adapter (fig.C) to the main unit as shown on the right. 6) Slide back the C FX3U-***-*** POWER B 6) RUN FX3U-48M FX3U-48MR/ES -48MR/ES FX3U-48M STOP

USER'S MANUAL Manual Number JY997D14801 Revision M Date July 2018 → FX3U Series Hardware Manual (Manual No. JY997D50301) → FX3UC (D, DS, DSS) Series Hardware Manual (Manual No. JY997D50501) → FX3UC-32MT-LT-2 Hardware Manual (Manual No. JY997D31601) Regarding the standards that relate to the main unit, please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider. Attention This product is designed for use in industrial applications. Caution for EC Directive The analog special adapters have been found to be compliant to the European power supply. [8] Special adapter connector: Used to connect this special adapter to PLC main unit or special adapter. [9] DIN rail mounting hook [10] Special adapter fixing hook [11] Special adapter connector: Used to connect communication or analog special adapters to the left side of the TC-ADP. 2. Installation special adapter slide lock (fig.B) of the main unit to fix the special adapter (fig.C). Connection precautions 5) 5) 5) 6) B

This manual describes the part names, dimensions, mounting, and specifications of the product. Before use, read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product. Make sure to learn all the product information, safety information, and precautions. Store this manual in a safe place so that it can be taken out and read whenever necessary. Always forward it to the end user. Registration: The company and product names described in this manual are registered trademarks or the trademarks of their respective companies. Effective July 2018 Specifications are subject to change without notice. ♥ 2005 Mitsubishi Electric Corporation Safety Precautions (Read these precautions before use.) This manual classifies the safety precautions into two categories: and . Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury. Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage. Depending on the circumstances, procedures indicated by may also cause severe injury. It is important to follow all precautions for personal safety. Associated Manuals Manual name Manual No. Description standards in the aforesaid manual and directive. However, for the very best per formance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points; As analog devices are sensitive by nature, their use should be considered care fully. For users of proprietary cables (integral with sensors or actuators), these users should follow those manufacturers installation requirements. Mitsubishi Electric recommend that shielded cables should be used. If NO other EMC protection is provided, then users may experience temporary loss or accuracy between ±10 % in very heavy industrial areas. However, Mitsubishi Electric suggest that if adequate EMC precautions are fol lowed for the users complete control system, users should expect accuracy as specified in this manual. • Sensitive analog cable should not be laid in the same trunking or cable conduit as high voltage cabling. Where possible users should run analog cables separately. • Good cable shielding should be used. When terminating the shield at Earth - ensure that no earth loops are accidentally created. • When reading analog values, EMC accuracy can be improved out by averaging the readings. This can be achieved either through functions on the analog special adapters or through a users program. 1. Outline FX3U-4AD-TC-ADP (hereinafter called TC-ADP) is an analog special adapter for measuring temperature via four channels of connected Type K or Type J thermocouple thermometer. 1.1 Incorporated Items Verify that the following product and items are included in the package: Product FX3U-4AD-TC-ADP K/J type thermocouple thermometer input special adapter Accessories User’s manual (This manual) 1.2 External Dimensions, Part Names, and Terminal Layout [5] [10] For installation/uninstallation details, refer to the respective PLC User's manual Hardware Edition. INSTALLATION PRECAUTIONS • Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. INSTALLATION PRECAUTIONS • Use the product within the generic environment specifications described in PLC main unit manual (Hardware Edition). Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S, SO2 or NO2), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind. If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur. • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. • Do not touch the conductive parts of the product directly. Doing so may cause device failures or malfunctions. • Connect special adapter securely to their designated connectors. Loose connections may cause malfunctions. 2.1 Connection to the PLC This section describes the connection method to the PLC (FX3U Series PLC is used for the following example). For installation method to other PLCs, refer to the respective PLC User's manual Hardware Edition. Procedure Connect all the high-speed I/O special adapters before connecting other special adapters when they are used in combination. Do not connect a high-speed I/O special adapter on the left side of any special adapters other than other high-speed I/O special adapters. 3. Wiring WIRING PRECAUTIONS • Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. WIRING PRECAUTIONS • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise: 1) Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main circuit, high-voltage line, or load line. Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line at least 100 mm (3.94") or more away from the main circuit, high-voltage line, or load line. 2) Ground the shield of the analog input/output cable at one point on the signal receiving side. However, do not use common grounding with heavy electrical systems. • Make sure to properly wire to the terminal block (European type) in accordance with the following precautions. Failure to do so may cause electric shock, equipment failures, a short-circuit,

