LIEBERT GXT4-1000RT230 (01) PDF MANUAL


Post questions, comments, reviews or page errors in the comment box below.

Your File is Ready … Download PDF

CLICK HERE TO DOWNLOAD LIEBERT GXT4-1000RT230 (01) PDF MANUAL


PDF Content Summary: Liebert® GXT4™ UPS 230V 700VA-3000VA User Manual TABLE OF CONTENTS IMPORTANT SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 GLOSSARY OF SYMBOLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.0 PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 Available Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3 Appearance and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.3.1 Appearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.3.2 Rear Panel Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.4 Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1.5 Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.5.1 Mains Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.5.2 Manual Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.5.3 Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 1.5.4 Battery Recharge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 1.5.5 Frequency Converter Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 1.5.6 Active ECO Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 2.1 Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.2 What’s Included . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.3 Preparation for Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.3.1 Installation Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.4 Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.4.1 Tower Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.4.2 Rack Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.5 Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.5.1 Connecting to AC Mains and Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.5.2 Connecting Battery Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2.6 Connecting Communication Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2.6.1 Connecting USB Communication Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cables . . . . . . . . . . . 14 3.0 OPERATION AND DISPLAY PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 3.1 LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 3.2 Control Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 3.3 LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 3.4 Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 3.4.1 Startup Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 3.4.2 Default Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 3.4.3 Main Menu Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 3.4.4 Prompt List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 3.4.5 Warning List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 3.4.6 Fault List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 4.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 i 4.1 Startup Checklist for the Liebert GXT4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 4.2 Starting the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 4.3 Manual Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 4.4 Manual Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 4.5 Shut Down the Liebert GXT4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 4.6 Disconnecting Input Power from the Liebert GXT4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 5.0 COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 5.1 Liebert IntelliSlot Communication Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 5.1.1 Liebert MultiLink. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 5.2 USB Port Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 5.2.1 Configuration Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 5.3 RS-232 Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 5.4 Terminal Block Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 5.4.1 Any Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 5.4.2 Battery Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 5.4.3 On Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 5.4.4 Low Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 6.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37 6.1 Replacing the Internal Battery Pack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 6.1.1 Battery Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 6.2 Battery Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 6.3 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 6.4 Checking UPS Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 7.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 7.1 UPS Symptoms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 7.1.1 Indicator and LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 7.1.2 Audible Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 7.2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 8.0 BATTERY CABINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42 9.0 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43 9.1 Product Warranty Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 9.2 Technical Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 ii FIGURES Figure 1 Liebert GXT4-700RT230 - GXT4-3000RT230 UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 2 Rear components, Liebert GXT4 230V 700VA and 1000VA models . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 3 Rear components, Liebert GXT4 230V 1500VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Figure 4 Rear components, Liebert GXT4 230V 2000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Figure 5 Rear components, Liebert GXT4 230V 3000VA models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Figure 6 Operating principle diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 7 Support bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Figure 8 Remove the front plastic bezel cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Figure 9 Tower installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Figure 10 Cable strain relief . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Figure 11 Battery cable attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Figure 12 Operation and display panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Figure 13 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Figure 14 Startup screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Figure 15 Startup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Figure 16 Starting and Start Successful screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Figure 17 Default screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Figure 18 Main Menu screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Figure 19 Status screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Figure 20 CONFIGURATION screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Figure 21 UPS screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Figure 22 Battery screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Figure 23 ECO Mode screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Figure 24 Outlet1 screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Figure 25 Outlet Control screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Figure 26 Outlet Setting screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Figure 27 Outlet2 setting screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Figure 28 LCD screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Figure 29 Language screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Figure 30 Color screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Figure 31 Factory Default screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Figure 32 Control screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Figure 33 Turn UPS On or Off screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Figure 34 Alarm Control screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Figure 35 Batt Test screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Figure 36 Log screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Figure 37 Clear Log screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Figure 38 About screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Figure 39 Network screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Figure 40 Terminal Block Communication pin layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Figure 41 Removing the front plastic bezel cover and battery door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Figure 42 Disconnecting the battery plug and battery connector (front view). . . . . . . . . . . . . . . . . . . . . . . . 38 Figure 43 Pulling out the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Figure 44 Battery cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 iii TABLES Table 1 UPS models, power ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Table 2 Input circuit breaker specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Table 3 Type of cord . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Table 4 Ratings of cord. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Table 5 LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Table 6 Control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Table 7 Prompts and meanings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Table 8 Warning list. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Table 9 Fault list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Table 10 Output voltage option, all models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Table 11 Replacement battery pack model numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Table 12 Description of the displayed fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Table 13 Audible alarm description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Table 14 Troubleshooting table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Table 15 Specifications of GXT4-700RT230/230E and GXT4-1000RT230/230E UPS . . . . . . . . . . . . . . . . . 43 Table 16 Specifications of the Liebert GXT4-1500RT230/230E, GXT4-2000RT230/230E and GXT-3000RT230/230E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Table 17 Operating temperature parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Table 18 Battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Table 19 Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 iv IMPORTANT SAFETY PRECAUTIONS ! WARNING Risk of electric shock. Can cause equipment damage, injury or death. Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or death. Refer all UPS and battery service to properly trained and qualified service personnel. Do not attempt to service this product yourself. Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Never work alone. SAVE THESE INSTRUCTIONS This manual contains important safety instructions that must be followed during the installation and maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or operate this UPS. UPS Safety Notes The UPS contains no user-serviceable parts except the internal battery pack. Do not remove the cover. Removing the cover may result in electric shock and will invalidate any implied warranty. The UPS has an internal battery, so the output receptacles of the UPS may carry live voltage even if the UPS is not connected to mains input power. Before moving or rewiring the UPS, disconnect mains input power and the battery and make sure that the UPS is completely shut down. Otherwise, the output terminal may carry live voltage, presenting an electric shock hazard. To ensure human safety and normal UPS operation, the UPS must be properly grounded before use. When the UPS is connected to an IT power distribution system, the short-circuit protection device must be installed on the neutral line. Install and use the UPS in the following environments: • Temperature: 0°C to 40°C (32 - 104°F); relative humidity: 0% to 95%, non-condensing) • Out of direct sunlight • Away from heat source • Stable surface, not subject to vibrations or shocks • Away from dust and other particulates • Away from corrosive substances, salts and flammable gases Keep the air inlet and outlet of the UPS unobstructed. Poor ventilation will increase the UPS internal temperature and can shorten the life of the UPS and its batteries. Keep liquid and other foreign objects away from the UPS. This UPS is not intended for use with life support and other designated critical devices. Maximum load must not exceed that shown on the UPS rating label. This UPS is designed for data processing equipment. If uncertain, consult your local dealer or Emerson Network Power® representative. Battery Safety ! WARNING Risk of electric shock and explosion. Can cause equipment damage, injury and death. Do not dispose of the battery in a fire. The battery may explode. Do not open or damage the battery. Released electrolyte is toxic and is harmful to skin and eyes. If electrolyte comes into contact with the skin, wash the affected area immediately with plenty of clean water and get medical attention. 1 Liebert® GXT4™ ! WARNING Risk of electric shock. Can cause equipment damage, injury and death. A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries: • Remove watches, rings and other metal objects. • Use tools with insulated handles. • Wear rubber gloves and boots. • Do not lay tools or metal parts on top of batteries. • Disconnect charging source prior to connecting or disconnecting battery terminals. • Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded supply circuit). ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT4 series complies with the limits for a Class A digital device. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense. The Liebert GXT4 series complies with the requirements of EMC Directive 2004/108/EC and the published technical standards. Continued compliance requires installation in accordance with these instructions and use of accessories approved by Emerson®. Information for the Protection of the Environment UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic cards, electronic components). The components removed must be taken to specialized collection and disposal centers. NOTICE TO EUROPEAN UNION CUSTOMERS: DISPOSAL OF OLD APPLIANCES—This product has been supplied from an environmentally aware manufacturer that complies with the Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/CE. The “crossed-out wheelie bin” symbol at right is placed on this product to encourage you to recycle wherever possible. Please be environmentally responsible and recycle this product through your recycling facility at its end of life. Do not dispose of this product as unsorted municipal waste. Follow local municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste electrical and electronic equipment (WEEE). For information regarding the scrapping of this equipment, please browse eu.emersonnetworkpower.com (“Products session” or “Contact us” session) or call our worldwide technical support. • Toll Free: 00 80011554499 • Toll Number Based in Italy: +39 0298250222 Liebert® GXT4™ 2 GLOSSARY OF SYMBOLS Risk of electrical shock

! i - + PbH2SO4 R Indicates a warning or a caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve-regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage WEEE

