Free English ELITECH EK-3030E (01) PDF Document. Free English ELITECH EK-3030E (01) PDF User Guide. Free English ELITECH EK-3030E (01) PDF User Manual. Free English ELITECH EK-3030E (01) PDF Owner Guide. Free English ELITECH EK-3030E (01) PDF Owner Manual. Free English ELITECH EK-3030E (01) PDF Reference Guide. Free English ELITECH EK-3030E (01) PDF Instruction Guide. Free English ELITECH EK-3030E (01) PDF Reference Manual. Free English ELITECH EK-3030E (01) PDF Instruction Manual. Free English ELITECH EK-3030E (01) PDF Operating Instructions.


CLICK HERE TO DOWNLOAD ELITECH EK-3030E (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.

NO IMAGE CONTENT AT THIS TIME. PLEASE CHECK BACK LATER

What are the technical specifications of the ELITECH EK-3030E?

The technical parameters for the ELITECH EK-3030E are as follows:

1) Measuring range: -40°C ~ 99°C

2) Controlling range: -40°C ~ 85°C

3) Accuracy: -30°C ~ 50°C, ±1°C ± 0.5dig; others, ±2°C ± 0.5dig

4) Resolution: 0.1°C

5) Mounting size: 71mm*29mm

6) Power supply: 220 ± 10%(VAC), 50/60Hz

7) Power consumption: <5W

8) Output capacity:

Refrigeration: 10A/220VAC or 16A/220VAC, directly drive a single phase compressor 1HP

Defrost: 10A/220VAC

Fan: 10A/220VAC

One-way buzzer alarm output

9) Work ambient temperature: -5°C ~ 60°C; work ambient humidity: 10% ~ 90% non condensing

10) Storage temperature: -25°C ~ 75°C

11) Sensor type: NTC (10KΩ/25°C, B value 3435K)

12) Sensor length: 2m


How do I understand the display panel and indicator lights on the ELITECH EK-3030E?

The display panel can display three digits, two status indicators (key lock and fan), and four parameter descriptors (temp on, temp off, def cycle, def time).

Under normal running states, all descriptors will not light; when in the menu-setting mode, the corresponding parameter descriptor lights. Under normal running status, if there is refrigeration/heating output, “On” descriptor lights; if defrost runs, “Def” descriptor lights.

Indicator light status description:

Indicator light Symbol Status Meaning
Key lock A key symbol OFF Unlocked status
ON Key lock status
Refrigeration/Heating output A snowflake symbol ON Output work
OFF Output stop
FLASH Output time delay
Defrost Def OFF Defrost stop
Flash(slowly) Defrost time delay
Flash(quickly) Defrost dripping
Fan A fan symbol ON Fan work
FLASH Fan time delay
OFF Fan stop

What are the functions of the keys on the ELITECH EK-3030E?

There are a total of six keys in the controller.

A snowflake with a water drop symbol Forced defrost key “Temp On”
An upward-pointing arrow UP key “Temp Off”
A downward-pointing arrow DOWN key OK/unlock key/OK

How do I lock and unlock the ELITECH EK-3030E controller?

Under the status of controller locking, press the OK key for one second, the controller will be unlocked, and at the same time, the buzzer beeps for about 30 seconds. If no key operation within 30 seconds, the controller will lock automatically.


How do I set the start and stop temperatures on the ELITECH EK-3030E?

Under the normal running status, press the OK key. The corresponding parameter descriptor lights, and it displays the value of “temp on” (or “temp off”) in the display window, which indicates that it has entered the setup menu of “temp on” (or “temp off”). The parameter could be adjusted by pressing the UP or DOWN keys. If the UP or DOWN key is kept pressed, the parameter could be adjusted quickly. In the setting mode, press and release the OK key, or no key operation within 30 seconds, it will exit from setting mode and save the parameters.

Parameter descriptor Description Setting range Default setting Work mode Note
Temp On Descriptor lights Start temperature Temp Off ~ +85.0°C 10.0°C Refrigeration If cabinet temperature is higher than set temperature, refrigeration starts.
-40.0°C ~ Temp Off -10.0°C Heating If cabinet temperature is lower than set temperature, heating starts.
Temp Off Descriptor lights Stop temperature -40.0°C ~ Temp On -10.0°C Refrigeration If cabinet temperature is lower than set temperature, refrigeration closes.
Temp On ~ +85.0°C 10.0°C Heating If cabinet temperature is higher than set temperature, heating closes.