FX3S/FX3G/FX3GC/FX3U/ FX3UC Series User's Manual - Analog Control Edition FX3S/FX3G/FX3GC/FX3U/ FX3UC Series Programming Manual - Basic & Applied Instruction Edition FX3S Series JY997D16701 MODEL CODE: 09R619 JY997D16601 MODEL CODE: 09R517 JY997D48601 Describes specifications for analog control and programming method for FX3S/FX3G/FX3GC/ FX3U/ FX3UC Series PLC. Describes PLC programming for basic/applied instructions and devices. Explains FX3S Series PLC [3] [2] [1] [4] [6] [7] [8] ) " 5 5. 3( 09 ) h c t i p ) e " l 6 o 8 h . 3 g ( n 8 i t 9 n u o m ( ) " 8 1. 4( 6 01 24+ 24- J-type J-type L1+ L1- L2+ 1) Turn off the power. Disconnect all the cables connected to the PLC main unit and special adapter, and demount the main unit and special adapter mounted on DIN rail or mounted directly using screws. 2) Install an expansion board to the main unit. For the expansion board installation procedure, refer to the following manual: → FX3U Series User's Manual - Hardware Edition 3) Remove the special adapter connector cover on the expansion board (fig.A). When connecting this product to another special FX3U-48MR/ES FX3U-48M 4) adapter, please replace the 'expansion board' in the above description with a 'special adapter' and wire breakage, malfunctions, or damage to the product. - The disposal size of the cable end should follow the dimensions described in the manual. - Tightening torque should follow the specifications in the manual. - Twist the end of strand wire and make sure that there are no loose wires. - Do not solder-plate the electric wire ends. - Do not connect more than the specified number of wires or electric wires of unspecified size. - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed. 3.1 Applicable cable and terminal tightening torque

User’s Manual - Hardware Edition FX3G Series User’s Manual - Hardware Edition FX3GC Series User’s Manual - Hardware Edition FX3U Series MODEL CODE: 09R535 JY997D31301 MODEL CODE: 09R521 JY997D45401 MODEL CODE: 09R533 JY997D16501 specifications for I/O, wiring, installation, and maintenance. Explains FX3G Series PLC specifications for I/O, wiring, installation, and maintenance. Explains FX3GC Series PLC specifications for I/O, wiring, installation, and maintenance. Explains FX3U Series PLC 7(0.28") 74(2.92") 15.5 (0.62") [11] Special adapter connector cover is removed 15.1 (0.6") 17.6 (0.7") [9] L2- L3+ L3- L4+ L4- perform the procedure as indicated. 4) Slide the special adapter slide lock 3) B (fig.B) of the main unit. When connecting this product to another special adapter, please replace the 'main unit' in the A above description with a 'special adapter' and perform the procedure as indicated. (Please replace the following procedures similarly.) RUN STOP B 3.1.1 Type terminal block (European type) 1) Wire size 4) - The power supply wiring and the Type K/J changeover input wiring should use 22-20 AWG wire. - Thermocouple wiring should use the compensating lead wire suitable for the type of thermocouple. → For details of compensating lead wire, Refer to Section 3.3 2) Applicable cable Type Wire size

User’s Manual - Hardware Edition FX3UC Series User’s Manual - Hardware Edition MODEL CODE: 09R516 JY997D28701 MODEL CODE: 09R519 specifications for I/O, wiring, installation, and maintenance. Explains FX3UC Series PLC specifications for I/O, wiring, installation, and maintenance. [1] DIN rail mounting groove (DIN rail: DIN46277) [2] Name plate [3] Special adapter slide lock: Weight: Approx. 0.1 kg (0.22 lbs) Single-wire 0.3 mm2 to 0.5 mm2 (AWG22 to 20) 2-wire 2 pieces of 0.3 mm2 (AWG22)

How to obtain manuals For product manuals or documents, consult with the Mitsubishi Electric dealer from who you purchased your product. Used to connect additional special adapters onto the left side of this special adapter. [4] Special adapters connector cover: Remove this cover to connect additional special adapters to the left side.