3 Liebert® GXT4™ Product Description 1.0 PRODUCT DESCRIPTION The Liebert GXT4 is a compact, online uninterruptible power system (UPS) that continuously conditions and regulates its output voltage. The UPS is designed to supply microcomputers and other sensitive electronic equipment with clean sine wave input power, 700VA to 3000VA at 230V. Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject to voltage sags, spikes and complete failure that may interrupt computer operations, cause data loss and damage equipment. The Liebert GXT4 protects equipment from these disturbances. The Liebert GXT4 continuously charges its batteries from the mains, enabling it to supply power to connected loads, even when the mains fail. This section describes the UPS, its features, models, appearance and components, operating principles and operating mode. 1.1 Features The UPS includes these features: • Intelligent battery management to extend battery life • LCD for user-friendly operation and local monitoring and configuration of operational parameters • Flexible network management with Liebert MultiLink® software • Fan fault self-inspection and automated diagnostic function • Intelligent fan operation, automatically changing rotation speed depending on system requirements, to decrease power consumption and noise • Input circuit breaker to ease recovery from overloads • CE mark and safety approval from CE • Communication options: USB port, Liebert IntelliSlot® port and terminal block communication • Dry contacts for remote monitoring • Input power factor greater than 0.99 • Output voltage selection function 1.2 Available Models Available models of the UPS are listed in Table 1: Table 1 UPS models, power ratings
Model
Nominal Power Rating
GXT4-700RT230 GXT4-700RT230E
700VA/630W
GXT4-1000RT230 GXT4-1000RT230E
1000VA/900W
GXT4-1500RT230 GXT4-1500RT230E
1500VA/1350W
GXT4-2000RT230 GXT4-2000RT230E
2000VA/1800W
GXT4-3000RT230 GXT4-3000RT230E
3000VA/2700W
Liebert® GXT4™ 4 Product Description 1.3 Appearance and Components 1.3.1 Appearance The Liebert GXT4 rack/tower models in various power ratings have the same general appearance, controls and features (see Figure 1). The various rack/tower models differ largely in the type of receptacles each has. Figure 1 Liebert GXT4-700RT230 - GXT4-3000RT230 UPS Operation and Display Panel Ventilation Slots 1.3.2 Rear Panel Features The rear panel of the Liebert GXT4 has these features: • Liebert IntelliSlot® Port • USB port • Input Circuit Breaker • Input Receptacle • General Output Receptacles • Programmable Output Receptacles • Cable Strain Relief Attachment Hole • External Battery Connector • Cooling Fan • RS-232 port • Terminal Block Communication • Output Circuit Breakers (only on GXT4-3000RT230/230E models) Figure 2 Rear components, Liebert GXT4 230V 700VA and 1000VA models

Liebert IntelliSlot Port USB Port General Output Receptacle, 2 Programmable Output Receptacle #2, 2 Input Circuit Breaker

Terminal Block RS232 Port Cooling Fan External Battery Connector Programmable Output Receptacle #1 - 2 Input Receptacle

5 Liebert® GXT4™ Product Description Figure 3 Rear components, Liebert GXT4 230V 1500VA models

Liebert IntelliSlot Port USB Port Dry Contacts RS232 Port Fan Input Circuit Breaker External Battery Connector C14 Input General Output Outlet1 Receptacles (Programmable ) Outlet2 Receptacles Programmable

Figure 4 Rear components, Liebert GXT4 230V 2000VA models

Liebert IntelliSlot Port USB Port Input Circuit Breaker C20 Input Programmable Outlets #1

Terminal Block Communications RS232 Port Cooling Fan External Battery Connector Non-Programmable Outlets Programmable Outlets #2

Figure 5 Rear components, Liebert GXT4 230V 3000VA models

Liebert IntelliSlot Port USB Port Input Circuit Breaker Output Circuit Breakers Programmable Outlets #1 Non-Programmable Outlet

Terminal Block Communications RS232 Port Cooling Fan External Battery Connector General Output Programmable Outlets #2 C20 Input Receptacle

Liebert® GXT4™ 6 Product Description

1.4 Major Components The operating principle of the UPS is shown in Figure 6. Figure 6 Operating principle diagram Dynamic Bypass Programmable Outlet Group 1

L TVSS Rectifier/PFC DC-DC EMI/RFI L

NN

G EMI/RFI Input Filter Converter Inverter Battery Charger Battery Output Filter G Programmable Outlet Group 2 General Outlet Group General Outlet (3000 VA Only)

The UPS is composed of mains input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery charger, DC-to-DC converter, battery, dynamic bypass and UPS output. Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters The Liebert GXT4 has surge protection and filters that protect the connected load from power surges and sags, electromagnetic interference (EMI) and radio frequency interference (RFI). These features can minimize any surges or interference present in the mains power. The filters also prevent surges or interference generated by the UPS from adversely affecting other devices connected on the same branch as the UPS. Rectifier/Power Factor Correction (PFC) Circuit In normal operation, the Liebert GXT4’s rectifier/power factor correction (PFC) circuit converts mains power to regulated DC power for use by the inverter while ensuring that the wave shape of the input current used by the UPS is near ideal. Extracting this sine wave input current achieves two objectives: • Efficient power use by the UPS • Reduced reflected harmonics This results in cleaner power being available to other devices in the building that are not protected by the UPS. Inverter In normal operation, the Liebert GXT4’s inverter utilizes the DC output of the PFC circuit to produce precise, regulated sine wave AC power. When mains power fails, the inverter receives DC power from the battery through the DC-to DC converter. In either operation mode, the UPS inverter is online, continuously generating clean, precise, regulated AC output power. Battery Charger The battery charger utilizes energy from the mains power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the Liebert GXT4 is plugged in, even when the UPS is not turned On. 7 Liebert® GXT4™ Product Description DC-to-DC Converter The DC-to-DC converter raises the DC voltage from the battery to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, increasing reliability. Battery The Liebert GXT4 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life, operate the Liebert GXT4 in an ambient temperature of 0°C to 25°C (32°F to 77°F). Optional external battery cabinets are available to extend battery run times. Dynamic Bypass The Liebert GXT4 provides an alternate path for mains power to the connected loads in the unlikely event of a UPS malfunction. Should the Liebert GXT4 have an overload, overtemperature, or UPS failure condition, the UPS automatically transfers the connected loads to bypass. NOTE The bypass power path does not protect the connected loads from disturbances on the mains. 1.5 Operating Mode The UPS operation modes include the following: Mains (AC) Mode, Bypass Mode, Battery Mode, Battery Recharge Mode, Active ECO Mode and Frequency Converter Mode. Refer to 3.0 - Operation and Display Panel for details about the operating mode indicators and control buttons. 1.5.1 Mains Mode During Mains Mode, the mains provides input power to the Liebert GXT4. The filters, PFC circuit and inverter process this power to provide high-quality sine wave power to connected loads. The UPS maintains the batteries in a fully charged state. 1.5.2 Manual Bypass Mode Manual Bypass Mode occurs when the unit is manually placed in internal bypass by navigating the LCD display menu to select 3 Control > 1 Turn On & Off > Turn UPS Bypass. Bypass operation is indicated by an audible alarm and illuminated amber bypass indicator. (If other indicators are illuminated, refer to 7.0 - Troubleshooting). During Bypass Mode, mains power bypasses the inverter and provides energy to the connected load. NOTICE Risk of loss of power to the connected load. Can cause equipment damage. Turning Off the UPS in Bypass Mode will result in loss of output power to the connected load. Liebert® GXT4™ 8 Product Description 1.5.3 Battery Mode The Liebert GXT4 enters Battery Mode when mains power fails or is outside acceptable limits. The battery system supplies power through the DC-to-DC converter to the inverter to generate clean AC power for the connected loads. When the Liebert GXT4 enters Battery Mode, the UPS sounds a half-second beep at 10-second intervals. When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to warn that the battery is getting low (this Low Battery Warning is user-configurable). In Battery Mode, the battery indicator will illuminate and the LCD will show the prompt Silence Alarm and choices of Yes and No. The default is No. Press either the Up or Down arrow button to select Yes, then press the Enter button to silence the alarm. Once the alarm prompt has been acknowledged, the UPS will display the estimated battery run time and battery capacity. Refer to 7.0 - Troubleshooting. For approximate battery run times, refer to Table 17. NOTICE Risk of loss of power to the connected load. Can cause equipment damage. Turning Off the Liebert GXT4 when it is in Battery Mode will result in loss of output power to the connected load. If the UPS is turned Off manually, it must be manually restarted after mains power returns. If the UPS is turned Off by a communication signal or because the batteries are depleted, it will operate as set in the configuration program for Auto-Restart (Refer to 5.2.1 - Configuration Program). 1.5.4 Battery Recharge Mode Once mains power is applied to the Liebert GXT4, the Battery Charger begins charging the batteries. 1.5.5 Frequency Converter Mode All models of the Liebert GXT4 are capable of frequency conversion. Frequency Conversion Mode can be selected using the configuration program. Allowable frequency operating modes include: • Auto Sensing - 50Hz or 60Hz – Bypass Enabled • Auto Sensing - 50Hz or 60Hz – Bypass Disabled • Frequency Converter - 50Hz – Bypass Disabled • Frequency Converter - 60Hz – Bypass Disabled NOTE The default for all models of the Liebert GXT4 is “Auto Sensing - 50Hz or 60Hz – Bypass Enabled.” ! CAUTION Risk of electric shock. Can cause injury or death. Never touch the AC input receptacle while the UPS is operating. Voltage may still be present even when the AC input indicator is Off. 1.5.6 Active ECO Mode All Liebert GXT4 models can operate in Active ECO Mode. In this mode, the connected equipment is powered through the bypass path to increase efficiency, reducing the electrical costs. Active ECO mode keeps the rectifier and inverter operating, allowing the inverter to remain synchronized to bypass. This synchronization allows the transfer of the connected equipment to UPS inverter power almost seamlessly if bypass power falls outside the user-set limits. Once bypass power returns within the acceptable parameters, the UPS will return to Active ECO Mode operation. The default setting is Active ECO Mode Off. 9 Liebert® GXT4™ Installation 2.0 INSTALLATION 2.1 Unpacking and Inspection Unpack the UPS and conduct the following checks: • Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local dealer or Emerson® representative immediately. • Check the accessories against the delivery list. If there is any discrepancy, contact your local dealer or your Emerson representative immediately. 2.2 What’s Included • Terminal Block Communication Terminals • Compact Disk with: • Liebert MultiLink® Shutdown Software • Configuration Program • User Manual • USB Cable—one, 1.2m (3.9 ft.) long • RS-232 Cable—one, 2m (6-1/2 ft) long • Cable Strain Relief—two pieces • Rack mounting hardware, including screws, handles and mounting rail kit (not included with “E” models) • Plastic tower stand sets—two (four pieces) • Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance) With 700VA - 1500VA Units: • 10A IEC C13 C14 Output Cable—two, 2m (6-1/2 ft.) long • CEE 7/7 (Schuko) to IEC C13 input cord—one, 2.5m (8-1/2 ft.) long (not included with “E” models) • BS 1363 (UK) to IEC C13 input cord—one, 2.5m (8-1/2 ft.) long (not included with E models) • Australian type A to SAA input cord—one (except “E” models) With 2000VA - 3000VA Units: • 10A IEC C13 C14 Output Cable—three, 2m (6-1/2 ft.) long • CEE 7/7 (Schuko) to IEC C20 Input Cable—one, 2.5m (8-1/5 ft.) long (not included with “E” models) • BS1363 (UK) to IEC C20 Input Cable—one, 2.5m (8-1/5 ft.) long (not included with “E” models) • Australian type A to SAA input cord—one (not included with “E” models) NOTE The GXT4 External Battery Cabinet shipping package includes one battery cabinet, two spacers for tower configuration and one DC power cable and rack mounting hardware, including screws, handles and mounting rail kit (not included with “E”) models. 2.3 Preparation for Installation 2.3.1 Installation Environment • Install the UPS indoors in a controlled environment where it cannot be accidentally turned Off. The installation environment should meet the specifications in 9.0 - Specifications. • Place the UPS in an area where airflow around the unit is unrestricted and away from water, flammable liquids, gases, corrosives and conductive contaminants. Avoid direct sunlight. NOTE Operating the Liebert GXT4 in temperatures above 25°C (77°F) reduces battery life. Liebert® GXT4™ 10 Installation Installation Clearances Maintain a clearance of at least 100mm (4 inches) in the front and rear of the Liebert GXT4. Do not obstruct the air inlets on the front panel or rear panel of the UPS—blocking the air inlets reduces ventilation and heat dissipation, shortening the service life of the Liebert GXT4. 2.4 Mechanical Installation The Liebert GXT4 may be installed as a tower or in a rack, depending on space and use considerations. The Liebert GXT4 may be used alone, as a single UPS, or with up to six battery cabinets. NOTE When installing the UPS or making input and output connections, comply with all relevant safety codes and standards. 2.4.1 Tower Installation To install the Liebert GXT4 as a tower: 1. Take the support bases from the accessories package (see Figure 7). Figure 7 Support bases Spacers Connectors Support Bases 2. If optional Liebert external battery cabinets will be connected to the Liebert GXT4, take out the spacers delivered with the battery cabinet. 3. Connect the spacers and the support bases as shown in Figure 7. Each Liebert GXT4 needs two assembled support bases, one in the front and one in the rear. 4. Adjust the direction of the operation and display panel and logo on the Liebert GXT4. a. Remove the front plastic bezel cover (see Figure 8). Figure 8 Remove the front plastic bezel cover Front Plastic Bezel Cover Operation and Display Panel Rotated Clockwise 90 Degrees b. Pull the operation and display panel, rotate it 90 degrees clockwise and snap it back into position (see Figure 8). c. Pull the logo on the front plastic bezel cover, rotate it 90 degrees clockwise and snap it back into position. The rotated front plastic bezel cover is shown in Figure 9. d. Replace the front plastic bezel cover on the Liebert GXT4. At this point, the UPS operation and display panel and logo have been rotated 90 degrees clockwise, which provides upright viewing for users. 11 Liebert® GXT4™ Installation 5. Place the Liebert GXT4 and any battery cabinets on the support bases. Each Liebert GXT4 needs four support bases, as shown in Figure 9. Figure 9 Tower installation Liebert GXT4 UPS and

