FREE ENGLISH AIRWELL VVFA-335R-01T32 (01) PDF USER GUIDE
FREE ENGLISH AIRWELL VVFA-335R-01T32 (01) PDF USER MANUAL
FREE ENGLISH AIRWELL VVFA-335R-01T32 (01) PDF OWNER GUIDE
FREE ENGLISH AIRWELL VVFA-335R-01T32 (01) PDF OWNER MANUAL
FREE ENGLISH AIRWELL VVFA-335R-01T32 (01) PDF REFERENCE GUIDE
FREE ENGLISH AIRWELL VVFA-335R-01T32 (01) PDF INSTRUCTION GUIDE
FREE ENGLISH AIRWELL VVFA-335R-01T32 (01) PDF REFERENCE MANUAL
FREE ENGLISH AIRWELL VVFA-335R-01T32 (01) PDF INSTRUCTION MANUAL
FREE ENGLISH AIRWELL VVFA-335R-01T32 (01) PDF OPERATING INSTRUCTIONS


CLICK HERE TO DOWNLOAD AIRWELL VVFA-335R-01T32 (01) PDF MANUAL

If this is not the document you want for this product, click here to see if we have any other documents for this product.

What are the key features of the Airwell Flow Logic(MINI) VVFA unit?

Key features include:

Energy Efficiency Upgrades:

• Full DC fan motor with zigzag design for reduced airflow disturbance, less vibration, and pressure loss.

• Super big diameter fan (550mm) to enhance heat exchange efficiency.

• Changed exchanger pipe diameter (from Φ8 to Φ7) with high-efficiency corrugated fins, increasing heat exchanger area and improving efficiency by 30%.

• Special structure for increased wind-cooled PCB effect.

• PID control for precise management of EEV opening degree, compressor rotation speed, and fan speed.

• Tube-in-tube type two-stage sub-cooling design to enhance efficiency (on double fan models).

• Larger capacity full DC inverter compressor.

• Double rotor compressor with keel motor technology, increasing efficiency by 10% compared to normal types.

Control Technology:

• Double pressure sensor with PID control: Adjusts target evaporation/condensation temperature to increase compressor frequency quickly.

• Intelligent defrosting technology: Judges frosting degree based on low pressure and defrost temperature sensor changes, entering defrost only when necessary to extend heating time.

Cleaning Technology:

• Inverse balancing technology: Indoor & outdoor unit self-cleaning module uses waste heat for heating, defrosting, and sterilizing the indoor unit without stopping.

• Quick setting and cleaning technology: Uses accurate temperature control for rapid frost and instant frost effects.

Installation Flexibility:

• Easy Installation: 4-way pipe connection (front, back, left, right).

• Long Piping: Total pipe length up to 300m.

• High Drop: Maximum drop between indoor and outdoor units up to 50m (or 40m depending on model/configuration, refer to specs).

• Versatile Environment: Suitable for various installation environments (double fan models).


What are the nominal operating conditions for testing?

Nominal conditions are:

• Indoor temperature (cooling): 27 DB(°C)/19 WB(°C)

• Indoor temperature (heating): 20 DB(°C)/14.5 WB(°C)

• Outdoor temperature (cooling): 35 DB(°C)/24 WB(°C)

• Outdoor temperature (heating): 7 DB(°C)/6 WB(°C)

• Data is measured with 7.5m equivalent pipe and 0m height difference.

• Noise level is measured in the third octave band limited values in the semi-anechoic chamber, using a real time analyser calibrated sound intensity meter (sound pressure noise level).


What are the functions of the main components listed in the manual?