3) Termination of cable end Strip the coating of strand wire and twist the cable core before connecting it, or strip the coating of single wire before connecting it. 3.4 Grounding Grounding should be performed as stated below. • The grounding resistance should be 100 Ω or less. 4.4 Performance Specifications Specifications An alternative connection is to use a ferrule with insulating sleeve. <Reference> Item • Independent grounding should be performed for best results. When independent grounding is not performed, perform "shared grounding" of the Centigrade (°C) Fahrenheit (°F) Manufacturer Model Caulking tool Phoenix Contact Co., Ltd. AI 0.5-8WH CRIMPFOX 6*1 following figure. For details, refer to the respective PLC User's manual Hardware Edition. Input signal Thermocouple type K or J JIS C 1602-1995

(or CRIMPFOX 6T-F*2) *1 Old model name: CRIMPFOX ZA 3 *2 Old model name: CRIMPFOX UD 6 PLC Other PLC equipment Other PLC equipment Other equipment Rated temperature range Type K -100 °C to +1000 °C Type K -148 °F to +1832 °F Type J -100 °C to +600 °C Type J -148 °F to +1112 °F

- Strand wire/single wire - Ferrule with insulation sleeve Independent grounding Shared grounding Common grounding Digital outputType K -1000 to +10000 Type K -1480 to +18320 Insulation sleeve Contact area (Best condition) (Good condition) (Not allowed) Type J -1000 to +6000 Type J -1480 to +11120

9 mm (0.35") (Crimp area) 8 mm (0.31") 2.6 mm (0.1") 14 mm (0.55") • The grounding wire size should be AWG 22-20 (0.3-0.5 mm2). • The grounding point should be close to the PLC, and all grounding wire should be as short as possible. 4. Specifications ResolutionType K 0.4 °C Type K 0.72 °F Type J 0.3 °C Type J 0.54 °F Total accuracy ±(0.5 % full scale +1 °C) When using a ferrule with insulation sleeve, choose a wire with proper cable sheath referring to the above outside dimensions, or otherwise, the wire cannot be inserted easily. The tightening torque must be 0.22 to 0.25 N•m. Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do so may cause equipment failures or malfunctions. STARTUP AND MAINTENANCE PRECAUTIONS • Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions. A/D conversion time • FX3U/FX3UC Series PLC: 200 ∝s (The data will be updated at every scan time of the PLC.) • FX3S/FX3G/FX3GC Series PLC: 250 ∝s (The data will be updated at every scan time of the PLC.) 3.2 Power Supply Wiring For the power supply wiring, refer to the following manual. → FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition 3.3 Selection of thermocouple * For repair, contact your local Mitsubishi Electric representative. • Do not drop the product or exert strong impact to it. Doing so may cause damage. DISPOSAL Type K +10100 +10000 C ° 0 1 0 1 Type K +18500 +18320 F ° 0 5 8 1 +

→ For the terminal configuration, refer to Section 1.2 Precautions on thermocouple wiring • Thermocouple type - There are 2 types of thermocouples: Type K and Type J. Select the desired PRECAUTIONS • Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device. Input characteristics -100°C C ° 0 1 1 - 0 +1000°C -1000 -1100 + -148°F F ° 6 6 1 - 0 +1832°F -1480 -1660

type. However, be sure to connect the same type of thermocouple to all the channels. - Use insulated thermocouple types. • Compensating lead TRANSPORTATION AND STORAGE PRECAUTIONS Type J+6100 +6000 C ° Type J +11300 +11120 F °

wire To connect the thermocouple, use one of the right types of compensating lead wires. The compensating Thermocouple Type of compensating lead wire Type K KX, KCA, KCB, KCC Type J JX • The product is a precision instrument. During transportation, avoid impacts larger than those specified in the general specifications by using dedicated packaging boxes and shock-absorbing palettes. Failure to do so may cause failures in the product. After transportation, verify operation of the product and check for damage of the mounting part, etc. -100°C C ° 0 1 1 - 0 -1000 -1100 0 1 6 + +600°C F ° 6 6 1- -148°F -1480 -1660 0 0 3 1 1 + +1112°F

lead wire indicates the temperature value of approximately 0.12 °C higher than that of the wire resistor (10 Ω). Temperature value should be used in consideration of this point. If the compensating lead wire is very long, the wire may be easily affected by noise, etc. It is, therefore, recommended that the length of the compensating lead wire should be 100 m (328' 1") or less. Example of thermocouple wiring 4.1 Applicable PLC Model name Applicability FX3S Series PLC Ver. 1.00 or later (from first production) FX3G Series PLC Ver. 1.00 or later (from first production) Insulation method • The photocoupler is adopted to insulate the analog input area from the PLC. • The DC/DC converter is adopted to insulate the power supply line from the analog input area. • A channels are not insulated from each other.

