What is the main function of the FOXESS EPSBOX-SP in a residential power system?
The FOXESS EPSBOX-SP is an auxiliary product suitable for the residential power system that integrates a Smart Meter, Breaker, ATS, and other devices internally. It supports continuous loads up to 100A, enabling whole-house backup power without interruption.
What is the automatic switching time for the FOXESS EPSBOX-SP?
The power supply status of the load can be switched automatically or manually, and the automatic switching time is less than 3 seconds for the FOXESS EPSBOX-SP.
How does the FOXESS EPSBOX-SP switch power sources during a power grid failure?
The FOXESS EPSBOX-SP will automatically switch to the reserve power supply side (EPS terminal of the inverter) to supply power to the load when the power grid fails, and it will switch back to the power grid side to supply power to the load when the power grid is restored.
What are the dimensions of the FOXESS EPSBOX-SP in millimeters?
The dimensions are 446mm in width, 550mm in height (550mm total, 608mm to the top of the enclosure), and 146mm in depth (139mm for the main body, with protrusions).
What are the labels and descriptions for the ferrules/terminals on the FOXESS EPSBOX-SP?
The ferrules are labeled A through G with the following descriptions:
| Item | Description | Item | Description |
|---|---|---|---|
| A | METER/CT/RS485 | E | LOAD |
| B | UTILITY SUPPLY | F | INVERTER EPS |
| C | INVERTER 2 | G | GROUND |
| D | INVERTER GRID |
What are the required pin definitions for the Meter / RS485 interface for KH series when wiring the FOXESS EPSBOX-SP?
The pin definitions for the Meter / RS485 interface for KH series are as follows:
| PIN | 1 | 2 |
|---|---|---|
| Definition | Meter485A | Meter485B |
What are the required pin definitions for the Meter / RS485 interface for HI-G2 series when wiring the FOXESS EPSBOX-SP?
The pin definitions for the Meter / RS485 interface for HI-G2 series are as follows:
| PIN | 1 | 2 |
|---|---|---|
| Definition | Meter485A | Meter485B |
What are the required pin definitions for the Meter / RS485 interface for EVO series when wiring the FOXESS EPSBOX-SP?
The pin definitions for the Meter / RS485 interface for EVO series are as follows:
| PIN | 9 | 10 |
|---|---|---|
| Definition | Meter485A | Meter485B |
What are the reference wire gauge specifications for different interfaces on the FOXESS EPSBOX-SP?
The reference wire gauge specifications are as follows:
| Interface | INVERTER 2/INVERTER GRID/INVERTER EPS | UTILITY SUPPLY/LOAD |
|---|---|---|
| Cable | 14-22mm² | 16-37mm² |
What are the required wire specifications for INVERTER GRID & INVERTER EPS wiring on the FOXESS EPSBOX-SP?
The wire specification and crimping wire outer diameter is 14-22mm. The wire stripping length is 140mm, and the stripping length of the copper-core wire is 14mm (L, N and PE).
Note: The EVO series EPS does not have a PE wire, so its EPS can be used with a two-core cable.
What are the required wire specifications for UTILITY SUPPLY & LOAD wiring on the FOXESS EPSBOX-SP?
The wire specification and crimping wire outer diameter is 16-37mm. The wire stripping length is 140mm, and the stripping length of the copper-core wire is 18mm (L, N and PE).
What are the required wire specifications for RS485 wiring on the FOXESS EPSBOX-SP?
The wire outer diameter is 3-6.5mm. The stripped length of the wire is 150mm, and the stripped length of the copper core is 10mm.
What are the pin definitions for the Meter 485 and CT interface of the KH / HI-G2 series on the FOXESS EPSBOX-SP?
For KH and H1-G2 series:
| PIN | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
|---|---|---|---|---|---|---|---|---|
| Definition | Meter485A | Meter485B | 485B | 485A | CT2+ | CT2- | CT1- | CT1+ |
| PIN | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 |
| Definition | / | K1 | K2 | K3 | K4 | / | DI | COM |
What are the pin definitions for the communication ports on the FOXESS EPSBOX-SP when using the EVO series?