Part name Sign Function Data Note
Compressor / Capacity control, meet indoor load request by adjusting frequency and opening and closing fixing frequency compressor. 20°C
Pressure switch HPS High pressure protection 4.15Mpa, OFF
LPS In cooling, compressor frequency adjustment and protection control for abnormal pressure. 0~1.7MPa
Electronic expansion valve EEV In heating, refrigerant flow control (subcooling valve) Φ3.0
Solenoid valve SV1 1. Keep balance of high/low pressure when compressor starts up and stops
2. High/low pressure protection
AC220V Open when power is on, close when power is off. 2A
4-way valve 4WV Changing over between cooling and heating AC220V electrified in heating; powered off in cooling or defrosting.
Temp. sensor Td Detect the top temp. of compressor R(80°C)=50K B(25/80°C)=4450K
Ts Detect the top suction of compressor
Tao Detect ambient temp., set primary fan speed and control defrost condition R(80°C)=10K B(25/80°C)=3700K
Tdef Detect frost condition of outdoor heat exchanger

What is the function of the BM1 dial switch?

The switch BM1-1 is used for locking the indoor units number.

The initial status is “OFF”. After power on, the display board will show “***” which indicates the number of Indoor units that the outdoor unit can communicate with.

If it matches the actual number of indoor units, change the setting from “OFF” to “ON”. If it does not match, solve the communication problem first before changing the switch.

The other BM1 switches (BM1-2 to BM1-8) relate to model settings and require setup on site according to the table provided in the manual.

Dial Switch Introduction

Dial switch [1] [2] [3] [4] [5] [6] [7] [8] MODEL Notes
BM1 0 0 1 1 08 0 is OFF
1 is ON
requires set up on site
0 1 0 1 0 0 0 10
0 1 1 1 12

What do the symbols on the wiring diagram mean?

SYMBOL SIGNIFICATION SYMBOL SIGNIFICATION
R/S/T Power line PD High pressure sensor
N Neutral line PS Low pressure sensor
L1/L2/L3 Power supply TD Comp. vent sensor
U/V/W COMP. power line TE(1) Defrost temp. sensor
HEATER1/2 COMP. heater TS Comp. inhale sensor
4WV 4 way valve TA Ambient temp. sensor
DCFAN1/2 DC fan motor SV1 Unload valve
SW4-7 Button SV2 Spray valve
BM1 Dial switch R Red
CT Current test B Black
HPS High pressure switch W White
LEVA1 Elec-expansion valve BL Blue
CN31 Modbus Y Yellow
Y/G Yellow/Green
G Green

How is the cooling capacity calculated?

The cooling capacity to be known is calculated using the following formula:

Cooling capacity = Nominal cooling capacity * A * B * C * D * E

Where:

A = Capacity compensation value based on indoor air wet-bulb temperature condition.

B = Capacity compensation value based on outdoor air dry-bulb temperature condition.

C = Capacity modification value under airflow variation rate of indoor unit group (only for duct units).

D = Capacity compensation suitable for total capability of indoor unit group (%).

E = Capacity compensation value based on pipe length, pipe diameter, and height drop.

Refer to the performance curves in the manual for the specific values of A, B, C, D, and E based on your operating conditions and installation specifics.

Note: The main pipe diameter should be enlarged one size if the single way pipe length is over 90m. Compensation factors should be adjusted for vertical height drops based on the provided table if outdoor is lower than indoor in cooling mode.

Adjustment Factor for Vertical Height Drop (Cooling Mode – Outdoor Lower than Indoor)

Vertical height drop 5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
Adjustment factor (subtract from E) 0.003 0.006 0.009 0.012 0.015 0.018 0.021 0.024 0.027 0.030

How is the heating capacity calculated?

The heating capacity to be known is calculated using the following formula:

Heating capacity = Nominal heating capacity * A * B * C * D * E * F

Where:

A = Capacity compensation value based on indoor air dry-bulb temperature condition.

B = Capacity compensation value based on outdoor air wet-bulb temperature condition.

C = Capacity modification value under airflow variation rate of indoor unit group (only for duct units).

D = Capacity compensation suitable for total capability of indoor unit group (%).

E = Capacity compensation value based on pipe length, pipe diameter, and height drop.

F = Capacity compensation value for defrost capability of outdoor heat exchanger.

Refer to the performance curves in the manual for the specific values of A, B, C, D, E, and F based on your operating conditions and installation specifics.

Note: The main pipe diameter should be enlarged one size if the single way pipe length is over 90m. Compensation factors should be adjusted for vertical height drops based on the provided table if outdoor is higher than indoor in heating mode.