Using Type J Thermocouple Wiring *1 Terminal block J-type J-type TC-ADP Temperature compensation circuit FX3GC Series PLC Ver. 1.40 or later (from first production) FX3U Series PLC Ver. 2.20 or later (from first production) FX3UC Series PLC Ver. 1.30 or later (from the production manufactured in August, Occupied points 0 point (This number is not related to the maximum number of input/output points of the PLC.)

Thermocouple Compensating lead wire (Shielded) L + L - 3 kΩ 2004 with SER No. 48****) The version number can be checked by monitoring D8001/D8101 as the last three ch digits indicate it. 4.2 General Specifications Items other than the following are equivalent to the those of the PLC main unit. 「电器电子产品有害物质限制使用标识要求」的表示方式 Note: This symbol mark is for China only. 含有有害6物质的名称,含有量,含有部品 This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be

Temperature compensation circuit For general specifications, refer to the respective PLC User's manual Hardware Edition. 本产品中所含有的有害6物质的名称,含有量,含有部品如下表所示。 held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.

External power supply wiring 24 V DC L + L - 24+ 3 kΩ +5 V ch Item Specification Dielectric withstand voltage 500 V AC for one minute Between all terminals and ground terminal of PLC main unit Insulation resistance 5 MΩ or higher by 500 V DC insulation resistance tester 产品中有害物质的名称及含量 有害物质 多溴 Warranty Exclusion of loss in opportunity and secondary loss from warranty liability Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to: (1) Damages caused by any cause found not to be the responsibility of Mitsubishi. (2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products. (3) Special damages and secondary damages whether foreseeable or not, compensation for

*2 Grounding 24- 4.3 Power Supply Specifications Item Specification 部件名称 铅 (Pb) 汞 (Hg) 镉 (Cd) 六价铬 (Cr(VI)) 多溴联苯 (PBB) 二苯醚 (PBDE) accidents, and compensation for damages to products other than Mitsubishi products. (4) Replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.

(Ground resistance: 100 Ω or less) L +, L -, ch : represents the channel number. A/D conversion 24 V DC +20 %/-15 %, 45 mA for 24 V DC 可编程 外壳 ○ ○ ○○ ○ ○ For safe use

*1 When using the Type J thermocouple, short-circuit the 'Type J' terminals and turn the special auxiliary relay (Type K/J mode changeover) ON. circuit driving power Interface driving Connect a 24 V DC power supply to the terminal block. 5 V DC, 15 mA 控制器 印刷基板 × ○○ ○ ○ ○ • This product has been manufactured as a general-purpose part for general

For details of auxiliary relays, refer to the following manual. → FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual - Analog Control Edition *2 24 V DC service power supply of the FX3S/FX3G/FX3U Series PLC can also be used. power 5 V DC power is supplied from the internal power supply of main unit. 本表格依据SJ/T 11364的规定编制。 ○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572 • 规定的限量要求以下。 ×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T • 26572规定的限量要求。 基于中国标准法的参考规格:GB/T15969.2 industries, and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life. Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine or passenger movement vehicles, consult with Mitsubishi Electric. This product has been manufactured under strict quality control. However when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.

HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

JY997D14801M Side B Side A Side B FX3U-4AD-TC-ADP JAPANESE ENGLISH Applicable standards FX3U-4AD-TC-ADP units made in June, 2005 or later comply with the EC Directive (EMC Directive) and UL standards (UL, cUL). Further information can be found in the following manual. → FX3S Series Hardware Manual (Manual No. JY997D48301) → FX3G Series Hardware Manual (Manual No. JY997D46001) → FX3GC Series Hardware Manual (Manual No. JY997D45201) [5] Direct mounting hole:2 holes of φ4.5 (0.18") (mounting screw: M4 screw) Not used when connecting to FX3GC/FX3UC Series PLC. [6] POWER LED (green): Lit while 24 V DC power is supplied properly to terminals '24+' and '24-'. [7] Terminal block (European type): Connect thermocouple sensor input, Type K or J changeover input, and 24 V DC 5) Connect the special adapter (fig.C) to the main unit as shown on the right. 6) Slide back the C FX3U-***-*** POWER B 6) RUN FX3U-48M FX3U-48MR/ES -48MR/ES FX3U-48M STOP USER'S MANUAL Manual Number JY997D14801 Revision M Date July 2018 → FX3U Series Hardware Manual (Manual No. JY997D50301) → FX3UC (D, DS, DSS) Series Hardware Manual (Manual No. JY997D50501) → FX3UC-32MT-LT-2 Hardware Manual (Manual No. JY997D31601) Regarding the standards that relate to the main unit, please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider. Attention This product is designed for use in industrial applications. Caution for EC Directive The analog special adapters have been found to be compliant to the European power supply. [8] Special adapter connector: Used to connect this special adapter to PLC main unit or special adapter. [9] DIN rail mounting hook [10] Special adapter fixing hook [11] Special adapter connector: Used to connect communication or analog special adapters to the left side of the TC-ADP. 2. Installation special adapter slide lock (fig.B) of the main unit to fix the special adapter (fig.C). Connection precautions 5) 5) 5) 6) B This manual describes the part names, dimensions, mounting, and specifications of the product. Before use, read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product. Make sure to learn all the product information, safety information, and precautions. Store this manual in a safe place so that it can be taken out and read whenever necessary. Always forward it to the end user. Registration: The company and product names described in this manual are registered trademarks or the trademarks of their respective companies. Effective July 2018 Specifications are subject to change without notice. ♥ 2005 Mitsubishi Electric Corporation Safety Precautions (Read these precautions before use.) This manual classifies the safety precautions into two categories: and . Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury. Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage. Depending on the circumstances, procedures indicated by may also cause severe injury. It is important to follow all precautions for personal safety. Associated Manuals Manual name Manual No. Description standards in the aforesaid manual and directive. However, for the very best per formance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points; As analog devices are sensitive by nature, their use should be considered care fully. For users of proprietary cables (integral with sensors or actuators), these users should follow those manufacturers installation requirements. Mitsubishi Electric recommend that shielded cables should be used. If NO other EMC protection is provided, then users may experience temporary loss or accuracy between ±10 % in very heavy industrial areas. However, Mitsubishi Electric suggest that if adequate EMC precautions are fol lowed for the users complete control system, users should expect accuracy as specified in this manual. • Sensitive analog cable should not be laid in the same trunking or cable conduit as high voltage cabling. Where possible users should run analog cables separately. • Good cable shielding should be used. When terminating the shield at Earth - ensure that no earth loops are accidentally created. • When reading analog values, EMC accuracy can be improved out by averaging the readings. This can be achieved either through functions on the analog special adapters or through a users program. 1. Outline FX3U-4AD-TC-ADP (hereinafter called TC-ADP) is an analog special adapter for measuring temperature via four channels of connected Type K or Type J thermocouple thermometer. 1.1 Incorporated Items Verify that the following product and items are included in the package: Product FX3U-4AD-TC-ADP K/J type thermocouple thermometer input special adapter Accessories User’s manual (This manual) 1.2 External Dimensions, Part Names, and Terminal Layout [5] [10] For installation/uninstallation details, refer to the respective PLC User's manual Hardware Edition. INSTALLATION PRECAUTIONS • Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. INSTALLATION PRECAUTIONS • Use the product within the generic environment specifications described in PLC main unit manual (Hardware Edition). Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S, SO2 or NO2), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind. If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur. • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. • Do not touch the conductive parts of the product directly. Doing so may cause device failures or malfunctions. • Connect special adapter securely to their designated connectors. Loose connections may cause malfunctions. 