How do I access and modify the system menu settings on the ELITECH EK-3030E?

Under the normal running temperature display window, press the OK key for more than 5 seconds, and it will display parameter code “F1” in the temperature display window, which indicates that it has entered the system setup menu. The parameter codes could be switched by pressing the UP or DOWN keys, and press and release the OK key to display the corresponding parameter values.

The parameters could be adjusted by pressing the UP or DOWN keys, and if the UP or DOWN key is kept pressed, the parameters could be adjusted quickly. Press and release the OK key to save the modified parameter value and return to display parameter code.

In System menu setting status, press the OK key for 5 seconds or no key operation within 30 seconds, it will save the parameters and exit from system menu setting status.

If an error occurs when you save the parameters, it shows “Err” in the temperature display window, and it returns to the normal display status in 5 seconds.


What are the main parameters (F1-F12) for the ELITECH EK-3030E?

Parameters Description Setting range Default value Note
F1 Defrost time 1 – 120 Min 30 Min Duration time during defrost
F2 Defrost cycle 0 – 120 Hour 6 Hour The interval during two defrosts (Auto record every one hour)
F3 Defrost cycle calculation 0: Cumulative controller work time after power on
1: Cumulative compressor work time after power on
2: Controlled by external defrost timer
1 If 2 is selected, defrost is started by external defrost timer; that is, Either H15 or H16 needs to be set as 6. If not, defrost function is canceled.
F4 Dripping time after defrost 0 – 120min 3min Time delay after finishing defrost
F5 Defrost type 0: Electric heating defrost
1: Hot gas defrost
2: wind defrost
0 Before hot gas defrost, the compressor stops for 3 minutes then starts defrost, to make sure the reliability of the system. After hot gas defrost, compressor starts after 2 minutes time delay.
F6 Defrost termination temperature -40.0°C ~ 50.0°C 10°C If defrost sensor temperature is high than the set value, defrost stops and defrost is forbidden.
F7 Fan running mode -180 ~ -1: Fan starts ahead of compressor 180 ~ 1s(second)
0: Fan and compressor run synchronically
c: Fan runs continuously (no time delay after dripping)
d: Fan runs continuously, stops during defrost and dripping
1 ~ 300: Fan starts behind compressor 1 ~ 300 (seconds)
0
F8 Initial fan start time delay after dripping 0 ~ 300S 30S Initial fan start time delay after dripping
F9 Compressor start time delay 0 ~ 10Min 0 Compress start minimum time interval from its last stop (include the compressor start time delay for the initial power on).
F10 Over temperature alarm time delay after power on 0 ~ 24 Hour 2 Hour After power on, during this time range, there is no over temperature alarm signal.
F11 Over temperature alarm 0 ~ 50.0°C 5.0°C Refrigeration mode:
If cabinet temperature is higher than “Temp On value + Over temperature alarm value” or lower than “Temp Off value – over temperature alarm value”, it alarms.
Heating mode:
If cabinet temperature is higher than “Temp Off value + Over temperature alarm value” or lower than “Temp On value – over temperature alarm value”, it alarms.
F12 Over temperature alarm time delay 0 ~ 120Min 10Min Alarm won’t occur until over temperature duration is longer than this parameter.

What are the hidden parameters (H15-A8) for the ELITECH EK-3030E and how do I access them?

To access the hidden parameter list, in System menu setting status, press and hold the UP key and DOWN key for more than 5 seconds, it will blinkingly display password setting. The hidden menu is unavailable for access until a correct password is set. The password fixed value is “-15”. Under System menu, press the OK key for 3 seconds, or no key operation within 30 seconds, it will exit from system setting menu.