Liebert GXT4 UPS 2.4.2 Rack Installation External Battery Cabinet Operation and Display Panel Rotated for Tower Operation Support Bases Support Bases

The Liebert GXT4 UPS and external battery cabinets (EBC), when installed in a rack enclosure, must be supported by a shelf or rack-mount rails. The Liebert GXT4 UPS and EBC units ship with all required hardware to allow rack-mount installation (not included with “E” models). Because different rack-mount options install differently, refer to the installation instructions provided with the rack mount kit being used. 2.5 Cable Connection The Liebert GXT4 rear panel has an input receptacle and output receptacles. Refer to 1.3.2 - Rear Panel Features for details. The battery cables are supplied with the battery cabinet. 2.5.1 Connecting to AC Mains and Loads NOTE Ensure that all the loads are turned Off. Prepare an input power supply that is properly protected by a circuit breaker in accordance with national and local electrical codes. The wall receptacle must be grounded. Emerson® recommends installing an upstream circuit breaker of the same or higher rating as the Liebert GXT4’s input circuit breaker. The specification of input circuit breaker on the rear panel of the UPS is given in Table 2. Table 2 Input circuit breaker specifications
Unit Rating
Circuit Breaker Rating
700-1500 VA Models
10A
2000-3000VA Models
16A
Liebert® GXT4™ 12 Installation For North America Installations Detachable Power Supply Cord Not Provided. Power Supply Cord Selection (for units which power supply cord not furnished with) - Use UL Listed detachable power supply cord, three conductors, minimum 4.5 ft. (1.5m), maximum 14.8 ft. (4.5m) long. Types SP-2, SP-3, SV and similar cords may be provided if the cord is not long. Refer to Tables 3 and 4 for details. Table 3 Type of cord
UPS Model
Type of Cord
GXT4-700RT230, GXT4-700RT230E GXT4-1000RT230, GXT4-1000RT230E GXT4-3000RT230, GXT4-3000RT230E
SVE, SVO, SVOO, SVT, SVTO, SVTOO, SPE-2, SPT-2, NISP-2, NISPE-2, NISPT-2, SPE-3, SPT-3, SJ, SJE, SJO, SJOO, SJT, SJTO, SJTOO, S, SE, SO, SOO, ST, STO, STOO
Table 4 Ratings of cord
UPS Model
Minimum Wire Gauge
Minimum Cord Ratings
Attachment Plug Ratings
GXT4-3000RT230 GXT4-3000RT230E
12 AWG/3C
250 V, 105oC, VW-1
20 A, +250V (NEMA L6-20P)
GXT4-700RT230 GXT4-700RT230E GXT4-1000RT230 GXT4-1000RT230E
16 AWG/3C
250 V, 105oC, VW-1
15 A, +250V (NEMA L6-15P)
Liebert GXT4 models 700-1500VA and 2000VA have three groups of outlets as shown in Figures 2, 3 and 5. One group is always On; the other two groups may be controlled with either programmed responses or over an SNMP network. The 3000VA GXT4 UPS has four groups of outlets: two groups are not controlled (always On), and two groups may be controlled with either programmed responses or over an SNMP network. Verify that the equipment is plugged into the appropriate outlets if any outlets will be controlled with these features. 1. Plug equipment into the appropriate output receptacles on the rear of the Liebert GXT4. NOTE 1. Do not overload any output receptacle. 2. Output cable length should not exceed 10m (32.8 ft). 2. Plug the input receptacle of the Liebert GXT4 into the input power connection. 3. Install the two cable strain relief fixtures to secure either the input or output cables to prevent accidental disconnection. a. Insert one end into the provided holes on the rear of the unit. b. Place the power cord(s) inside the loop. c. Tighten the loop around the cables. Figure 10 Cable strain relief Hold the cable Insert into the provided hole to secure the line buckle 13 Liebert® GXT4™ Installation 2.5.2 Connecting Battery Cables 1. Verify that the battery isolation breaker is in the Off (open) position. 2. Take out the battery cable included with the battery cabinet. 3. Connect one end of the battery cable to the external battery connector on the rear panel of the UPS, and connect the other end to any battery port on the rear panel of the battery cabinet. 4. Repeat Steps 1 through 3 for each battery cabinet that will be connected to the system. Additional battery cabinets will plug into the previously installed battery cabinet. 5. Switch On the battery breaker on the rear of the external battery cabinet. 6. Use the configuration program included with the UPS to specify the number of external battery cabinets connected to the Liebert GXT4. See Table 17 for approximate battery run times. Figure 11 Battery cable attachment Battery Cable Liebert GXT4 External Battery Cabinet 2.6 Connecting Communication Cables Communication cable connection includes USB and optional card cables. 2.6.1 Connecting USB Communication Cables 1. Remove the USB communication cables from the accessories bag. 2. Insert one end of the USB communication cable to the USB port on the rear panel of the Liebert GXT4 (see Figure 2). 3. Insert the other end of the USB communication cable to the USB port of the computer. 2.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cables 1. Remove the protective cover from the Liebert IntelliSlot port on the Liebert GXT4 and set it aside. 2. Insert the Liebert IntelliSlot card into the Liebert IntelliSlot port and secure it with screws. 3. To connect any cable associated with a Liebert IntelliSlot card, refer to the user manual provided with the card. To configure and use the Liebert IntelliSlot communication card, refer to the card’s user manual. Manuals for the various Liebert IntelliSlot cards are available at Liebert’s Web site: liebert.com Liebert® GXT4™ 14 Operation and Display Panel 3.0 OPERATION AND DISPLAY PANEL This chapter describes the Liebert GXT4 controls, particularly the operation and display panel on the front of the Liebert GXT4. The panel has four control buttons, seven LED indicators and a liquid crystal display (LCD), as shown in Figure 12. Figure 12 Operation and display panel

Inverter Indicator Liebert® GXT4™ AC Power System Fault Battery Indicator Bypass Indicator Programmable Outlet1 Indicator

Indicator ESC Button 1 2 ESC Programmable Outlet2 Indicator ECO Mode Indicator Enter Button

