What are the different configurations and features of the HONEYWELL RP470B (01) pneumatic selector relay?

The HONEYWELL RP470B (01) is a three-port relay that comes in two configurations, RP470A and RP470B, with the following differences:

RP470A Configuration:

• Transmits the higher of two input signals.

• Selects the higher pressure with a sensitivity of .015 psi (1.03 kPa).

• Is used in sensor lines, such as LP914 or LP915 temperature sensors with a 1.25 to 2.50°F (0.68 to 1.3°C) accuracy, depending on sensor span.

• Has a gray body.

RP470B Configuration:

• Locks out one pressure signal when a second pressure signal is higher.

• Functions as a repeater for signal isolation.

• Functions as a lower-of-two-pressures selector.

• Has a gray and black body.


What is required before installing the HONEYWELL RP470B (01) for a lower-of-two-pressures application?

In a lower-of-two-pressures application, the HONEYWELL RP470B (01) requires a 0.007 Filter Restrictor (part no. 14002913-002) if the input is not already restricted, such as a one-pipe device input.


How do I install and mount the HONEYWELL RP470B (01)?

The HONEYWELL RP470B (01) can either be suspended on tubing or mounted on a surface.

For surface mounting:

1. Use the provided mounting clip.

2. Secure the clip to a wall or panel using a No. 10 x 1/2 in. sheet metal screw (obtain locally).

3. Snap the relay into the mounting clip.


What precautions should be taken when connecting or disconnecting tubing from the HONEYWELL RP470B (01)?

All connections on the HONEYWELL RP470B (01) are sharp barb 5/32 in. (4 mm) O.D. polyethylene tubing connections. To prevent damage to these sharp barb connections, do not attempt to cut or pull the tubing off.

To remove tubing correctly:

1. Cut the tubing a few inches from the control device.

2. Use a coupling to reconnect the tubing.


How can I test the HONEYWELL RP470B (01) when it is used as a Higher-of-Two-Pressures Relay (RP470A configuration)?

To check out the HONEYWELL RP470B (01) in this configuration, you must ensure that the higher-of-two-input pressures at Ports 3 and 5 is transmitted through output Port 2.


How can I test the HONEYWELL RP470B (01) when it is used as a Lockout Relay, Repeater, or Lower-of-Two-Pressures selector (RP470B configuration)?

Testing depends on the application:

Lockout Relay application: Ensure that the relay passes the signal at Port 2 to Port 3 if the pressure at Port 5 is lower than the pressure at Port 2. When the pressure at Port 5 is greater than the pressure at Port 2, lockout should occur.

Lower-of-two-pressures application: Make sure that the output is the lower pressure.


What are the technical specifications for the HONEYWELL RP470B (01)?

Models:

• RP470A Higher-of-Two Pressures Relay

• RP470B Lockout Relay or Repeater

Operating Pressure Range:

• Normal: 0 to 18 psi (0 to 124 kPa)

• Maximum: 30 psi (207 kPa)

Maximum Safe Air Pressure: 30 psi (207 kPa)

Ambient Operating Limits:

• Temperature: 0 to 140°F (-18 to 60°C)

• Relative Humidity: 5 to 95%

Air Handling Capacity: 0.039 scfm at 1 psi (18 ml/s at 7 kPa) differential

Construction: Molded plastic with neoprene diaphragm and valox valve seat


How does the HONEYWELL RP470B (01) operate when configured as a Higher-of-Two Pressures Relay (RP470A)?

In the RP470A configuration, the relay compares two input pressures at Port 3 and Port 5.

• When the pressure at Port 3 is greater than the pressure at Port 5, Port 3 supplies the output through Port 2, and the output at Port 2 equals the pressure at Port 3.

• When the pressure at Port 5 is greater than the pressure at Port 3, Port 3 closes off, and the output at Port 2 equals the pressure at Port 5.

NOTE: Accuracy decreases when used with circuits having 0.005 restrictors (e.g., TP974, 0.30 psi) compared with those having 0.007 restrictors (0.15 psi).


How does the HONEYWELL RP470B (01) operate in its standard Lockout/Repeater configuration (RP470B)?

In the RP470B configuration, the operation is as follows:

• When the pressure at Port 2 is greater than the input pressure at Port 5, Port 2 supplies output through Port 3.

• When the pressure at Port 5 is greater than the pressure at Port 2, the diaphragm closes off the output (Port 3). This action prevents the Port 2 signal from passing through Port 3.


What are the port connections when replacing an older relay with the HONEYWELL RP470B (01) for a Higher-of-Two Pressures application?

The following table identifies the ports of older Honeywell pneumatic relays when upgrading to a HONEYWELL RP470B (01) in an RP470A configuration.

Table 1. RP470A Connections for a Higher-of-Two Pressures Application.
RP470A RP405A RP407 RP904A RO48B
Input A 3 P1 M P1 1 & 2
Input B 5 P2 P P2 4 & 5
Output 2 B B1 B 3
Main M

What are the port connections when replacing an older relay with the HONEYWELL RP470B (01) for a Lockout operation?

The following table identifies the ports of older Honeywell pneumatic relays when upgrading to a HONEYWELL RP470B (01) in an RP470B configuration.

Table 2. RP470B Connections for a Lockout Operation.
RP470B RP405A RP407 RP904A RO48B
Output 3 P1 M P1 1 & 2
Pilot 5 P2 P P2 4 & 5
Input 2 B B1 B 3
Main M

How does the HONEYWELL RP470B (01) function as a repeater?

When piped as a repeater, the HONEYWELL RP470B (01) provides circuit isolation by repeating the input pressure with a second air source. The signal at Port 5 blocks Port 3 until the signal at Port 2 builds up a matching pressure. This maintains the pressure at Port 3 to be equal to Port 5. Port 3 acts as an exhaust port in this configuration.


How can the HONEYWELL RP470B (01) be used for a lowest-of-several-pressures selection?

For a lowest-of-several-pressures application, multiple HONEYWELL RP470B (01) relays are used. In this setup, each relay acts as a repeater, but they only repeat the lowest input pressure. It is important to note that all inputs must be isolated, and a restricted main is required for this application.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

CLICK HERE TO DOWNLOAD HONEYWELL RP470B (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.