Adjustment Factor for Vertical Height Drop (Heating Mode – Outdoor Higher than Indoor)

Vertical height drop 5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
Adjustment factor (subtract from E) 0.003 0.006 0.009 0.012 0.015 0.018 0.021 0.024 0.027 0.030

What are the correction factors for pipe length and drop?

Correction factors adjust the rated capacity based on the single pipe length from the farthest outdoor unit to the farthest indoor unit and the vertical height difference (drop) between them. Separate tables are provided for cooling and heating modes.

Cooling Correction Factor Table:

Drop (m) 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 175
50.0 0 0 0 0 0 0 0.902 0.881 0.86 0.838 0.815 0.792 0.77 0.748 0.726 0.719 0.698 0.669 0.650
40.0 0 0 0 0 0.93 0.902 0.881 0.86 0.838 0.815 0.792 0.77 0.748 0.726 0.719 0.698 0.669 0.650
30.0 0 0 0 0.95 0.93 0.902 0.881 0.86 0.838 0.815 0.792 0.77 0.748 0.726 0.719 0.698 0.669 0.650
20.0 0 0 0.97 0.95 0.93 0.902 0.881 0.86 0.838 0.815 0.792 0.77 0.748 0.726 0.719 0.698 0.669 0.650
10.0 0 0.99 0.97 0.95 0.93 0.902 0.881 0.86 0.838 0.815 0.792 0.77 0.748 0.726 0.719 0.698 0.669 0.650
0.0 1 0.99 0.97 0.95 0.93 0.902 0.881 0.86 0.838 0.815 0.792 0.77 0.748 0.726 0.704 0.682 0.660 0.650
-10.0 0 0.982 0.965 0.942 0.921 0.898 0.875 0.852 0.832 0.81 0.788 0.768 0.748 0.728 0.703 0.678 0.652 0.638
-20.0 0 0 0.96 0.938 0.915 0.892 0.871 0.85 0.828 0.806 0.782 0.76 0.738 0.716 0.701 0.675 0.644 0.625
-30.0 0 0 0 0.931 0.907 0.887 0.866 0.844 0.823 0.801 0.777 0.756 0.735 0.713 0.700 0.671 0.635 0.613
-40.0 0 0 0 0 0.900 0.882 0.861 0.839 0.818 0.797 0.772 0.751 0.730 0.708 0.698 0.668 0.627 0.600

Heating Correction Factor Table:

Drop (m) 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 175
50.0 0 0 0 0 0 0.900 0.883 0.867 0.846 0.824 0.803 0.782 0.761 0.740 0.718 0.696 0.673 0.651
40.0 0 0 0 0 0.914 0.906 0.890 0.873 0.853 0.833 0.813 0.792 0.772 0.752 0.733 0.712 0.690 0.669
30.0 0 0 0 0.929 0.921 0.911 0.896 0.880 0.861 0.841 0.822 0.803 0.783 0.764 0.748 0.728 0.706 0.687
20.0 0 0 0.943 0.938 0.929 0.917 0.902 0.887 0.868 0.850 0.831 0.813 0.794 0.776 0.764 0.745 0.722 0.704
10.0 0 0.957 0.957 0.948 0.936 0.923 0.908 0.893 0.876 0.858 0.841 0.823 0.806 0.788 0.779 0.761 0.739 0.722
0.0 1 0.986 0.971 0.957 0.943 0.929 0.914 0.900 0.883 0.867 0.850 0.833 0.817 0.800 0.794 0.778 0.755 0.740
-10.0 0 0.986 0.971 0.957 0.943 0.929 0.914 0.900 0.883 0.867 0.850 0.833 0.817 0.800 0.794 0.778 0.755 0.740
-20.0 0 0 0.971 0.957 0.943 0.929 0.914 0.900 0.883 0.867 0.850 0.833 0.817 0.800 0.794 0.778 0.755 0.740
-30.0 0 0 0 0.957 0.943 0.929 0.914 0.900 0.883 0.867 0.850 0.833 0.817 0.800 0.794 0.778 0.755 0.740
-40.0 0 0 0 0 0.943 0.929 0.914 0.900 0.883 0.867 0.850 0.833 0.817 0.800 0.794 0.778 0.755 0.740

What is the operating range for temperature?