Parameters Description Setting range Default value Note
H15 Digital input 1 definition ± 6:start defrost
± 5:heating mode
± 4:Normal external alarm
± 3: Emergency external alarm
± 2: Pressure switch alarm
± 1:Door switch alarm
0:Forbidden
Positive number represents default normally open, close valid; Negative number represents default normally closed, open valid.
0
H16 Digital input 2 definition 0
A1 Normal external alarm time delay 0~240s 60s
A2 Compressor/defrost/fan stop or not during normal alarm 0: no effect;
1: only compressor stops;
2: Compressor, defroster and fan all stop
0
A3 Emergency external alarm time delay 0~240s 0
A4 Compressor/defrost/fan stop or not during Emergency alarm 0: no effect;
1: only compressor stops;
2: Compressor, defroster and fan all stop
0
A5 Door switch alarm delay 0~240s 60s
A6 Compressor and fan status during door open 0:no effect
1:Close fan
2:Close compressor
3:Close both fan and compressor
3
A7 Fan stop time during door open ON: Non-stop;
OFF: Not start before door closed;
1~240s: (stop time);
40s If A6=0 or 2, this parameter is invalid.
A8 Pressure switch auto reset permission 0: Auto reset is forbidden;
1~5: Auto reset times
2 When the parameter is not 0, if pressure switch auto reset times exceeds the set times, then auto reset is not allowed. Power on the controller again, auto reset times will be recalculated.

How do I perform a manual defrost on the ELITECH EK-3030E?

In the status of non-defrosting, non-defrost-dripping, non-parameter setting, and defrost cycle is not set to 0 and the defrost sensor temperature is less than the set defrost termination temperature (F6), press the defrost key for more than three seconds, it enters to manual defrost status, and the defrost working indicator lights and start defrosting.

In the defrost status (non-parameter setting status), press the defrost key for more than three seconds, it exits from defrost status, and the defrost working indicator flashes, defrost stops and start defrost dripping.


How can I view the defrost sensor temperature on the ELITECH EK-3030E?

Under the normal running status or lock status, press the DOWN key, it displays defrost sensor temperature in the temperature display window. Release the key, it returns to the normal display status.


How do I mute the buzzer alarm on the ELITECH EK-3030E?

Press any key to eliminate the alarm buzzer beeping, but the alarm indicator light will not be off until the alarm is released.


How do I perform a factory reset on the ELITECH EK-3030E?

In the key lock status, press the UP key and DOWN key for more than 10 seconds, it displays “CON” for 3 seconds, within these three seconds, press the OK key to confirm the current parameter setting as the factory preset data, and it displays “YES”, so that end-users could recover the controller parameters to the appropriate setting in case of emergency.

In the key lock status, press the UP key and DOWN key for more than 10 seconds, it displays “DON” for 3 seconds, within these three seconds, press the OK key to recover to the factory preset parameter setting and it displays “YES”.

Note: Before recovering to factory preset parameter setting, to make sure that the parameters have previously backed up. Otherwise, it will recover to the factory default parameters.


How does the control output logic work on the ELITECH EK-3030E?

1) Refrigeration control

Compressor startup condition (meet all the condition as below):

Compressor stop time exceeds the set compressor time delay;

Fan starts ahead of compressor (Fan starts ahead of compressor is set as minus);

The status of non-defrosting, non-defrost-dripping; when cabinet temperature ≥ set “Temp On” value or during hot gas defrost.

Compressor stop condition (meet any of the conditions as below):

When cabinet temperature ≤ set “Temp Off” value;

When start electric-heating defrost;

When hot gas defrost stops;

2) Defrost control

Defrost startup condition (meet all the condition as below):

Defrost cycle is not set as 0;

Defrost sensor temperature is lower than the set defrost termination temperature;

Finish the set “defrost cycle” or forced defrost starts.

Defrost close condition: It is controlled by both temperature and time. After start defrosting, if defrost sensor temperature reaches “defrost termination temperature”, then defrost finishes and stop defrost. If defrost time is too long and exceeds “defrost time”, the controller will also stop defrost. If neither temperature nor time reaches the set value, it could exit from defrost status through manually pressing the key of “forced defrost”.

Defrost dripping time: The purpose of defrost dripping is to discharge the water accumulated during defrost in the evaporator. If the water could not be discharged timely, the water will be frozen again during refrigeration. Therefore, it is necessary to set a defrost dripping time to make sure a timely water discharge during defrost. During this period, the compressor does not start, and “defrost” working status indicator flashes at this time.

3) Fan control

Fan is controlled by compressor time:

-180 ~ -1: Fan starts ahead of compressor 180 – 1S

0: Fan and compressor run synchronically

c: Fan runs continuously

d: Fan runs continuously, stops during defrost and dripping

1 ~ 300: Fan starts behind compressor 1 ~ 300S


What do the alarm outputs and error codes on the ELITECH EK-3030E mean?