For EVO series:
RJ45 Port (Pins 1-8):
| PIN | PIN Definition |
|---|---|
| 1 | Paralle_CANH |
| 2 | Paralle_CANL |
| 3 | Wifi_485A |
| 4 | Wifi_485B |
| 5 | Wifi_485A |
| 6 | DI |
| 7 | GND |
| 8 | 12V |
COM Port (Pins 1-24):
| PIN | PIN Definition | PIN | PIN Definition |
|---|---|---|---|
| 1 | DRM1/5 | 13 | CT2+ |
| 2 | DRM2/6 | 14 | CT2- |
| 3 | DRM3/7 | 15 | CT1- |
| 4 | DRM4/8 | 16 | CT1+ |
| 5 | DRM0 | 17 | K1 |
| 6 | RefGen | 18 | K2 |
| 7 | GND | 19 | K3 |
| 8 | Estop | 20 | K4 |
| 9 | Meter_485A | 21 | Termina_H |
| 10 | Meter_485B | 22 | Termina_L |
| 11 | 485B | 23 | BMS_CANH |
| 12 | 485A | 24 | BMS_CANL |
What steps are involved in the general electrical connection process for the FOXESS EPSBOX-SP?
Step 1: Open the box cover, remove the fixing screws of the insulation board, and then take out the insulation board.
Step 2: Pass cable through cable gland and wire according to the marks at the bottom of the box. After wiring all cables, restore the insulation board to its original position and then tighten the box cover.
What are the steps for wiring the INVERTER GRID & INVERTER EPS connections on the FOXESS EPSBOX-SP?
Step 1: The wire specification and crimping wire outer diameter is 14-22mm; the wire stripping length is 140mm; the stripping length of the copper-core wire is 14mm (L, N and PE).
Step 2: Pass cable through cable gland. Connect L, N and PE to the tubular terminal by crimping (only multi-core soft stranded wires must be crimped to tubular terminal; single core wires, thick stranded hard stranded wires, and tinned fine wire soft stranded wires may not be crimped).
Step 3: Connect the power lines L, N and PE: Insert them in the circuit breakers and PE connectors in sequence according to the marks on the bottom of the box, and then tighten the screws (M5, 3.5-5N M).
What is a note regarding PE connection for the EVO series EPS when wiring the FOXESS EPSBOX-SP?
The EVO series EPS does not have a PE wire, so its EPS can be used with a two-core cable.
What important notes should be considered when parallel-connecting energy storage inverters to the FOXESS EPSBOX-SP?
It is necessary that PE is connected to a functional ground, even if the grid connection is not active.
When parallel-connecting energy storage inverters, considering that the FOXESS EPSBOX-SP only accepts multi-core flexible stranded cables, all cable paralleling must be completed externally prior to entering the BOX. Ensure the sum of currents entering the BOX does not exceed 63A per phase. Exceeding this limit will trip circuit breakers, causing system failure. Additionally, configure inverters per their user manuals. Prior to installation, confirm the inverters support this functionality.
What are the required wire specifications and crimping details for UTILITY SUPPLY & LOAD wiring on the FOXESS EPSBOX-SP?
The wire specification and crimping wire outer diameter is 16-37mm; the wire stripping length is 140mm; the stripping length of the copper-core wire is 18mm (L, N and PE).
Pass cable through cable gland. Connect L, N and PE to the tubular terminal by crimping (only multi-core soft stranded wires must be crimped to tubular terminal; single core wires, thick stranded hard stranded wires, and tinned fine wire soft stranded wires may not be crimped).
Connect the power lines L, N and PE: Insert them in the circuit breakers and PE connectors in sequence according to the marks on the bottom of the box, and then tighten the screws.
How should the RS485 communication cable be prepared for wiring on the FOXESS EPSBOX-SP?
The wire outer diameter is 3-6.5mm, the stripped length of the wire is 150mm, and the stripped length of the copper core is 10mm.
Pass cable through cable gland and crimp the tubular terminal (only multi-core soft stranded wires must be crimped to tubular terminal, single core wires, thick stranded hard stranded wires, and tinned fine wire soft stranded wires may not be crimped).
Wiring: Insert into the quick-connect terminal.
What should be done if only one communication cable is required for the RS485 connection on the FOXESS EPSBOX-SP?