2.1 Connection to the PLC This section describes the connection method to the PLC (FX3U Series PLC is used for the following example). For installation method to other PLCs, refer to the respective PLC User's manual Hardware Edition. Procedure Connect all the high-speed I/O special adapters before connecting other special adapters when they are used in combination. Do not connect a high-speed I/O special adapter on the left side of any special adapters other than other high-speed I/O special adapters. 3. Wiring WIRING PRECAUTIONS • Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product. WIRING PRECAUTIONS • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions. • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise: 1) Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main circuit, high-voltage line, or load line. Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line at least 100 mm (3.94") or more away from the main circuit, high-voltage line, or load line. 2) Ground the shield of the analog input/output cable at one point on the signal receiving side. However, do not use common grounding with heavy electrical systems. • Make sure to properly wire to the terminal block (European type) in accordance with the following precautions. Failure to do so may cause electric shock, equipment failures, a short-circuit, FX3S/FX3G/FX3GC/FX3U/ FX3UC Series User's Manual - Analog Control Edition FX3S/FX3G/FX3GC/FX3U/ FX3UC Series Programming Manual - Basic & Applied Instruction Edition FX3S Series JY997D16701 MODEL CODE: 09R619 JY997D16601 MODEL CODE: 09R517 JY997D48601 Describes specifications for analog control and programming method for FX3S/FX3G/FX3GC/ FX3U/ FX3UC Series PLC. Describes PLC programming for basic/applied instructions and devices. Explains FX3S Series PLC [3] [2] [1] [4] [6] [7] [8] ) " 5 5. 3( 09 ) h c t i p ) e " l 6 o 8 h . 3 g ( n 8 i t 9 n u o m ( ) " 8 1. 4( 6 01 24+ 24- J-type J-type L1+ L1- L2+ 1) Turn off the power. Disconnect all the cables connected to the PLC main unit and special adapter, and demount the main unit and special adapter mounted on DIN rail or mounted directly using screws. 2) Install an expansion board to the main unit. For the expansion board installation procedure, refer to the following manual: → FX3U Series User's Manual - Hardware Edition 3) Remove the special adapter connector cover on the expansion board (fig.A). When connecting this product to another special FX3U-48MR/ES FX3U-48M 4) adapter, please replace the 'expansion board' in the above description with a 'special adapter' and wire breakage, malfunctions, or damage to the product. - The disposal size of the cable end should follow the dimensions described in the manual. - Tightening torque should follow the specifications in the manual. - Twist the end of strand wire and make sure that there are no loose wires. - Do not solder-plate the electric wire ends. - Do not connect more than the specified number of wires or electric wires of unspecified size. - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed. 3.1 Applicable cable and terminal tightening torque User’s Manual - Hardware Edition FX3G Series User’s Manual - Hardware Edition FX3GC Series User’s Manual - Hardware Edition FX3U Series MODEL CODE: 09R535 JY997D31301 MODEL CODE: 09R521 JY997D45401 MODEL CODE: 09R533 JY997D16501 specifications for I/O, wiring, installation, and maintenance. Explains FX3G Series PLC specifications for I/O, wiring, installation, and maintenance. Explains FX3GC Series PLC specifications for I/O, wiring, installation, and maintenance. Explains FX3U Series PLC 7(0.28") 74(2.92") 15.5 (0.62") [11] Special adapter connector cover is removed 15.1 (0.6") 17.6 (0.7") [9] L2- L3+ L3- L4+ L4- perform the procedure as indicated. 4) Slide the special adapter slide lock 3) B (fig.B) of the main unit. When connecting this product to another special adapter, please replace the 'main unit' in the A above description with a 'special adapter' and perform the procedure as indicated. (Please replace the following procedures similarly.) RUN STOP B 3.1.1 Type terminal block (European type) 1) Wire size 4) - The power supply wiring and the Type K/J changeover input wiring should use 22-20 AWG wire. - Thermocouple wiring should use the compensating lead wire suitable for the type of thermocouple. → For details of compensating lead wire, Refer to Section 3.3 2) Applicable cable Type Wire size User’s Manual - Hardware Edition FX3UC Series User’s Manual - Hardware Edition MODEL CODE: 09R516 JY997D28701 MODEL CODE: 09R519 specifications for I/O, wiring, installation, and maintenance. Explains FX3UC Series PLC specifications for I/O, wiring, installation, and maintenance. [1] DIN rail mounting groove (DIN rail: DIN46277) [2] Name plate [3] Special adapter slide lock: Weight: Approx. 0.1 kg (0.22 lbs) Single-wire 0.3 mm2 to 0.5 mm2 (AWG22 to 20) 2-wire 2 pieces of 0.3 mm2 (AWG22) How to obtain manuals For product manuals or documents, consult with the Mitsubishi Electric dealer from who you purchased your product. 3) Termination of cable end Strip the coating of strand wire and twist the cable core before connecting it, or strip the coating of single wire before connecting it. Used to connect additional special adapters onto the left side of this special adapter. [4] Special adapters connector cover: Remove this cover to connect additional special adapters to the left side. 3.4 Grounding Grounding should be performed as stated below. • The grounding resistance should be 100 Ω or less. 4.4 Performance Specifications Specifications