Up Button Down Button 3.1 LED Indicators The seven LED indicators on the front of the operation and display panel are: • Inverter • Battery • Bypass • Programmable Outlet1 • Programmable Outlet2 • ECO Mode • Fault Figure 12 shows the indicators’ locations; their descriptions and functions are shown in Table 3. Table 3 LED indicators
LED Indicators
LED Color
Description
Inverter
Green
On when the inverter is supplying power
Bypass
Amber
On when the load is supplied by the mains through automatic/manual bypass
Battery
Amber
On when the load is supplied by the battery
Fault
Red
On when an error has occurred within the UPS
Programmable Outlet1
Green
On when programmable Outlet1 is On
Programmable Outlet2
Green
On when programmable Outlet2 is On
ECO Mode
Green
On when the UPS is in ECO Mode
15 Liebert® GXT4™ Operation and Display Panel 3.2 Control Buttons The four control buttons on the front of the operation and display panel are: • ESC • Up • Down • Enter Figure 12 shows the buttons’ locations; their descriptions and functions are shown in Table 4. Table 4 Control buttons
Control Buttons
Description
ESC Button
Pressing this button returns to the previous menu or aborts any change in the input data field before confirming.
Up Button
Pressing this button can move the cursor up or increase the value displayed in the input data field. When a menu is displayed on several screens, pressing the button can scroll up.
Down Button
Pressing this button can move the cursor down or decrease the value displayed in the input data field. When a menu is displayed on several screens, pressing the button can scroll down.
Enter Button
Pressing this button can enter the next level menu or confirm the parameter setting value.
3.3 LCD The LCD panel shows the UPS status and enables changes to the UPS settings by assisting in navigating through the Liebert GXT4’s menu (see 3.4 - Menu Structure). Liebert® GXT4™ 16 Operation and Display Panel 3.4 Menu Structure The menu structure of the LCD is shown in Figure 13. Figure 13 Menu structure Audible Alarm Output

Start Windows System Status Status Configuration Load Input Battery Time Since Startup UPS Startup on Bypass Enable Auto Shutdown Enable Auto Restart Frequency Selection Output Level Selection Battery Cabinets

Main Menu Control Log Turn UPS On/Off Alarm Control Batt Test View Log Clear Log Turn UPS On Turn UPS Off 1. Audible Alarm On 2. Audible Alarm Off 1. Start 2. Cancel 3. Batt Test Result BATT ECO Mode Outlet 1 Low Battery Time Warning Batt Test Interval Batt Replace Time Enable/Disable Voltage Tolerance Frequency Tolerance Requalification Time Turn On

About Network PN/SN/Firmware Version Address: MAC Address: IPV4 Address: IPV6STATIC Address: IPV6AUTO Address: IPV6LINK Outlet 2 Factory Default LCD Control Setting Language Color Turn Off Reboot Settings as Outlet1 (only Outlet2) Turn On Delay Turn Off When UPS On Battery and On Overload Turn Off When UPS On Battery for Some Time Turn On When Power Returns for Some Time Turn Off When Runtime Less Than Some Time Turn Off When Batt Capacity Less Than Some Time 1 English 2 French

17 Liebert® GXT4™ Operation and Display Panel 3.4.1 Startup Screen When the Liebert GXT4 is starting up, it initiates a self-test and displays the screen shown in Figure 14 for about 10 seconds. Figure 14 Startup screen EMERSON Network Power After about 10 seconds, the LCD shows one of the On screens in Figure 15; the screen shown depends on whether input power is available. Figure 15 Startup screens

TURN ON UPS YES NO O/P: 0V HZ 0.0A I/P : 230V 50HZ 0.0A BATT: 100% 320MINS LOAD: 0% AC NOT AVAILABLE START ON BATTERY? YES NO O/P: 0V 0HZ 0.0A I/P : 230V 50HZ 0.0A BATT: 100% 320MINS LOAD: 0%

Input Power is Available Input Power is Not Available To turn on the UPS, press either the Up or Down button to select YES and press the Enter button. The UPS will start up, the LCD will display UPS STARTING and then START SUCCESSFUL after the UPS is turned On, as shown in Figure 16. Figure 16 Starting and Start Successful screens

UPS STARTING O/P: 0V 0HZ 0.0A I/P : 230V 50HZ 0.0A BATT: 100% 320MINS LOAD: 0% START SUCCESSFUL O/P: 230V 50HZ 4.6A I/P : 230V 50HZ 5.0A BATT: 100% 15MINS LOAD: 40%

Liebert® GXT4™ 18 Operation and Display Panel 3.4.2 Default Screen Press any button in the START SUCCESSFUL screen to enter the default interface, shown in Figure 17. Figure 17 Default screen GXT4-UPS 3KVA Values shown will vary according to installation and configuration. O/P: 230V 50HZ 11.7A I /P: 230V 50HZ 13.1A BATT: 100% 3MINS LOAD: 100% In the default screen, the LCD shows the UPS model, output parameters, input parameters, battery capacity with run time estimate and load percentage. The UPS operation mode (online /inverter, ECO, Battery or Bypass) will be indicated by the LED indicators. If no control button (ESC, Up, Down, Enter) is pressed for 2 minutes, the LCD will enter the screen saver mode (backlight turns off). It will remain off until a control button is pressed. 3.4.3 Main Menu Screen Press the Enter button in the default screen to enter the MAIN MENU screen, as shown in Figure 18. Figure 18 Main Menu screen 1 STATUS 2 CONFIGURATION 3 CONTROL 4 LOG 5 ABOUT 6 NETWORK To select a submenu, press the Up or Down button to move the cursor to the required item, then press the Enter button to enter its submenu or set its parameter. STATUS Screen In the MAIN MENU screen, select STATUS to enter the Status Screen, displaying OUTPUT, LOAD, INPUT, BATTERY and TIME SINCE STARTUP, as shown in Figure 19. 19 Liebert® GXT4™ Operation and Display Panel

Figure 19 Status screens OUTPUT VOLTAGE : 120V FREQUENCY : 60HZ CURRENT : 17.6A POWER : 2112KWH BATTERY LOAD CAP : 90% WATT : 1620W VA : 1800VA INPUT VOLT : 120V FREQ : 60 HZ CURR : 18.6A POWER : 97KWH

CAPACITY : 90% RUNTIME : 100MINS VOLTAGE : 80V CONFIGURATION Screen TIME SINCE STARTUP 05D 15H 30M

Select MAIN MENU > CONFIGURATION to enter the Configuration menu. This menu has seven submenus, as shown in Figure 20. Figure 20 CONFIGURATION screen 1. UPS 2. BATTERY 3. ECO MODE 4. OUTLET 1 5. OUTLET2 6. LCD 7. FACTORY DEFAULT In the CONFIGURATION screen, press the Up or Down button to move the cursor to the required item, then press the Enter button to enter a submenu or set its parameters. Liebert® GXT4™ 20 Operation and Display Panel UPS Screen Select MAIN MENU > CONFIGURATION > UPS to enter the UPS screen. This menu has six screens, as shown in Figure 21. Figure 21 UPS screens

AUDIBLE ALARM OFF ENABLE AUTO RESTART YES STARTUP ON BYPASS NO FREQUENCY SELECTION AUTO - BYPASS ENABLE GUARANTEE SHUTDOWN NO VOLTAGE SELECTION 230

Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings. Battery Screen Select MAIN MENU > CONFIGURATION > BATTERY to enter the BATTERY screen. This menu has four screens, as shown in Figure 22. Figure 22 Battery screen

EXT BATT CABINET 0 CABINETS BATT TEST INTERVAL 8 WEEKS LOW BATTERY TIME 2 MINS BATT REPLACE TIME2014 Y 1 M 1 D

Press the Up or Down button to increase or decrease the value of the settings, and press the Enter button to confirm it. 21 Liebert® GXT4™ Operation and Display Panel ECO Mode Screens Select MAIN MENU > CONFIGURATION > ECO MODE to enter the ECO MODE screens, as shown in Figure 23. Figure 23 ECO Mode screen

ECO MODE ON FREQUENCY TOLERANCE 3 Hz VOLTAGE TOLERANCE 10% REQUALIFICATION TIME 5 MINS

Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings. Outlet1 Screen Select MAIN MENU > 2 CONFIGURATION > 4 OUTLET1 to enter the OUTLET1 screen. This menu has two submenus, as shown in Figure 24. Figure 24 Outlet1 screen OUTLET1 1 OUTLET CONTROL 2 OUTLET SETTING Liebert® GXT4™ 22 Operation and Display Panel Select 1 OUTLET CONTROL and press the Enter button to enter the OUTLET CONTROL screen, as shown in Figure 25. Figure 25 Outlet Control screen

OUTLET CONTROL TURN OFF REBOOT OUTLET CONTROL TURN ON

Outlet Control is On Outlet Control is Off Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings. Select 2 Outlet Setting and press the Enter button to enter the OUTLET SETTING screen, as shown in Figure 26. Figure 26 Outlet Setting screen

TURN ON DELAY 0 MINS TURN OFF WHEN UPS ON OVERLOAD AND ON BATTERY NO TURN OFF WHEN UPS ON BATTERY FOR OFF TURN ON WHEN POWER RETURNS: 0 MINS

TURN OFF WHEN RUNTIME LESS THAN OFF TURN ON WHEN POWER RETURNS: 0 MINS TURN OFF WHEN BATT CAPACITY LESS THAN OFF TURN ON WHEN POWER RETURNS: 0 MINS

Press the Up or Down button to move the cursor to the required item, and press the Enter button to confirm the settings. 23 Liebert® GXT4™

Outlet2 Screen Operation and Display Panel

The Outlet2 screens are the same as the Outlet1 screens. The same settings are available as on the Outlet1 screen. If the Outlet2 group will have the same settings as the Outlet1 group, the Liebert GXT4 offers a programming shortcut, as shown in Figure 27. When configuring the Outlet2 group, the select YES and press the Enter button to apply the Outlet1 settings to the Outlet2 screen. Figure 27 Outlet2 setting screen APPLY THE SAME SETTINGS AS OUTLET1 YES NO LCD screen Select Main Menu -> 2 CONFIGURATION -> 6 LCD to enter the LCD screen. This menu has two submenus, as shown in Figure 28. Figure 28 LCD screen 1 LANGUAGE 2 COLOR Select 1 LANGUAGE and press the Enter button to enter the LANGUAGE screen, as shown in Figure 29. The Liebert GXT4 is capable of supporting multiple languages. For the list of supported languages and instructions on how to upload them, refer to the Configuration Program user manual on the included CD. Figure 29 Language screen 1 English

