What are the specifications of the HONEYWELL TC809D1004?

SPECIFICATIONS VALUE
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.4 mA (LED on)
Average Operating Current: 750 μΑ (LED Flashing)
EOL Resistance: 47K Ohms
Maximum SLC Wiring Resistance: 40 Ohms
Maximum IDC wiring resistance: 1,500 Ohms
Maximum IDC Voltage: 11 Volts
Maximum IDC Current: 240 μΑ
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 4 1/2 in H x 4.275 in W x 1.4 in D (Mounts to a 4 in square by 2 1/8 in deep box.)
Accessories: SMB500 Electrical Box

What should I do before installing the HONEYWELL TC809D1004?

This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.


What is the general function of the HONEYWELL TC809D1004?

The HONEYWELL TC809D1004 Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent 2-wire initiating device circuits (IDC), at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices, or either normally open or normally closed security devices. The TC809D1004 is also UL listed as a commercial proprietary burglar alarm accessory.


How do I mount the HONEYWELL TC809D1004?

The HONEYWELL TC809D1004 mounts directly to 4-inch square electrical boxes. The box must have a minimum depth of 2 1/8 inches. Surface mounted electrical boxes (SSDSMB500) are available.


What are the wiring instructions for the HONEYWELL TC809D1004?

NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power limited wiring only.

1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams.

2. Set the address on the module per job drawings.

3. Secure module to electrical box (supplied by installer).


How is the address set on the HONEYWELL TC809D1004?

The HONEYWELL TC809D1004 provides two independent circuits, L and H, at consecutive addresses.

Monitor module L (using terminals 6 and 7) responds at the address set on the code switches. Monitor module H (using terminals 8 and 9) will automatically respond at the next higher address. For example, if the code switches are set to 76, module L will respond at address 76 and module H will respond at address 77. Use caution to avoid duplicate addressing of modules on the system.


What are the wiring requirements and limitations for the HONEYWELL TC809D1004?

Signal Line Circuit (SLC):

The SLC has a maximum voltage of 32 VDC. A shielded-twisted pair is recommended for the wiring.

Initiating Device Circuits (L&H):

There are two initiating device circuits. Each is power limited to 240 mA @ 11 VDC MAX. An 47k EOL Resistor (14501600-027 or equal) is required for each circuit.

Device Compatibility and Restrictions:

UL listed contact closure devices may be used. Do not mix fire alarm initiating, supervisory, or security devices on the same initiating device circuit. All wiring shown is supervised and power limited. Install contact closure devices per the manufacturer’s installation instructions.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

CLICK HERE TO DOWNLOAD HONEYWELL TC809D1004 (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.