The controller has one way buzzer alarm output. In the running status, when the following conditions occur, the buzzer beeps:

When the cabinet sensor fails, it displays the fault code E1 in the temperature display window; the controller will run in the fixed pattern, the compressor stops for 30 minutes, then run for 15 minutes. After cabinet sensor failure is released, it refers to the normal temperature control mode and exits from the fixed compressor start/stop mode.

When defrost sensor fails, it alternately displays the fault code E2 and the current cabinet temperature in the temperature display window; the controller controls according to the set defrost cycle and defrost time. When the defrost sensor failure is released, it refers to the dual-control mode by both time and temperature.

If the cabinet sensor and defrost sensor fail simultaneously, it alternately displays the fault code E1 and E2 in the temperature display window.

When cabinet temperature ≥ “Temp On value” + “over temperature alarm value” and the duration ≥ “temperature alarm time delay” after power on, a high temperature alarm occurs. It alternately displays the current cabinet temperature and the fault code HA in the temperature display window. When cabinet temperature < "Temp On value" + "over temperature alarm value" - "temperature alarm return", it is canceled.

When cabinet temperature ≤ “Temp Off value” – “over temperature alarm value” and the duration ≥ “temperature alarm time delay”, a low temperature alarm occurs. It alternately displays the current cabinet temperature and the fault code LA in the temperature display window. When cabinet temperature > “Temp Off value” – “over temperature alarm value” + “low temperature alarm return”, it is canceled.


How do the digital switch inputs work on the ELITECH EK-3030E?

Two way digital switch input could be set in different function through parameters “H15” and “H16”.

Start defrost: When F3=2 (controlled by external defrost timer) and digital input valid, and meet the conditions of defrost, start defrosting.

Heating mode: When digital input is valid, it switches to heating mode; when digital input is invalid, it recovers to refrigeration mode.

Normal external alarm: When the digital input is valid, after finish the time delay of parameter A1, if the digital input is still valid, it displays the alarm information EA, and all relay output status is determined by parameter A2. If the digital input is invalid, alarm will stop immediately.

Emergency external alarm: When the digital input is valid, after finish the time delay of parameter A3, if the digital input is still valid, it displays the alarm information CA, and all relay output status is determined by parameter A4. If the digital input is invalid, alarm will stop immediately.

Pressure switch alarm: When the digital input is valid, it displays alarm information CA, all replay output are close. When digital input is invalid, it will automatically reset according to parameter A8 and A9.

Door switch alarm: When the digital input is valid, after finish the time delay of parameter A5, if the digital input is still valid, it displays the alarm information “dor”, and compressor and fan output status are determined by parameter A6 and A7. If the digital input is invalid, alarm will stop immediately.


How should I wire the ELITECH EK-3030E controller?

Based on the wiring diagram, connect the terminals as follows:

Terminals 1 & 2 (Power 220V): Connect the Live (L) and Neutral (N) wires of the 220V power supply here.

Terminal 3 (Compressor): This is the output for the compressor.

Terminal 4 (Defrost): This is the output for the defrost heater.

Terminal 5 (Fan): This is the output for the fan.

Terminal 6 (Common): This is a common terminal for the compressor, defrost, and fan relays.

Terminals 7 & 8 (Cabinet sensor): Connect the cabinet temperature sensor to these two terminals.

Terminals 8 & 9 (Defrost sensor): Connect the defrost (evaporator) temperature sensor to these two terminals. Note that terminal 8 is common for both sensors.

Terminals 10 (GND), 11 (DIG2), 12 (DIG1): These are for the digital inputs. Connect your digital switches (like door switch, pressure switch) between GND and DIG1 or DIG2.

UART Port: There is a 4-pin UART port for communication (S, +5V, RXD, TXD, GND). This is used for connecting to a communication adapter.


What are the safety rules for installing and using the ELITECH EK-3030E?

Danger:

1. Strictly distinguish the power wire, relay output, sensor down-lead and data line, and the relay could not be overloaded.

2. Prohibit connecting the wire terminals without electricity cut-off.

Warning:

Prohibit using this unit under the environment of over damp, high temp., strong electromagnetism interference or strong corrosion.

Notice:

1. The power supply should conform to the voltage value indicated in the instruction, and make sure a steady power supply.

2. To avoid the possible interference, the sensor down-lead/data line and power wire should be kept in a proper distance.

3. When evaporator sensor is installed, the sensor should be well connected with the copper tube which is 5cm away from evaporator inlet.