2

Liebert® GXT4™ 24 Operation and Display Panel Select 2 COLOR and press the Enter button to enter the COLOR screen, as shown in Figure 30. Figure 30 Color screen EMERSON EMERSON EMERSON EMERSON FACTORY DEFAULT screen Select MAIN MENU -> 2 CONFIGURATION -> 7 FACTORY DEFAULT to enter the FACTORY DEFAULT screen, as shown in Figure 31. Figure 31 Factory Default screen RESET ALL SETTINGS TO FACTORY DEFAULT SETTINGS? YES NO Control Screen Select MAIN MENU -> 3 CONTROL to enter the CONTROL screen. This screen has three submenus, as shown in Figure 32. Figure 32 Control screen 1 TURN ON & OFF 2 ALARM CONTROL 3 BATT TEST In the CONTROL screen, press the Up or Down button to move the cursor to the required item, and press the Enter button to enter its submenu. 25 Liebert® GXT4™ Operation and Display Panel TURN ON & OFF screen Select MAIN MENU -> 3 CONTROL -> 1 TURN ON & OFF to enter the TURN ON & OFF screen. This screen shows one of two displays, depending on the state of the UPS, as shown in Figure 33. Figure 33 Turn UPS On or Off screen

TURN ON UPS TURN OFF UPS TURN ON UPS BYPASS

UPS is Off UPS is On ALARM CONTROL screen Select MAIN MENU -> 3 CONTROL -> 2 ALARM CONTROL to enter the ALARM CONTROL screen, as shown in Figure 34. This section allows active audible alarms to be silenced. To completely turn off the audible alarm, refer to CONFIGURATION > UPS as shown in Figure 21. Figure 34 Alarm Control screen 1 AUDIBLE ALARM ON 2 AUDIBLE ALARM OFF BATT TEST screen Select MAIN MENU -> 3 CONTROL -> 3 BATT TEST to enter the BATT TEST screen, as shown in Figure 35. Figure 35 Batt Test screen 1 START 2 CANCEL 3 BATT TEST RESULT Liebert® GXT4™ 26 Operation and Display Panel Log Screen Select MAIN MENU -> 4 LOG to enter the LOG screen. This screen has two submenus, as shown in Figure 36. Figure 36 Log screens 254/255

1 VIEW LOG 2 CLEAR LOG CLEAR LOG Screen 255 OD 1H 17m AGO UPS switch to Online mode

Select MAIN MENU > LOG > CLEAR LOG to enter the CLEAR LOG screen, as shown in Figure 37. Figure 37 Clear Log screen DO YOU WANT TO CLEAR EVENT LOGS? YES NO Press the Up or Down button to move the cursor to the required item. Press the Enter button to confirm the settings. ABOUT Screen Select MAIN MENU> ABOUT to enter the ABOUT screen, as shown in Figure 38. Figure 38 About screen PN: GXT4-2000RT230 SN:1XXX60XXX1AFCXX FW VER: U100D100 HW VER: H100 The ABOUT screen displays UPS model, serial number, software version and hardware version. 27 Liebert® GXT4™ Operation and Display Panel Network Select MAIN MENU>NETWORK to enter the NETWORK screen. The NETWORK screen displays the MAC address and the IPv4 IP address. If the Liebert GXT4 is fitted with an optional Liebert IntelliSlot Web card (Liebert IS-WEBCARD), the screen will display IPv6 IP address settings (IPv6 requires configuration), as shown in Figure 39. Figure 39 Network screens

ADDRESS MAC 00-02-11-4X-AX ADDRESS IPV4 10.163.226.231/24 ADDRESS IPV6 STATIC ::