In the case that only one communication cable is required, the extra opening in the leftmost cable glands should be plugged up.
How should the meter’s RS485 port be connected if Inverter 2 requires an electric meter with the FOXESS EPSBOX-SP?
If Inverter 2 requires an electric meter, connect the meter’s RS485 port in parallel with Meter1’s RS485 port. Specifically, connect A to A and connect B to B. Additionally, set this meter’s communication address to 2.
What wiring instructions apply when using a CT with the FOXESS EPSBOX-SP?
When using a CT, its ratio must match the inverter’s preset ratio. For example, inverters of KH/HI-G2/EVO series require a 3000:1 CT ratio. And it must be connected to the CT2 terminal on the inverter. Verify correct CT orientation to prevent abnormal power generation.
What are the steps for making the Earth Connection on the FOXESS EPSBOX-SP?
Step 1: Trim 9mm of insulation from the wire end of a 10mm² wire.
Step 2: Insert striped wire into earth terminal and ensure all conductor strands are captured in the earth terminal. Crimp the earth terminal with crimping pliers. Put the earth terminal with striped wire into the corresponding crimping pliers and crimp the contact.
Step 3: Use the crimping pliers to press the grounding wire into the ground terminal, screw the ground screw with a screwdriver (M5, 2.0N M).
What checks need to be performed after installing the FOXESS EPSBOX-SP?
Check and confirm that the equipment is installed securely and reliably.
Check if the grounding wire is correctly, firmly and reliably connected.
Check if the wire is correctly, firmly and reliably connected (confirm if the phase sequence is correct).
Check if the communication wire is correctly, firmly and reliably connected.
What is the default state of the automatic transfer switch equipment on the FOXESS EPSBOX-SP?
The default state of the automatic transfer switch equipment is automatic mode. If you need to switch manually, please adjust the double power transfer switch to manual mode.
What precautions must be taken before product maintenance and testing for the FOXESS EPSBOX-SP?
Before product maintenance and testing, all external power sources must be cut off, and maintenance shall be operated by professional personnel. Do not modify the product during maintenance.
What are the environmental and installation precautions for mounting the FOXESS EPSBOX-SP?
Ensure that the installation site meets the following conditions:
- Not in direct sunlight.
- Not in areas where highly flammable materials are stored.
- Not in potential explosive areas.
- Not in the cool air directly.
- Not near the television antenna or antenna cable.
- Not higher than altitude of about 2000m above sea level.
- Not in environment of precipitation or humidity (> 95%).
- Under good ventilation condition.
- The ambient temperature in the range of -25°C to +60°C.
- The slope of the wall should be within +5°.
The wall hanging the FOXESS EPSBOX-SP should meet conditions below: A.Solid brick/concrete, or strength equivalent mounting surface; B.FOXESS EPSBOX-SP must be supported or strengthened if the wall is not firm enough (such as wooden wall, the wall covered by thick layer of decoration).
Please avoid direct sunlight, rain exposure, snow laying up during installation and operation.
What are the minimum distance requirements for space around the FOXESS EPSBOX-SP during mounting?
The minimum distances are:
| Position | Min Distance |
|---|---|
| Left | 200mm |
| Right | 200mm |
| Top | 300mm |
| Bottom | 500mm |
What are the tools required for installation of the FOXESS EPSBOX-SP?
Tools required for installation:
- Marker pen;
- Electric drill (drill bit set 8mm);
- Crimping pliers;
- Stripping pliers;
- Screwdriver.
What are the dimensions shown on the back of the FOXESS EPSBOX-SP for bracket fixing?
The dimensions (unit: mm) on the back of the machine are as follows: 288.8mm height for the mounting portion, 261.2mm height for the bracket mounting area, 420mm width, 430mm width for the bracket alignment, and hole distances of 270mm between centers and 26.5mm from the edge.
What is the required depth and width for drilling holes when mounting the FOXESS EPSBOX-SP bracket?
Drill holes with electric drill, make sure the holes are at least 50mm deep and 8mm wide, and then tighten the expansion tubes.
How is the bracket installed onto the wall using expansion screws for the FOXESS EPSBOX-SP?
Insert the expansion tubes into the holes and tighten them. Install the bracket with the expansion screws (M6, 2.2-2.7N M).
