What are the electrical specifications for the HEATFLO KUH-C-07-71 Power Disconnect Switch Kits?
The following table outlines the electrical data and standard contactor ratings for various models compatible with the disconnect switch kits:
| Model | Volts | kW | Phase | Amps | Standard Contactor Rating (Qty.) |
|---|---|---|---|---|---|
| KUH-C-02-81 | 208 | 2.667 | 1 | 12.8 | – |
| KUH-C-02-21 | 208/240 | 2/2.667 | 1 | 11.1* | – |
| KUH-C-02-71 | 277 | 2.667 | 1 | 9.6 | – |
| KUH-C-04-81 | 208 | 4 | 1 | 19.2 | – |
| KUH-C-04-83 | 208 | 4 | 3 | 11.2 | 30A (1) |
| KUH-C-04-21 | 208/240 | 3/4 | 1 | 16.7* | – |
| KUH-C-04-23 | 208/240 | 3 | 9.6* | 30A (1) | |
| KUH-C-04-71 | 277 | 4 | 1 | 14.5 | – |
| KUH-C-04-43 | 480 | 4 | 3 | 4.8 | 30A (1) |
| KUH-C-05-81 | 208 | 5 | 1 | 24.0 | – |
| KUH-C-05-83 | 208 | 5 | 3 | 13.8 | 30A (1) |
| KUH-C-05-21 | 208/240 | 3.75/5 | 1 | 20.8* | – |
| KUH-C-05-23 | 208/240 | 3.75/5 | 3 | 12.1* | 30A (1) |
| KUH-C-05-71 | 277 | 5 | 1 | 18.2 | – |
| KUH-C-05-43 | 480 | 5 | 3 | 6.0 | 30A (1) |
| KUH-C-07-81 | 208 | 7.5 | 1 | 36.1 | 50A (1) |
| KUH-C-07-83 | 208 | 7.5 | 3 | 20.9 | 30A (1) |
| KUH-C-07-21 | 208/240 | 5.625/7.5 | 1 | 31.1* | 30A (1) |
| KUH-C-07-23 | 208/240 | 5.625/7.5 | 3 | 18.1* | 30A (1) |
| KUH-C-07-71 | 277 | 7.5 | 1 | 27.2 | 30A (1) |
| KUH-C-07-43 | 480 | 7.5 | 3 | 9.0 | 30A (1) |
| KUH-C-10-81 | 208 | 10 | 1 | 48.0 | 50A (1) |
| KUH-C-10-83 | 208 | 10 | 3 | 27.8 | 30A (1) |
| KUH-C-10-21 | 208/240 | 7.5/10 | 1 | 41.7* | 30A (1) |
| KUH-C-10-23 | 208/240 | 7.5/10 | 3 | 24.0* | 30A (1) |
| KUH-C-10-43 | 480 | 10 | 3 | 12.0 | 30A (1) |
| KUH-C-12-83 | 208 | 12.5 | 3 | 34.8 | 50A (1) |
| KUH-C-12-23 | 208/240 | 9.375/12.5 | 3 | 30.1* | 50A (1) |
| KUH-C-12-43 | 480 | 12.5 | 3 | 15.1 | 30A (1) |
| KUH-C-15-83 | 208 | 15 | 3 | 41.8 | 50A (1) |
| KUH-C-15-23 | 208/240 | 11.25/15 | 3 | 36.2* | 50A (1) |
| KUH-C-15-43 | 480 | 15 | 3 | 18.1 | 30A (1) |
| KUH-C-20-23 | 208/240 | 15/20 | 3 | 48.0* | 50A (1) |
| KUH-C-20-43 | 480 | 20 | 3 | 24.0 | 30A (1) |
| KUH-C-25-43 | 480 | 25 | 3 | 30.0 | 50A (1) |
| KUH-C-30-83 | 208 | 30 | 3 | 83.4 | 50A (2) |
| KUH-C-30-23 | 208/240 | 22.5/30 | 3 | 72.2* | 50A (2) |
| KUH-C-30-43 | 480 | 30 | 3 | 36.1 | 30A (2) |
| KUH-C-35-23 | 208/240 | 26.25/35 | 3 | 84.3* | 50A (2) |
| KUH-C-35-43 | 480 | 35 | 3 | 42.1 | 30A (2) |
| KUH-C-40-23 | 208/240 | 30/40 | 3 | 96.0* | 50A (2) |
| KUH-C-40-43 | 480 | 40 | 3 | 48.0 | 30A (2) |
| KUH-C-45-43 | 480 | 45 | 3 | 54.1 | 30A (2) |
*208V amperage is 86% of 240V value.