ADDRESS IPV6 AUTO :: ADDRESS IPV6 LINK Fe80::202:99ff:fe0f:4ba 2%1

Liebert® GXT4™ 28

3.4.4 Prompt List Operation and Display Panel

A prompt screen is displayed during the operation of the system to alert you to certain conditions and/or to require your confirmation of a command or other operation. See Table 5 for the system prompts and meanings. Table 5 Prompts and meanings
Prompt
Meanings
Mains Power Restored
The mains power returns and the UPS transfers back to mains (AC) mode.
UPS Return From A Low Battery Condition
The UPS transfers back to mains (AC) mode from battery low mode.
UPS Return From Battery Mode
The UPS transfers back to mains (AC) mode from battery mode.
UPS Self Test Successful
The UPS self-test is successfully performed.
UPS Shutdown Command Received
The UPS shut down was initiated through communication.
UPS Turn Off
The UPS shuts down and has no output power.
UPS Turn On
The UPS starts up successfully and supplies protected power to the load.
UPS Shutdown Process Had Been Cancelled
The shutdown command sent through Liebert MultiLink or SNMP card to the UPS is canceled,
ECO Mode Enabled
The UPS is configured to ECO mode operation,
ECO Mode Disabled
The UPS is configured to Online mode, supplying protected power to the load through the inverter.
UPS Internal Temperature Return To Normal
The internal temperature of the UPS recovers to normal range.
UPS Load Return From Overload
The loads are reduced, and the UPS recovers to normal state from overload.
Load On Inverter
The inverter is on and supplies protected power to the load.
Load On ECO Bypass
The UPS is on ECO mode; the mains is supplying power to the load directly to reduce energy usage.
OUTLET1 Closed Auto / Manual
The programmable output receptacle 1 received a turn-off command and is turned Off.
OUTLET1 Open Auto / Manual
The programmable output receptacle 1 received a Turn-On command and is turned On
OUTLET2 Closed Auto / Manual
The programmable output receptacle 2 received a Turn-Off command and is turned Off.
OUTLET2 Open Auto / Manual
The programmable output receptacle 2 received a turn-on command and is turned On.
Bypass Power Restored
The bypass power recovered and the UPS can now transfer to bypass.
3.4.5 Warning List All UPS warning messages are described in Table 6. Table 6 Warning list
Warning
Description
Mains Power Not Available
The mains power is not available, or it cannot satisfy the input requirements for the UPS to operate from mains power
UPS Batteries Low And Exhausted Soon
The battery capacity is low and will be exhausted soon
UPS Has Switched To Battery Mode
The mains power is abnormal or the PFC side is faulty, the UPS transfers back to Battery mode
Load On Bypass
The UPS transfers to Bypass mode, at this point, the input mains power supplies power to the load directly, and the load is not protected
Input Power Wiring Error
L-N line reverse or PE not connected.
Bypass Power Not Available
The bypass power is not available, or it cannot satisfy the requirements for the UPS transfers to bypass
UPS Maintenance Bypass Output
The UPS transfers to maintenance bypass.
29 Liebert® GXT4™ Operation and Display Panel 3.4.6 Fault List All UPS fault messages are described in Table 7. Table 7 Fault list
Fault
Description
UPS Self-Test Failed
The battery is bad or weak or not connected.
UPS Overload
The UPS is overloaded.
Inverter Out Of Order
The inverter has failed.
Battery Weak/Bad
The battery is bad or weak.
Output Short Circuit
The output connection is short-circuited.
DC Bus Overvoltage
The DC bus is faulty.
UPS Overtemperature
Overtemperature occurs to the UPS and the UPS will transfer to Bypass mode.
Charger Out Of Order
The charger has failed.
Fan Out Of Order
At least one fan is failed.
DC Bus Discharge Fail
DC-DC failure occurs.
Rectifier Out Of Order
Rectifier failure occurs.
If a fault occurs, the UPS automatically switches to Bypass Mode. The original operating mode will be maintained only in the case of a battery disconnection fault. The fault message alternates with UPS Mode once a second, the red fault indicator on the operation and display panel lights up and the alarm sounds continuously. If a fault occurs, proceed as follows: 1. Enter the ALARM CONTROL screen (see Figure 34), and select AUDIBLE ALARM ON or AUDIBLE ALARM OFF to switch the alarm On or Off. 2. Enter the EVENT LOG screen (see Figure 36), and select VIEW LOG to view the entire Event log. NOTE There will be a short delay before the EVENT LOG screen displays the historical fault log to allow the log to load. Liebert® GXT4™ 30 Operation 4.0 OPERATION This section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual bypass, shutting down the UPS and disconnecting mains power from the UPS. NOTE The Liebert GXT4’s battery has been fully charged before delivery, but some charge will be lost during storage and shipping. To ensure that the battery has adequate reserve power to protect the connected load, charge the battery for three hours before putting the UPS into service. 4.1 Startup Checklist for the Liebert GXT4 Before starting the UPS, perform these checks: ___ 1. Check that the input plugs and loads are connected properly and reliably. ___ 2. Check that the battery cable is connected properly. ___ 3. Check that the communication cables are connected properly. 4.2 Starting the UPS 1. Plug the UPS into the appropriate AC outlet. 2. 3000VA models only—Close the input breaker on the rear of the unit. 3. The UPS will begin the startup sequence once AC power is present. NOTE The UPS will sound an audible alarmist is normal 4. On the LCD, press either the Up or Down button once, then press the Enter button to turn on the UPS. The UPS will sound the audible alarm again when the output receptacles are being supplied by the internal bypass. It will sound one more time as the inverter powers the connected equipment. 5. Check the LCD and LED indicators to ensure the UPS is operating normally. 6. Check the load percentage on the default screen to ensure the connected equipment is not exceeding the UPS rated capacity. The UPS is now providing conditioned power to the connected load. 4.3 Manual Battery Test To initiate a manual battery test, select MAIN MENU > CONTROL>BATT TEST>START. • If the battery test results show FAILED, allow the UPS to recharge the batteries for 24 hours. • Retest the batteries after 24 hours of charging. • After the batteries have been retested, if the battery test still shows FAILED, contact your local Emerson® representative or Emerson Network Power Channel Support. 4.4 Manual Bypass To manually transfer the connected equipment to the internal bypass: 1. From the main menu select CONTROL, then press Enter. 2. Select TURN ON & OFF and press Enter. 3. Select TURN UPS BYPASS and press Enter. The UPS will transfer the connected loads to the internal bypass. If the internal bypass is not available because of mains power problems, pressing this button once will be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other indicators are illuminated, refer to 7.0 - Troubleshooting.) 31 Liebert® GXT4™ Operation 4.5 Shut Down the Liebert GXT4 To shut down the UPS from the LCD: 1. From the Main Menu select CONTROL, press Enter, then select TURN ON & OFF. 2. Press the enter key. 3. Select TURN UPS OFF, then press Enter. 4. Press either the Up or Down button to move the cursor to confirm the shutdown command and press Enter. The UPS will sound an audible alarm; this is normal. Power to the connected equipment is now Off. 5. The UPS display will still be illuminated because the batteries are still being charged. The UPS display will still be illuminated because the batteries are still being charged. The UPS may now be disconnected from AC power, and the UPS will completely shut down in approximately 15 seconds. 4.6 Disconnecting Input Power from the Liebert GXT4 1. After the UPS has been shut down as detailed in 4.5 - Shut Down the Liebert GXT4, disconnect the input cable from the wall socket. 2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the power-off is complete. 3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet. After powering Off the UPS, the UPS ceases output and the load is powered Off. Liebert® GXT4™ 32 Communication 5.0 COMMUNICATION This section describes the four types of communication ports on the rear of the UPS: • Liebert IntelliSlot® port • USB port (standard B-type) • Terminal Block Communication • RS232 port (DB9F) ! CAUTION To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables. 5.1 Liebert IntelliSlot Communication Cards The Liebert IntelliSlot port accepts four optional cards: • Liebert IntelliSlot Web Card (IS-WEBCARD) • Liebert IntelliSlot Relay Card (IS-RELAY) • Liebert IntelliSlot MultiPort Card (IS-MULTIPORT) • Liebert IntelliSlot Unity Card (IS-UNITY-DP) The Liebert IntelliSlot Web Card provides SNMP monitoring and control of the UPS across the network. The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers support for Liebert MultiLink® shutdown software. The Liebert IntelliSlot MultiPort Card provides four sets of contacts for support of up to four computers that have Liebert MultiLink installed. The Liebert IntelliSlot Unity Card provides SNMP and/or RS-485 monitoring of the UPS across the network and/or building management system. The Liebert IntelliSlot UNITY card also enables monitoring external temperature, humidity and contact closure inputs using external sensors. (The Liebert IS-UNITY-DP compatibility will be a future release, contact your Emerson sales representative for availability.) Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any additional ancillary product for the Liebert GXT4. These instructions are available at: multilink.liebert.com 5.1.1 Liebert MultiLink Liebert MultiLink monitors the UPS continuously and can shut down the computer or server in the event of an extended power failure. Liebert MultiLink can also be configured to shut down the UPS. Liebert MultiLink can communicate with the UPS via the USB port, RS232 port, contact closures via terminal block or over the network via SNMP using the Liebert IS-WEBCARD. An optional Liebert MultiLink license kit permits shutting down multiple computers that are protected by the UPS. For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and Liebert MultiLink License Kits, visit the Liebert Web site ( liebert.com) or contact your local Emerson® representative. 33 Liebert® GXT4™ Communication 5.2 USB Port Communication The standard B-type USB port is used to connect the UPS and network server or other computer system using Liebert MultiLink®. A standard B-type USB port is provided to allow connection to a computer or network server. The USB port can be used to communicate with the Liebert GXT4 configuration program (see section 5.2.1 for details) or Liebert MultiLink (refer to 5.1.1 - Liebert MultiLink for description) that is provided on the CD that is included with the UPS. 5.2.1 Configuration Program The configuration program is on the Liebert GXT4 CD and can be used instead of making configuration setting changes from the LCD panel. The configuration program communicates to a computer running a Microsoft® Windows® operating system via the included USB cable. For most users, the factory default settings are adequate. This section give a brief overview of the features and parameters that are available for modification, as well as the factory default settings. Should any changes be necessary, refer to the Configuration Program User Manual that is located on the included CD for further details. The configuration program allows these features of the Liebert GXT4 to be changed: • Change and set the display language • Enable/Disable Auto-Restart (default is Enable) • Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass disabled (default is Auto-Select with bypass enabled) • Set the Low Battery Warning alarm time from 2 to 30 minutes (default is 2 minutes) • Enable/Disable the Auto-Battery test (default is Enable) • Enable/Disable Auto-Restart after removing Remote shutdown (default is Disable) • Set the wiring mode of Remote shutdown (default is normally open) • Set the Auto-Enable output after remote shutdown (default is Disable) • Set the Auto-Battery test to 8, 12, 16, 20, or 26 weeks (default is 8 weeks) • Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculated by Emerson® software products (default is zero) • Select one of multiple output voltages to match various voltages (see Table 8). Table 8 Output voltage option, all models
Factory Default Setting
Output Voltage Option
230VAC
200V, 208V, 220V, 230V, 240V
NOTICE The output voltage settings cannot be changed while the UPS is On and powering connected loads. NOTE Programming the output voltage of a 230V model of the Liebert GXT4 to 220V automatically derates the UPS to 96% of both the VA and watt ratings (refer to 9.0 - Specifications for VA and watt ratings). NOTE • This program is compatible with UPS models beginning with ‘GXT4,’ as in ‘GXT4-3000RT230.’ It is not compatible with earlier versions of the Liebert GXT UPS. • A computer running Microsoft® Windows 2000®, Windows XP®, Windows Vista®, Windows 7 or Windows 8 is required to set up and run the configuration program. Liebert® GXT4™ 34 Communication 5.3 RS-232 Port The RS-232 port uses an Emerson® proprietary protocol that is for use with Liebert MultiLink®. This port enables a more secure connection instead of the USB cable, to the computer or server that has Liebert MultiLink installed. 5.4 Terminal Block Communication The Terminal Block includes eight pins, as shown in Figure 40. Figure 40 Terminal Block Communication pin layout

1 2 3 4 5 6 7 8 5.4.1 Any Mode Shutdown Any Mode Shutdown Battery Mode Shutdown On Battery Mode Low Battery

