What is the function of the KDV 72, KDV 96, and KDV 35 voltmeters?

These models measure the voltage value of any line (AC+DC) very accurately in true RMS. Any line can be measured between 0…500V.

What is the function of the KDV 72-3F, KDV 96-3F, and KDV 35-3F voltmeters?

These models measure the true RMS voltage value of the line very accurately.

How is the voltage displayed on the KDV 72-3F, KDV 96-3F, and KDV 35-3F models?

The measured values for the lines are shown every 3 seconds in a cycle.

How can a specific line’s voltage be continuously observed on the KDV 72-3F, KDV 96-3F, or KDV 35-3F models?

If the user would like to observe the value of any specific line, the user needs to select the desired value. The selected value will be shown continuously for 60 seconds, after which the device will begin cycling through the line values again.

What are the technical specifications for the KDV series voltmeters?

Code Display Measurement Range Dim. Weight (kg)
KDV 72 3 Digit, Red, 14mm 0..500V Figure-1 0,20
KDV 96 3 Digit, Red, 14mm 0…500V Figure-2 0,24
KDV 72-3F 3 Digit, Red, 14mm L1: 180V…260V
L2: 5…300V
L3: 5…300V
Figure-1 0,20
KDV 96-3F 3 Digit, Red, 14mm L1: 180V…260V
L2: 5…300V
L3: 5…300V
Figure-2 0,24
KDV 35 3 Digit, Red, 10mm 0…500V Figure-3 0,19
KDV 35-3F 3 Digit, Red, 10mm L1: 180V…260V
L2: 5…300V
L3: 5…300V
Figure-3 0,19

Accuracy: ± (%1+1)

Class: 0,5

Supply Voltage: 220 Vac ±%20, 50 / 60 Hz

Power Consumption: < 3 VA

Ambient Temperature: -5°C…+ 55°C


How should the KDV 72 and KDV 96 models be connected?

These models have four terminals. Two terminals are for the Measurement Input, and the other two are for the Supply Input. Refer to the Connection Schemes diagram for KDV 72 / KDV 96 for specific terminal locations.

How should the KDV 72-3F and KDV 96-3F models be connected?

These models have four terminals labeled L3, L2, L1, and N. These terminals are used for both supply and measurement input. Refer to the Connection Schemes diagram for KDV 72-3F / KDV 96-3F for specific terminal connections.

How should the KDV 35 model be connected?

The KDV 35 model has four terminals. Two terminals are labeled L and N for Measurement Input, and the other two are labeled L and N for Supply Input. Refer to the Connection Schemes diagram for KDV 35 for specific terminal locations.

How should the KDV 35-3F model be connected?

The KDV 35-3F model has four terminals labeled L3, L2, L1, and N. These terminals are used for both Supply and Measurement Input. Refer to the Connection Schemes diagram for KDV 35-3F for specific terminal connections.

What are the physical dimensions of the KDV series voltmeters?

Figure-1 (applies to KDV 72 and KDV 72-3F):

Front Bezel: 72 mm (W) x 72 mm (H)

Panel Cutout: 65 mm x 65 mm

Depth behind panel: 73 mm

Figure-2 (applies to KDV 96 and KDV 96-3F):

Front Bezel: 96 mm (W) x 96 mm (H)

Panel Cutout: 90 mm x 90 mm

Depth behind panel: 64 mm

Figure-3 (applies to KDV 35 and KDV 35-3F):

Front Bezel Width (approx): 45 mm (based on terminal block width)

Overall Height: 65 mm

Panel Cutout Height: 50 mm (inner dimension)

DIN Rail Mount Width: 35 mm

Overall Depth: 58 mm

Depth from front face to mounting clip surface: 35.3 mm

Height from DIN rail bottom edge to top: 65 mm

Panel Cutout Width: 34 mm (inner dimension)