FREE ENGLISH CARLO GAVAZZI SHJWEM16A115 (01) PDF USER GUIDE
FREE ENGLISH CARLO GAVAZZI SHJWEM16A115 (01) PDF USER MANUAL
FREE ENGLISH CARLO GAVAZZI SHJWEM16A115 (01) PDF OWNER GUIDE
FREE ENGLISH CARLO GAVAZZI SHJWEM16A115 (01) PDF OWNER MANUAL
FREE ENGLISH CARLO GAVAZZI SHJWEM16A115 (01) PDF REFERENCE GUIDE
FREE ENGLISH CARLO GAVAZZI SHJWEM16A115 (01) PDF INSTRUCTION GUIDE
FREE ENGLISH CARLO GAVAZZI SHJWEM16A115 (01) PDF REFERENCE MANUAL
FREE ENGLISH CARLO GAVAZZI SHJWEM16A115 (01) PDF INSTRUCTION MANUAL
FREE ENGLISH CARLO GAVAZZI SHJWEM16A115 (01) PDF OPERATING INSTRUCTIONS
CLICK HERE TO DOWNLOAD CARLO GAVAZZI SHJWEM16A115 (01) PDF MANUAL
If this is not the document you want for this product, click here to see if we have any other documents for this product.
How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.
What are the safety and maintenance instructions for the instrument?
Read carefully the instruction manual. If the instrument is used in a manner not specified by the producer, the protection provided by the instrument may be impaired.
Maintenance: make sure that the connections are correctly carried out in order to avoid any malfunctioning or damage to the instrument. To keep the instrument clean, use a slightly damp cloth; do not use any abrasives or solvents. We recommend to disconnect the instrument before cleaning it.
What are the supply specifications for the SHJWEM16AXXX?
Power supply Overvoltage cat. II.
Rated operational voltage: SHJWEM16A230 240 VAC; SHJWEM16A115 115 VAC.
Rated impulse voltage: 2.5 kV.
Rated operational power: 1 W, 2.5 VA.
What are the general specifications of the SHJWEM16AXXX?
Address assignment: Automatic: the controller recognises the module through the SIN (Specific Identification Number) that has to be filled in the Sx tool.
Degree of protection: IP 20.
Pollution degree: 3.
Operating temperature: -20° to +50°C (-4° to 122°F).
Storage temperature: -50° to +85°C (-58° to 185°F).
Humidity (non-condensing): 20 to 90% RH.
What are the WiDup specifications?
Bus: Wireless dupline®.
Frequency: IEEE 802.15.4, @ 2.4 Ghz.
Diagnostics: 1. Field strength; 2. Network activites; 3. Devices’ presence.
Network topology: Star with max one wireless repeater.
Antenna: Internal.
Transmission power: According to IEEE 802.15.4.
Sensitivity: According to IEEE 802.15.4.
Number of slave nodes: Up to 250.
Transmission range: <700 m in the open air.
What are the rated electrical values the device can read out?
The rated values are:
A: 0 to 16000 mA
V: 99 to 132.0 V (SHJWEM16A115);
V: 198 to 264.0 V (SHJWEM16A230)
W: 3.0 to 4500.0 W
kWh: 0.1 to 99999999.9 kWh with roll over
Wdmd: 0.1 to 4500.0 W
VA: 0.1 to 4500.0 Va
var: 0.1 to 4500.0 var
PF: -0.999 … to … 1.000 PF
What do the LED indicators on the SHJWEM16AXXX mean?
Green LED: Power status.
ON: Supply ON.
OFF: Supply OFF.
Blu LED: WiDup.
Short blink: Sending data when associated to a SH2WBU230x.
Long blink: Sending data when not associated to any SH2WBU230x or when receiving a network configuration.
On: During network configuration when configured as a router.
What factors influence the transmission range of the SHJWEM16Axxx?
The main factors that influence the transmission range are the antenna location of the receivers and transmitters, the building structure and the number of obstacles in the connection path.
Other factors are noise sources (wi-fi routers, micro oven, blue tooth devices,…) that affect the receiver and dead spots caused by signal reflection from nearby conductive objects.
Since the anticipated transmission range depends on these system conditions, range tests should be performed before a specific range is determined for an application.
What are the general guidelines for the transmission range?
| Device position | Operating distance |
|---|---|
| In the open air | Approx. 700 m |
| Plaster-board/wood | Approx. 30 m Max. 5 walls |
| Tile and cellular concrete | Approx. 20 m Max. 3 walls |
| Reinforced concrete walls/ceilings | Approx. 10 m Max. 1 ceiling/wall |
What can limit the transmission range?
The transmission range is limited by:
• insulation material with metal foil
• intermediate ceilings with metal or carbon fibre panels
• lead glass or metal-coated glass
• mounting wall transmitters on metal walls