How is the FOXESS EPSBOX-SP fastened to the wall bracket?
Mount the FOXESS EPSBOX-SP to the bracket and fasten the BOX with two M5 bolts locking on both side (M5, 2.0N M).
What torque should be applied when removing/installing the insulation board fixing screws for the FOXESS EPSBOX-SP?
The fixing screws for the insulation board should be tightened with a torque of 1.5-1.8N M (M4).
What are the technical data specifications for the UTILITY SUPPLY interface of the FOXESS EPSBOX-SP?
For UTILITY SUPPLY on the FOXESS EPSBOX-SP:
- Rated voltage: 220/230/240VAC, L/N/PE
- Rated frequency: 50/60Hz
- Max. input current: 100A
What are the technical data specifications for the INVERTER GRID interface of the FOXESS EPSBOX-SP?
For INVERTER GRID on the FOXESS EPSBOX-SP:
- Rated voltage: 220/230/240VAC, L/N/PE
- Rated frequency: 50/60Hz
- Max. input current: 63A
What are the technical data specifications for the INVERTER EPS interface of the FOXESS EPSBOX-SP?
For INVERTER EPS on the FOXESS EPSBOX-SP:
- Rated voltage: 220/230/240VAC, L/N/PE
- Rated frequency: 50/60Hz
- Max. input current: 63A
What are the technical data specifications for the Load port of the FOXESS EPSBOX-SP?
For Load on the FOXESS EPSBOX-SP:
- Rated voltage: 220/230/240VAC, L/N/PE
- Rated frequency: 50/60Hz
- Max. output current: 100A
What are the technical data specifications for the INVERTER 2 interface of the FOXESS EPSBOX-SP?
For INVERTER 2 on the FOXESS EPSBOX-SP:
- Rated voltage: 220/230/240VAC, L/N/PE
- Rated frequency: 50/60Hz
- Max. input current: 63A
What is the Ingress Protection rating for the FOXESS EPSBOX-SP?
The Ingress Protection rating for the FOXESS EPSBOX-SP is IP65.
What operating temperature range is specified for the FOXESS EPSBOX-SP?
The operating temperature range for the FOXESS EPSBOX-SP is -25 … +60°C.
What derating is required for the FOXESS EPSBOX-SP when operating in off-grid mode at elevated temperatures?
In the off-grid mode, derating is required when the operating temperature exceeds 45°C. The specific derating for Max. Current (Load Current (A)) at different ambient temperatures is:
| Ambient Temperature (°C) | 45 | 50 | 55 | 60 |
|---|---|---|---|---|
| Max. Current (A) | 60 | 58 | 57 | 55 |
How do you operate the ATS Manual Mode on the FOXESS EPSBOX-SP?
Toggle the slide cover to the left until the arrow indicates that it is in the manual position, and pull out the handle and insert it into the conversion hole for conversion operation.
If you want to return to automatic mode, you must keep the arrow pointing to “manual” in manual mode, and then push the arrow to “automatic”.
The position of the arrow is the current working mode.
What should be done if the FOXESS EPSBOX-SP shows physical damage upon opening the package?
Ensure that the FOXESS EPSBOX-SP is intact during transportation. If there is any visible damage, such as cracks, please contact your dealer immediately.
What tubular ferrule models and quantities are included in the packing list for the FOXESS EPSBOX-SP?
The tubular ferrules provided are listed below with their corresponding quantities:
| Terminal model | RNY5.5-6 | RNY5.5-6-90D | E7510 | TF7510 | E6012 | E10-12 | E16-12 | E25-16 | E35-16 |
|---|---|---|---|---|---|---|---|---|---|
| Wire diameter (mm²) | 4-6 | 4-6 | 0.5-0.75 | 2×0.75 | 5-6 | 8-10 | 13-16 | 21-25 | 32-35 |
| Quantity | 1 | 2 | 6 | 2 | 11 | 9 | 15 | 6 | 6 |
What is the recommended torque when fixing the external power sources/lines on the FOXESS EPSBOX-SP circuit breakers?
When connecting power lines L, N and PE into the circuit breakers, the screws should be tightened to a torque of 3.5-5N M (M5).