What preparation steps must be taken before installing the power disconnect kit on the HEATFLO KUH-C-07-71?
1. The amperage rating of the disconnect must be equal to or greater than the amperage rating on Table A and as marked on the nameplate located on the bottom access door.
2. The power disconnect kit is to be installed in the rectangular knockout located in the bottom right corner on the back of the heater. The knockout can be removed using a hammer and chisel or other appropriate means.
For easier access to terminal screws to wire pigtail leads supplied on the heater, it is suggested that these connections be made before installing. See Wiring Instructions.
How do I install the KDS-1 (40 and 50 Amp) disconnect switch on the HEATFLO KUH-C-07-71?
For KDS-1 models:
1. The disconnect switch, with its mounting plate should be inserted into the heater cabinet by opening the bottom service door and positioned behind the opening created in step 2 (rectangular knockout).
2. Insert the four self tapping screws into the four holes in the rear panel. They should engage the holes in the mounting plate and then be tightened until they are secure.
3. Mount the switch faceplate to the switch using the two provided screws. Mount with the “OFF” position to “0” to the left and the on position “1” to the top. Slide the handle over the shaft and tighten the screw to secure.
How do I install the KDS-2 and KDS-3 (80 and 100 Amp) disconnect switches on the HEATFLO KUH-C-07-71?
For KDS-2 and KDS-3 models:
1. The cover plate should be placed over the rectangular opening with its four mounting holes lined up with the four holes in the cabinet and the four holes in the mounting bracket.
2. Insert the four self tapping screws into the four holes until they engage the holes in the mounting bracket and tighten until they are secure.
3. Place plastic bezel over the installed switch and push towards the switch until the tabs snap into place.
How does the Power Disconnect Switch operate on the HEATFLO KUH-C-07-71?
KDS-1: This switch disconnects the power to power leads when the handle is rotated to the “0” position (left). The power is on when the switch handle is rotated to the “1” position (top) position.
KDS-2 and KDS-3: This switch disconnects power to the power leads when the handle is placed in its full lower position. The power is on when the switch handle is in its full upper position.
What are the wiring instructions for the disconnect switch on the HEATFLO KUH-C-07-71?
1. Use the three pigtail leads supplied with the kit (40 & 80 Amp) when connecting to the power line.
a. Use No. 4GA Copper conductor wire only for 100 Amp disconnect when wiring to the power line.
2. The power disconnect wiring to the heater is to be made using the pigtail leads supplied on the heaters up to and including 25 kW. On larger heaters, the installer should supply 105˚C type AWM 600V wire.
Notes:
1. Remove lead wires marked L2 and AL2 when using one phase power service.
2. For units without contactors, disconnect switch is to be wired to lead wires on heater power.
3. Use copper supply wire only with this switch.
What safety warnings must be observed when installing the disconnect switch on the HEATFLO KUH-C-07-71?
ELECTRIC SHOCK HAZARD. Disconnect all power before installing disconnect switch. Failure to do so could result in personal injury or property damage. Disconnect switch must be installed by a qualified person and must be effectively grounded in accordance with the National Electrical Code, NFPA 70.
How should the nameplate be updated after installing a disconnect kit on the HEATFLO KUH-C-07-71?
For future replacement parts, the model number should be modified on the nameplate to show that a disconnect kit has been field installed on the heater. A label kit (P/N 170-302788-002) has been included in the plastic envelope located in the disconnect kit. Cut off the appropriate number for the size disconnect being installed (40 Amp = 1; 80 Amp = 2; 100 Amp = 3). The label has a pressure sensitive adhesive back so that the number can be placed over the “0”.
What replacement parts are available for HEATFLO KUH-C-07-71 Disconnect Switch Kits?
| Disconnect Size | Kit Model # | Disconnect | Cover Plate | Mounting Bracket |
|---|---|---|---|---|
| 50 Amp | KDS-1 | 292-303472-001 | 220-303485-010 | |
| 80 Amp | KDS-2 | 292-303472-002 | 220-303485-003 | 220-303484-003 |
| 100 Amp | KDS-3 | 292-303472-008 | 220-303485-003 | 220-303484-003 |