The unit should be operated within the following temperature ranges:

Cooling Mode:

• Outdoor Temperature (Dry Bulb): -5°C to 48°C

• Indoor Temperature (Wet Bulb): 15°C to 30°C (Continuous operation range)

Heating Mode:

• Outdoor Temperature (Wet Bulb): -20°C to 27°C

• Indoor Temperature (Dry Bulb): 10°C to 30°C (Continuous operation range)

Operating the unit outside these ranges may trigger protection devices.


What important safety precautions should be followed during installation and operation?

WARNINGS (Risk of serious injury or death):

• Installation or maintenance must be performed by an authorized agency. Non-specialized operation can cause water leakage, electric shock, or fire.

• Follow the manual strictly during installation to prevent water leakage, electric shock, or fire.

• Install the unit on a structure capable of bearing its weight to prevent it from falling and causing injury.

• Ensure installation defends against typhoons, earthquakes, etc., as abnormal installation can cause the unit to fall.

• Use the correct specified cables and ensure reliable earthing. Secure terminals firmly; loose connections cause overheating and fire.

• Ensure wiring is properly arranged and not raised or pinched by covers. Incorrect installation can cause heating and fire.

• Do not introduce air or any gas other than R410A into the refrigerant system. Gas mixtures cause abnormally high pressure, leading to rupture or injury.

• Use only specified accessories or parts during installation to prevent water leakage, electric shock, fire, or refrigerant leaks.

• Do not drain water into drainage grooves containing poisonous gases (like sulphur) as the gas can enter the indoor space.

• If refrigerant leakage occurs during or after installation, ventilate the area immediately. Refrigerant can produce poisonous gas upon contact with fire.

• Do not install the unit where flammable gas leakage might occur. Leaked gas accumulating around the unit can cause a fire.

• Install the drainage pipe according to the manual for fluent drainage and provide heat insulation to prevent dew condensation. Improper installation causes water leakage and property damage.

• If the supply cord is damaged, it must be replaced by the manufacturer, service agent, or similarly qualified persons.

• This appliance is not for use by persons with reduced capabilities unless supervised.

• Children aged 8+ and persons with reduced capabilities can use the appliance if supervised/instructed on safe use and hazards.

• Children shall not play with the appliance. Cleaning/maintenance shall not be done by unsupervised children.

• Do not operate via external timers or separate remote controls.

• Keep the appliance and cord away from children under 8 years.

• If transferring the unit, transfer this manual with it.

• Electrify the unit for over 12 hours before startup to protect the compressor. If unused for a long time, cut power.

CAUTIONS (Risk of injury or property damage):

• Earth the unit correctly. Do not connect the earth wire to gas pipes, water pipes, lightning rods, or telephone earth wires. Improper earthing causes electric shock.

• Do not install where flammable gas leaks might occur, to prevent fire.

• Install the water drainage pipe correctly to prevent water leakage and damage.

• Ensure the outdoor fan discharge does not directly blow on plants or flowers.

• Ensure sufficient maintenance space is available.

• When installing on a roof or high place, provide fixed ladders and railings for safety.

• Use two spanners to tighten flare nuts to the correct torque. Over-tightening can break the flare section, causing refrigerant leakage and potential oxygen deficiency.

• Insulate refrigerant pipes to prevent condensation and water damage.

• After piping work, perform a leakage test using nitrogen. Refrigerant leaks in small rooms exceeding concentration limits can cause oxygen deficiency.

• Use only R410A refrigerant. Do not mix refrigerants. R410A pressure is ~1.6 times higher than R22.

• Use R410A specific tools (manifold, hose, flare tool, torque spanner, vacuum pump adapter, leak detector). Charge refrigerant in liquid state from the tank.

• Provide heat insulation for both liquid and gas pipes to prevent condensation.


What tools are specified for working with R-410A refrigerant?