The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and static switch so that there is no power to the loads. Any Mode Shutdown can be operated locally or remotely: • Local Any Mode Shutdown can be performed by shorting Pin 1 and Pin 2. • Remote Any Mode Shutdown can be performed using a switch connected to Pin 1 and Pin 2 and mounted at a remote location. NOTE Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown, depending on the settings in the configuration program. A current-limited source for this optocoupler (+12VDC, 50mA) will be available from the UPS. The connection to the UPS for remote connection will be via terminal block connector. Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations. ! WARNING When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1 and Pin 2, the Liebert GXT4’s output can turn On automatically and without warning if the Pin 1 and Pin 2 connection is changed. 35 Liebert® GXT4™ Communication 5.4.2 Battery Mode Shutdown Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active. Battery Mode Shutdown can be performed locally or remotely: • Local Battery Mode shutdown can be performed by shorting Pin3 and Pin4. • Remote Battery Mode Shutdown can be performed using a switch connected to Pin3 and Pin4 and mounted at remote location. NOTE Remote Power Off will be performed by NO contact. A current-limited source (+12VDC, 50mA) will be available from UPS. The connection to the Liebert GXT4 for remote connection will be via terminal block connector. Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws. This signal must last for 1.5 seconds or longer. A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown timer. This timer cannot be stopped once triggered. If the mains power returns during this countdown, the Liebert GXT4 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting. 5.4.3 On Battery On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry contact will be closed. 5.4.4 Low Battery Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed. NOTE The rated values for the dry contacts for the On Battery and Low Battery signals are: • Rated Voltage: 30V (AC or DC) • Rated Current: 300mA Liebert® GXT4™ 36 Maintenance 6.0 MAINTENANCE This section describes replacing the internal battery pack, precautions, checking the Liebert GXT4’s status and checking UPS functions. ! WARNING The battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the battery pack: • Remove rings, watches and other metal objects. • Use tools with insulated handles. • Do not lay tools or other metal objects on the batteries. • If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson® representative immediately. • Do not dispose of batteries in a fire. The batteries may explode. • Handle, transport and recycle batteries in accordance with local regulations. 6.1 Replacing the Internal Battery Pack The Liebert GXT4 is designed to allow the user to replace the internal battery pack safely. Refer to Table 9 for internal battery pack part numbers for Liebert GXT4 UPS: Table 9 Replacement battery pack model numbers
UPS Rating, VA
Replacement Internal Battery Pack Model #
Quantity Required
700/1000
GXT4-5A48BATKIT
1
1500
GXT4-9A48BATKIT
1
2000
GXT4-9A48BATKIT
1
3000
GXT4-9A72BATKIT
1
Read all safety cautions before proceeding. A trained user can replace the internal battery pack when the UPS is always in a restricted access location (such as a rack or server closet). Contact your local dealer or Emerson representative to obtain the pricing of the appropriate replacement battery pack. ! CAUTION Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the instructions. 37 Liebert® GXT4™ Maintenance 6.1.1 Battery Replacement Procedures 1. Gently remove the front plastic bezel cover from the UPS. 2. Loosen and remove the six screws on the battery door, as shown in Figure 41. 3. Lay the battery door and screws aside for reassembly. Figure 41 Removing the front plastic bezel cover and battery door 4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown in Figure 42. Figure 42 Disconnecting the battery plug and battery connector (front view) Battery Connector Battery Receptacle 5. Grasp the battery handle and pull the internal battery pack out of the UPS, as shown in Figure 43. Figure 43 Pulling out the battery Internal Battery Pack Battery Handle Pull Out with Battery Handle 6. Unpack the new internal battery pack. Take care not to destroy the packing. Compare the new and old internal battery packs to make sure they are the same type and model. If they are the same, proceed with Step 7; if they are different, stop and contact your local Emerson® representative or Emerson Channel Support. 7. Line up and slide in the new internal battery pack. 8. Reconnect the battery plug and battery receptacle 9. Gently push the battery wire and internal battery pack back into the UPS. Liebert® GXT4™ 38 Maintenance 10. Reattach the front battery door with the six screws. 11. Reattach the front plastic bezel cover to the UPS. NOTE The internal battery pack is hot-swappable. However, caution should be exercised because during this procedure the load is unprotected from disturbances and power outages. Do not replace the battery while the UPS is in Battery Mode. This will result in a loss of output power and will drop the connected load. 6.2 Battery Charging The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design life. The Liebert GXT4 charges the batteries continuously when it is connected to the mains input power. If the Liebert GXT4 will be stored for a long time, Emerson recommends connecting the UPS to input power for at least 24 hours every three to four months to ensure full recharge of the batteries. 6.3 Precautions Although the Liebert GXT4 has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions: • Turn Off and unplug the Liebert GXT4 before cleaning it. • Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners. • Never block or insert any objects into the ventilation holes or other openings of the UPS. • Do not place the Liebert GXT4 power cord where it might be damaged. 6.4 Checking UPS Status Emerson® recommends checking the UPS operation status every six months. • Check whether the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm? • Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal Mode. If it is operating in Bypass Mode, stop and contact your local Emerson representative, or Emerson Channel Support. • Check whether the battery is discharging. When the mains input is normal, the battery should not discharge. If the UPS is operating in Battery Mode, stop and contact your local Emerson representative or Emerson Channel Support. 39 Liebert® GXT4™ Troubleshooting 7.0 TROUBLESHOOTING This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation. 7.1 UPS Symptoms The following symptoms indicate the Liebert GXT4 is malfunctioning: • The relative indicators illuminate, indicating the UPS has detected a problem. • An alarm buzzer sounds, alerting the user that the UPS requires attention. 7.1.1 Indicator and LCD In addition to the fault indicator being illuminated, the LCD will display the fault. The displayed fault on the LCD is described in Table 10 Table 10 Description of the displayed fault
Displayed Fault
Cause
Corrective Steps
UPS self test failed
The battery is bad or weak.
Contact customer service.
UPS shutdown command received
The UPS shuts down through communication.
Contact customer service.
UPS overload
The UPS is overloaded.
Reduce the load and contact customer service.
Inverter Out of Order
The inverter is faulty.
Contact customer service.
Battery Weak/Bad
The battery is bad or weak.
Replace the battery.
Output Short Circuit
The output connection is short-circuited.
Shut down the equipment and contact customer service.
DC Bus Overvoltage
The DC bus is faulty.
Contact customer service.
UPS Overtemperature
Over-temperature occurs to the UPS and the UPS will transfer to Bypass mode.
Reduce the load and contact customer service.
Charger Out of Order
The charger is faulty.
Contact customer service.
Fan Out of Order
At least one fan is faulty.
Contact customer service.
DC Bus Discharge Fail
A DC-DC failure occurs.
Contact customer service.
NOTE If the UPS encounters a fault and no correction attempt is performed within 2 minutes, the LCD backlight will flash (on 1 second and off 1 second) as an alert. Press any button to exit the alert mode. If no correction attempt is performed on the UPS, the LCD backlight will flash again until the UPS fault is corrected. Liebert® GXT4™ 40 Troubleshooting 7.1.2 Audible Alarm An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating status. The audible alarm will sound as described in Table 11. Table 11 Audible alarm description
Condition
Alarm
Battery discharge
Half-second beep every 10 seconds
Low battery
Two half-second beeps every 5 seconds
UPS fault, load on bypass
1-second beep every 4 seconds
UPS fault, no power to load
Continuous
Overload
Half-second beep every half second
Battery replacement
2-second beep every 2 minutes
Battery loss
Continuous
Wiring problem (loss of proper grounding for UPS)
Continuous
Bypass reminder
1-second beep every 60 seconds
7.2 Troubleshooting In the event of an issue with the UPS, refer to Table 12 to determine the cause and solution. If the fault persists, contact Emerson® Channel Support. Table 12 Troubleshooting table
Problem
Cause
Solution
UPS fails to start
UPS is short-circuited or overloaded
Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally.
Batteries are not charged enough or not connected
Check to ensure the internal battery is connected. If it is not, make the connection and try to start the unit. If the battery is connected, leave the UPS connected to input power for 24 hours to recharge batteries, then try to start the unit.
Battery indicator is illuminated
UPS is not plugged in
UPS is operating from battery mode. Ensure UPS is securely plugged into the wall receptacle.
UPS input protection fuse has blown/opened
UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then restart UPS.
Mains power is out of tolerance
UPS is operating from battery mode. Save data and close applications. Ensure mains supply voltage is within acceptable limits for UPS.
UPS has reduced battery backup time
Batteries are not fully charged
Keep UPS plugged in continuously at least 24 hours to recharge batteries.
UPS is overloaded
Check load level indicator and reduce the load on the UPS.
Batteries may not be able to hold a full charge due to age
Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support for replacement battery kit.
Battery indicator is flashing.
Battery source is not available; continuous horn.
Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed.
Bypass indicator is flashing.
Because the voltage or frequency is outside acceptable limits, the bypass is disabled.
The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this indicator will flash, indicating that the bypass is unavailable.
When reporting a UPS issue to Emerson, include the UPS model and serial number. These are located in several places for your ease of location: on the top panel (rack mount orientation); the left side (tower orientation); the rear panel; on the front of the unit behind the front plastic bezel; and on the LCD select MAIN MENU > ABOUT. 41 Liebert® GXT4™ Battery Cabinet 8.0 BATTERY CABINET Optional battery cabinets are available for the Liebert GXT4. The external battery connector and isolation breaker are on the battery cabinet’s rear panel, as shown in Figure 44. For battery cabinet specifications, refer to Table 15. Figure 44 Battery cabinet Isolation Breaker External Battery Connector ! WARNING Do not contact the external battery connector and ground without wearing protective gloves and clothing and taking other precautions against electrical shock. The battery loop and AC input are not insulated, which may cause a dangerous voltage between the external battery connector and ground. NOTE External battery connectors are wired in parallel. Either connector can be connected to the UPS or to another battery cabinet. NOTE The length of the standard battery cable delivered with the battery cabinet is 0.65m (2.13ft). Liebert® GXT4™ 42 Specifications 9.0 SPECIFICATIONS The specifications of the Liebert GXT4 are listed in Table 13 and Table 14. Table 13 Specifications of GXT4-700RT230/230E and GXT4-1000RT230/230E UPS
Parameters
Product model
GXT4-700RT230 GXT4-700RT230E
GXT4-1000RT230 GXT4-1000RT230E
Model Rating
700VA/630W
1000VA/900W
Dimensions, D x W x H, mm (in)
Unit
408 x 430 x 85 (16.2 x 16.9 x 3.4)
Shipping
617 x 570 x 262 (24.3 x 22.4 x 10.3)
Weight, kg (lb)
Unit
18.2 (40)
Shipping
24 (53); “E” model 20 (44)
Input AC
Voltage Range (typical)
230VAC nominal; variable based on output load
90% ~ 100% loading
177VAC/280VAC
70% ~ 90% loading
168VAC/280VAC
30% ~ 70% loading
150VAC/280VAC
0 ~ 30% loading
115VAC/280VAC
Frequency
40Hz ~ 70Hz; Auto Sensing
Input Power Receptacle
C14
Output AC
AC-AC Efficiency
> 88% AC-AC, minimum
Output Receptacles
C13 × 6
Voltage
200/208/220/230/240VAC (user configurable); ±3%
Frequency
50Hz or 60Hz
Waveform
Sine wave
Mains (AC) Mode Overload
200% for 2 seconds; 150% for 50 seconds with transfer to bypass
Internal Battery Charger
Charger Current, Amperes
1.3
Battery
Type
Valve-regulated, nonspillable, lead acid
Qty × V× Rating
4 × 12V × 5.0Ah
Battery Mfr/Part#
YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245
Backup Time
See Table 17 - Battery run times
Recharge Time
3 hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only)
Environmental Requirements
Operating Temp
0ºC to +40ºC (+32ºF to +104ºF); Table 16 - Operating temperature parameters
Storage Temp
-15ºC to +50ºC (5ºF to 122ºF)
Relative Humidity
0%RH to 95%RH, non-condensing
Operating Elevation
Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating
Storage Elevation
15,240 (50,000 ft.) maximum
Audible Noise
< 46 dBA, at 1 meter (3.2ft) from the rear < 43 dBA, at 1 meter (3.2ft) from the front or sides
Agency
Safety
IEC/EN/AS 62040-1:2008, GS mark; UL 1778 Listed
RFI/EMI
IEC/EN/AS 62040-2 2nd Ed (Category C2) = CISPR22 Class A
Surge Immunity
IEC/EN 62040-2 2nd Ed (IEC/EN 61000-4-5)
Transportation
ISTA Procedure 1A
43 Liebert® GXT4™ Specifications Table 14 Specifications of the Liebert GXT4-1500RT230/230E, GXT4-2000RT230/230E and GXT-3000RT230/230E
Parameters
Product model
GXT4-1500RT230 GXT4-1500RT230E
GXT4-2000RT230 GXT4-2000RT230E
GXT4-3000RT230 GXT4-3000RT230E
Model Rating
1500VA/1350W
2000VA/1800W
3000VA/2700W
Dimensions, D x W x H, mm (in)
Unit
497 × 430 × 85 (19.6 x 16.9 x 3.3)
602 × 430 × 85 (23.7 x 16.9 x 3.3)
Shipping
617 x 570 x 262 (24.3 x 22.4 x 10.3)
717 x 570 x 262 (28.2 x 22.4 x 10.3)
Weight, kg (lb)
Unit
23.2 (51.1)
25.5 (56.1)
32.4 (71.4)
Shipping
30 (66.1) “E” model: 26 (57.3)
32 (70.5) “E” model: 28 (61.7)
39 (86) “E” model: 35 (77.2)
Input AC
Voltage Range (typical)
230VAC nominal; variable based on output load
90% ~ 100% loading
177VAC/280VAC
196VAC/280VAC
70% ~ 90% loading
168VAC/280VAC
184VAC/280VAC
30% ~ 70% loading
150VAC/280VAC
161VAC/280VAC
0 ~ 30% loading
115VAC/280VAC
115VAC/280VAC
Frequency
40Hz ~ 70Hz; Auto Sensing
Input Power Receptacle
C14
C20
Output AC
AC-AC Efficiency
> 88% AC-AC, minimum
Output Receptacles
C13 x 6
C13 x 6; C19 x 1
Voltage
200/208/220/230/240VAC (user configurable); ±3%
Frequency
50Hz or 60Hz
Waveform
Sine wave
Mains (AC) Mode Overload
200% for 2 seconds; 150% for 50 seconds
200% for 2 seconds; 150% for 55 seconds
Internal Battery Charger
Charger Current, Amperes
1.88
2.71
2.5
Battery
Type
Valve-regulated, nonspillable, lead acid
Qty × V× Rating
4 × 12V × 9.0Ah
6 × 12V × 9.0Ah
Battery Mfr/Part#
Panasonic/UP-RW1245; CSB/ HR 1234W F2; CSB/UPS 12460 F2
Backup Time
See Table 17 - Battery run time
Recharge Time to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only)
4 hours
3 hours
Environmental Requirements