An alternative connection is to use a ferrule with insulating sleeve. <Reference> Item • Independent grounding should be performed for best results. When independent grounding is not performed, perform "shared grounding" of the Centigrade (°C) Fahrenheit (°F) Manufacturer Model Caulking tool Phoenix Contact Co., Ltd. AI 0.5-8WH CRIMPFOX 6*1 following figure. For details, refer to the respective PLC User's manual Hardware Edition. Input signal Thermocouple type K or J JIS C 1602-1995

(or CRIMPFOX 6T-F*2) *1 Old model name: CRIMPFOX ZA 3 *2 Old model name: CRIMPFOX UD 6 PLC Other PLC equipment Other PLC equipment Other equipment Rated temperature range Type K -100 °C to +1000 °C Type K -148 °F to +1832 °F Type J -100 °C to +600 °C Type J -148 °F to +1112 °F

- Strand wire/single wire - Ferrule with insulation sleeve Independent grounding Shared grounding Common grounding Digital outputType K -1000 to +10000 Type K -1480 to +18320 Insulation sleeve Contact area (Best condition) (Good condition) (Not allowed) Type J -1000 to +6000 Type J -1480 to +11120

9 mm (0.35") (Crimp area) 8 mm (0.31") 2.6 mm (0.1") 14 mm (0.55") • The grounding wire size should be AWG 22-20 (0.3-0.5 mm2). • The grounding point should be close to the PLC, and all grounding wire should be as short as possible. 4. Specifications ResolutionType K 0.4 °C Type K 0.72 °F Type J 0.3 °C Type J 0.54 °F Total accuracy ±(0.5 % full scale +1 °C) When using a ferrule with insulation sleeve, choose a wire with proper cable sheath referring to the above outside dimensions, or otherwise, the wire cannot be inserted easily. The tightening torque must be 0.22 to 0.25 N•m. Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do so may cause equipment failures or malfunctions. STARTUP AND MAINTENANCE PRECAUTIONS • Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions. A/D conversion time • FX3U/FX3UC Series PLC: 200 ∝s (The data will be updated at every scan time of the PLC.) • FX3S/FX3G/FX3GC Series PLC: 250 ∝s (The data will be updated at every scan time of the PLC.) 3.2 Power Supply Wiring For the power supply wiring, refer to the following manual. → FX3S/FX3G/FX3GC/FX3U/FX3UC Series User’s Manual - Analog Control Edition 3.3 Selection of thermocouple * For repair, contact your local Mitsubishi Electric representative. • Do not drop the product or exert strong impact to it. Doing so may cause damage. DISPOSAL Type K +10100 +10000 C ° 0 1 0 1 Type K +18500 +18320 F ° 0 5 8 1 +

→ For the terminal configuration, refer to Section 1.2 Precautions on thermocouple wiring • Thermocouple type - There are 2 types of thermocouples: Type K and Type J. Select the desired PRECAUTIONS • Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device. Input characteristics -100°C C ° 0 1 1 - 0 +1000°C -1000 -1100 + -148°F F ° 6 6 1 - 0 +1832°F -1480 -1660

type. However, be sure to connect the same type of thermocouple to all the channels. - Use insulated thermocouple types. • Compensating lead TRANSPORTATION AND STORAGE PRECAUTIONS Type J+6100 +6000 C ° Type J +11300 +11120 F °