R-410A specified tools Remarks
1 Gauge manifold Range: HP > 4.5MPa, LP > 2MPa
2 Charge hose Pressure: HP: 5.3MPa, LP: 3.5MPa
3 Electronic balance for charging R410A Cannot use the measurable charging tank
4 Torque spanner
5 Flare tool
6 Copper pipe gauge for adjusting projecting margin
7 Vacuum pump adapter Must be with reverse stop valve
8 Leakage detector Cannot use freon leakage detector, but the He detector

Note: When charging refrigerant, it must be taken out as liquid state from the tank.


What checks should be performed before installation?

1. Confirm if the model, power supply, pipe, wires, and parts purchased are correct.

2. Check if the indoor and outdoor units can be combined based on the following compatibility:

Outdoor Model Indoor Qty Total indoor capacity (X 100W)
VVFA-220R-01T32 13 113~293
VVFA-280R-01T32 16 140~364
VVFA-335R-01T32 19 158~410

Additionally, verify:

• If the connected units quantity and the total capacity are within the allowable range.

• If the refrigerant pipe length is within the limited range.

• If the pipe size is proper and installed horizontally (where required).

• If the branch pipe is installed correctly (horizontally or vertically).

• If the additional refrigerant is counted correctly and weighed.

• If there is any refrigerant leakage.

• If all indoor power supplies can be switched on/off simultaneously.

• If the power voltage complies with the rating label.

• If the addresses of indoors have been set.


Where should the outdoor unit be installed?

General Location Requirements:

• Place in a well-ventilated and dry location.

• Ensure noise and exhaust do not affect neighbors and ventilation is unobstructed.

• Ground must be steady, reliable, and strong enough to support the unit’s weight to prevent vibration and noise.

• Allow sufficient space for handling and maintenance as shown in the diagrams.

• Install in a publicly unapproachable place.

Locations to Avoid:

• Places with inflammable gas (risk of fire).

• Places with high oil content, salt spray, or harmful gases (e.g., spa areas, seaside).

• Areas subject to strong coal smoke.

• Places with high humidity.

• Locations near devices emitting Hertzian waves (keep at least 3 meters away from electromagnetic radiation sources).

• Dusty or polluted places that could jam the heat exchanger.

• Areas where voltage changes greatly.

• Where cold/hot air or noise will interfere with neighbors.

• Where other heat sources will affect the unit.

Additional Considerations:

• Ensure water can drain fluently.

• In snowy areas, provide protection (e.g., snow cover) to prevent clogging.

• Install anti-vibration rubber between the unit and bracket/foundation.

• Install in the shade, avoiding direct sunlight or high-temperature heat sources.

• Refer to diagrams for specific minimum clearance distances based on single/multi-unit installations and surrounding obstacles.


How should the outdoor unit be transported and handled?

• Move the unit to the installation location as close as possible before opening the packaging.

• Do not place anything on top of the equipment.

• Use 2 ropes when hoisting the outdoor unit.

• Hoist the unit levelly and slowly.

• Do not remove the packaging during hoisting.

• Avoid tying the elevator ropes in a way that hits the unit packaging or wrapping.

• Use suitable protection when hoisting the exterior.

• Before installation, do not deposit any material near the outdoor unit location to avoid fire hazards.

• Do not demolish the wooden foundation during handling.

• Prevent the outdoor unit from inclining.

• Handling should be done by more than two people.

• Use the designated handle points as shown in the manual diagram.


What are the requirements for refrigerant pipe connection?

General Method:

• Keep pipes as short as possible for efficiency.

• Daub refrigerant oil (ester oil for R410A) on the connector and flare nut.

• When bending pipes, use the largest possible semi-diameter (over 4 times pipe diameter) to avoid breakage.

• Align pipe centers, thread the nut by hand, then tighten with double spanners to the specified torque.

• Prevent impurities (sand, water) from entering the pipe. Use anti-fouling measures (clean pipe, flatten end, seal). Flat the pipe end or seal with adhesive tape depending on storage duration before installation.

Installation Cautions:

• When welding with hard solder, charge nitrogen (0.02MPa gauge pressure) into the pipe to prevent oxidation. Oxide film can clog capillaries/expansion valves.