Operating Temp 0ºC to 40ºC (32ºF to 104ºF); Table 16 - Operating temperature parameters
Storage Temp
-15ºC to +50ºC (5ºF to 122ºF)
Relative Humidity
0%RH to 95%RH, non-condensing
Operating Elevation
Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating
Storage Elevation
15000m (50,000 ft.) maximum
Audible Noise
< 45 dBA max. at 1 meter (3.2ft.) front and side < 46 dBA, at 1 meter (3.2ft.) rear
< 48 dBA max. at 1 meter (3.2ft.) front and side < 48 dBA, at 1 meter (3.2ft.) rear
Agency
Safety
IEC/EN/AS 62040-1:2008, GS mark; (3000VA model: UL 1778 Listed)
RFI/EMI
IEC/EN/AS 62040-2 2nd Ed. (Category C2) = CISPR22 Class A
Surge Immunity
IEC/EN 62040-2 2nd Ed. (IEC/EN 61000-4-5)
Transportation
ISTA Procedure 1A
Liebert® GXT4™ 44 Specifications Table 15 Battery cabinet specifications
Parameter
Model Number
GXT4-48VBATT GXT4-48VBATTE
GXT4-72VBATT GXT4-72VBATTE
Used w/UPS Model
GXT4-700RT230/230E, GXT4-1000RT230/230E, GXT4-1500RT230/230E, GXT4-2000RT230/230E
GXT4-3000RT230/230E
Dimensions, D x W x H, mm (in)
Unit
497 × 430 × 85 (19.7 x 16.9 x 3.3)
602 × 430 × 85 (23.6 x 16.9 x 3.3)
Shipping
617 x 570 x 262 (24.3x 22.4 x 10.3)
717 x 570 x 262 (28.2 x 22.4 x 10.3)
Weight, kg (lb)
Unit
32 (70.5)
42 (92.6)
Shipping
39 (86) “E” model 35 (77.2)
50 (110) “E” model 46 (101.4)
Battery parameters
Type
Valve-regulated, nonspillable, lead acid
Qty × V× Rating
2 × 4 × 12V × 9.0Ah
2 × 6 × 12V × 9.0Ah
Battery Mfr/Part#
Panasonic/UP-RW1245 CSB/HR 1234W F2; CSB/UPS 12460 F2
Backup Time
See Table 17 - Battery run times
Environmental
Operating Temperature
0ºC to 40ºC (32ºF to 104ºF)
Storage Temperature
-15ºC to +40ºC (19ºF to 104ºF)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 3000m (10,000 ft.) at 40ºC (104ºF) without derating
Storage Elevation
15000m (50,000 ft.) maximum
Agency
Safety
IEC/EN/AS 62040-1:2008, GS mark
RFI/EMI
FCC Part 15, Class A=CISPR22 Class A
Surge Immunity
IEC 62040-2 2nd Ed.: 2006
Transportation
ISTA Procedure 1A
Table 16 Operating temperature parameters
Ambient Temperature, °C (°F)
25-30 (77-86)
30-35 (86-95)
35-40 (95-104)
Maximum Output Power Factor Derating @ Maximum Load
100%-93%
93%-86%
86%-79%
45 Liebert® GXT4™ Specifications Table 17 Battery run times
Number of Batteries/Cabinets
Load Percent of Capacity
Run Time, Minutes *
700VA
1000VA
1500VA
2000VA
3000VA
Internal Battery
10%
105
91
112
81
91
20%
62
38
51
37
39
30%
37
31
34
23
23
40%
32
23
23
16
16
50%
27
17
18
12
12
60%
22
14
14
9
9
70%
18
11
11
7
7
80%
15
9
9
5
5
90%
13
8
7
4
4
100%
11
6
6
3
3
Internal Battery + 1 External Battery Cabinet
10%
427
334
330
222
302
20%
303
166
160
137
139
30%
164
138
128
94
95
40%
145
108
97
66
66
50%
126
92
72
49
48
60%
106
72
54
39
41
70%
94
56
46
34
34
80%
78
48
38
28
27
90%
69
40
34
23
23
100%
61
37
31
20
21
Internal Battery + 2 External Battery Cabinets
10%
480
457
447
426
431
20%
434
333
315
201
205
30%
329
224
186
149
150
40%
273
166
151
124
124
50%
203
151
131
97
97
60%
164
135
107
75
76
70%
153
113
92
61
63
80%
142
103
74
50
50
90%
131
92
64
41
45
100%
121
78
53
38
41
Internal Battery + 3 External Battery Cabinets
10%
480
480
467
451
455
20%
461
442
424
322
325
30%
439
337
311
195
196
40%
345
305
199
154
155
50%
323
208
160
136
136
60%
300
166
146
111
112
70%
213
155
131
96
98
80%
189
144
111
78
79
90%
163
132
99
68
70
100%
156
122
83
56
60
Liebert® GXT4™ 46 Specifications Table 17 Battery run times (continued)
Number of Batteries/Cabinets
Load Percent of Capacity
Run Time, Minutes *
700VA
1000VA
1500VA
2000VA
3000VA
Internal Battery + 4 External Battery Cabinets
10%
480
480
480
466
480
20%
480
460
444
421
423
30%
458
436
340
306
307
40%
442
340
309
192
192
50%
425
315
205
157
157
60%
336
218
165
142
143
70%
319
195
153
127
128
80%
301
165
141
107
109
90%
213
156
130
95
97
100%
197
147
112
80
81
Internal Battery + 5 External Battery Cabinets
10%
480
480
480
480
480
20%
480
467
457
438
440
30%
465
447
431
331
332
40%
452
428
333
224
225
50%
438
341
307
189
189
60%
425
320
208
158
159
70%
344
227
167
146
147
80%
329
208
158
133
135
90%
315
189
148
120
122
100%
301
164
139
104
106
Internal Battery + 6 External Battery Cabinets
10%
480
480
480
480
480
20%
480
480
466
450
452
30%
480
458
444
420
421
40%
462
442
422
319
319
50%
451
426
328
217
217
60%
440
341
305
186
187
70%
428
323
209
159
160
80%
368
306
184
148
150
90%
336
217
161
137
139
100%
325
201
153
126
128
* The times above are approximate. They are based on new, fully charged standard batteries at a temperature of 25°C (77°F) with 100% resistive UPS loading. The listed run times can vary by ±5% because of manufacturing variances of the batteries. 47 Liebert® GXT4™ Specifications 9.1 Product Warranty Registration Registration is not required to activate the product warranty on a Liebert UPS. Registration is required to qualify for the Product Protection Promise. To register, visit the Emerson Network Power® Web site to fill out the online form at: emersonnetworkpower.com/en-US/Forms/Pages/LiebertProductWarrantyRegis tration.aspx • To contact warranty support by e-mail: dpg.warranty@emerson.com 9.2 Technical Support Technical support contacts are listed on the back cover of this document. To contact Emerson Channel Product Support: Phone • NORTH AMERICA: 1-800-222-5877 • OUTSIDE NORTH AMERICA: 00-800-1155-4499 E-mail • TECHNICAL SUPPORT: liebert.upstech@emerson.com Liebert® GXT4™ 48

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2014 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SLI-23196_REV0_10-14 Emerson Network Power Liebert emerson.com Technical Support / Service Web Site liebert.com Monitoring liebert.monitoring@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Single-Phase UPS & Server Cabinets liebert.upstech@emerson.com 800-222-5877 Outside North America: +00800 1155 4499 Three-Phase UPS & Power Systems 800-543-2378 Outside North America: 614-841-6598 Environmental Systems 800-543-2778 Outside the United States: 614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257 Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines +63 2 687 6615 Fax: +63 2 730 9572


FREE ENGLISH PDF

OPERATING INSTRUCTIONS

USER GUIDE - USER MANUAL

OWNER GUIDE - OWNER MANUAL

REFERENCE GUIDE - REFERENCE MANUAL

INSTRUCTION GUIDE - INSTRUCTION MANUAL

Leave a Reply