wire To connect the thermocouple, use one of the right types of compensating lead wires. The compensating Thermocouple Type of compensating lead wire Type K KX, KCA, KCB, KCC Type J JX • The product is a precision instrument. During transportation, avoid impacts larger than those specified in the general specifications by using dedicated packaging boxes and shock-absorbing palettes. Failure to do so may cause failures in the product. After transportation, verify operation of the product and check for damage of the mounting part, etc. -100°C C ° 0 1 1 - 0 -1000 -1100 0 1 6 + +600°C F ° 6 6 1- -148°F -1480 -1660 0 0 3 1 1 + +1112°F

lead wire indicates the temperature value of approximately 0.12 °C higher than that of the wire resistor (10 Ω). Temperature value should be used in consideration of this point. If the compensating lead wire is very long, the wire may be easily affected by noise, etc. It is, therefore, recommended that the length of the compensating lead wire should be 100 m (328' 1") or less. Example of thermocouple wiring 4.1 Applicable PLC Model name Applicability FX3S Series PLC Ver. 1.00 or later (from first production) FX3G Series PLC Ver. 1.00 or later (from first production) Insulation method • The photocoupler is adopted to insulate the analog input area from the PLC. • The DC/DC converter is adopted to insulate the power supply line from the analog input area. • A channels are not insulated from each other.

Using Type J Thermocouple Wiring *1 Terminal block J-type J-type TC-ADP Temperature compensation circuit FX3GC Series PLC Ver. 1.40 or later (from first production) FX3U Series PLC Ver. 2.20 or later (from first production) FX3UC Series PLC Ver. 1.30 or later (from the production manufactured in August, Occupied points 0 point (This number is not related to the maximum number of input/output points of the PLC.)

Thermocouple Compensating lead wire (Shielded) L + L - 3 kΩ 2004 with SER No. 48****) The version number can be checked by monitoring D8001/D8101 as the last three ch digits indicate it. 4.2 General Specifications Items other than the following are equivalent to the those of the PLC main unit. 「电器电子产品有害物质限制使用标识要求」的表示方式 Note: This symbol mark is for China only. 含有有害6物质的名称,含有量,含有部品 This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be

Temperature compensation circuit For general specifications, refer to the respective PLC User's manual Hardware Edition. 本产品中所含有的有害6物质的名称,含有量,含有部品如下表所示。 held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.

External power supply wiring 24 V DC L + L - 24+ 3 kΩ +5 V ch Item Specification Dielectric withstand voltage 500 V AC for one minute Between all terminals and ground terminal of PLC main unit Insulation resistance 5 MΩ or higher by 500 V DC insulation resistance tester 产品中有害物质的名称及含量 有害物质 多溴 Warranty Exclusion of loss in opportunity and secondary loss from warranty liability Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to: (1) Damages caused by any cause found not to be the responsibility of Mitsubishi. (2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products. (3) Special damages and secondary damages whether foreseeable or not, compensation for

*2 Grounding 24- 4.3 Power Supply Specifications Item Specification 部件名称 铅 (Pb) 汞 (Hg) 镉 (Cd) 六价铬 (Cr(VI)) 多溴联苯 (PBB) 二苯醚 (PBDE) accidents, and compensation for damages to products other than Mitsubishi products. (4) Replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.

(Ground resistance: 100 Ω or less) L +, L -, ch : represents the channel number. A/D conversion 24 V DC +20 %/-15 %, 45 mA for 24 V DC 可编程 外壳 ○ ○ ○○ ○ ○ For safe use

*1 When using the Type J thermocouple, short-circuit the 'Type J' terminals and turn the special auxiliary relay (Type K/J mode changeover) ON. circuit driving power Interface driving Connect a 24 V DC power supply to the terminal block. 5 V DC, 15 mA 控制器 印刷基板 × ○○ ○ ○ ○ • This product has been manufactured as a general-purpose part for general

For details of auxiliary relays, refer to the following manual. → FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual - Analog Control Edition *2 24 V DC service power supply of the FX3S/FX3G/FX3U Series PLC can also be used. power 5 V DC power is supplied from the internal power supply of main unit. 本表格依据SJ/T 11364的规定编制。 ○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572 • 规定的限量要求以下。 ×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T • 26572规定的限量要求。 基于中国标准法的参考规格:GB/T15969.2 industries, and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life. Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine or passenger movement vehicles, consult with Mitsubishi Electric. This product has been manufactured under strict quality control. However when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.