• Ensure pipes are clean. If impurities enter, clean by flowing nitrogen (approx. 0.5MPa) through the pipe, stopping the ends intermittently.

• Install piping after stop valves are closed.

• Cool valves with a wet towel when welding near them.

• Use special shears, not a saw, to cut pipes.

• Use phosphor copper welding rod without flux for copper pipe welding. Flux (especially chlorine/fluorine containing) damages piping and refrigeration oil.

Material and Specs:

• Use phosphoric oxidize seamless copper pipe: C1220T-1/2H (diameter > 19.05mm); C1220T-0 (diameter ≤ 15.88mm).

• Confirm pipe thickness and specs based on selection method. For R410A, pipes over 19.05mm must be 1/2H type and meet minimum thickness requirements.

• Branch pipes and gather pipes must be manufacturer-specified.

• Install pipes within the allowable length/drop range.


How are refrigerant pipe diameters selected?

Pipe diameters depend on the location in the system and the connected capacity:

Pipe “a” (Between indoor unit and branch pipe): Diameter depends on the specific indoor unit’s gas and liquid pipe requirements (refer to indoor unit installation manual).

Pipe “b” (Between branch pipes): Diameter depends on the total indoor capacity downstream from that pipe section.

Pipe “b” Diameter Selection
Total indoor capacity after the branch pipe (kW) Gas pipe (mm) Liquid pipe (mm)
<16.8kW Ø15.88 Ø9.52
16.8kW ≤ X < 22.4kW Ø19.05 Ø9.52
22.4kW ≤ X < 33.0kW Ø22.22 Ø9.52
33.0kW ≤ X < 47.0kW Ø28.58 Ø12.7

Note: If the total indoor capacity after pipe ‘b’ is less than 14.0kW, use the same specs as pipe ‘a’. Adjust diameter on field if needed.

Pipe “c” (Main pipe between outdoor unit gather pipe and first branch pipe):

Pipe “c” Diameter Selection
Model Main Gas pipe (mm) Main Liquid pipe (mm) Enlarged Main Gas pipe (mm) Enlarged Main Liquid pipe (mm)
VVFA-220R-01T32 Ø19.05 Ø9.52 Ø22.22 Ø12.7
VVFA-280R-01T32 Ø22.22 Ø9.52 Ø25.4 Ø12.7
VVFA-335R-01T32 Ø25.4 Ø12.7 Ø28.58 Ø15.88

Note: Enlarge the main pipe diameter if the distance from the outdoor unit to the longest indoor unit is over 90m.

Copper Pipe Material Selection:

Material O type pipe: Soft pipe Hard pipe
Pipe diameter (mm) Ø6.35 Ø9.52 Ø12.7 Ø15.88 Ø19.05 Ø22.22 Ø25.4 Ø28.58 Ø31.8
Thickness (mm) 0.8 0.8 1.0 1.0 1.0 1.0 1.0 1.0 1.1

What are the applicable piping length and height difference limits?

Item Limit
Single way total pipe length 300m
Single way pipe length (Actual) Max.: 150m (Equivalent Length 175m)
Main pipe between outdoor to 1st branch Max.: 110m (Equivalent Length 135m)
Pipe length between outdoors Less than 10m to 1st branch pipe
Height difference between indoor and outdoor (Outdoor is upper) Max. 50m
Height difference between indoor and outdoor (Outdoor is lower) Max. 40m
Height difference between outdoors (in the same system) Within 5m (better be horizontal)
Height difference between indoors Max. 15m

What are the pipe connection methods for the outdoor unit?

Model Gas Pipe Diameter (mm) Gas Connection Method Liquid Pipe Diameter (mm) Liquid Connection Method
VVFA-220R-01T32 Ø19.05 Flared joint Ø9.52 Flared joint and Brazing
VVFA-280R-01T32 Ø22.22 Flared joint and Brazing Ø9.52
VVFA-335R-01T32 Ø25.4 Ø12.7 Flared joint

What are the pipe connection specifications for indoor units?

Model Capacity Gas pipe Diameter (mm) Gas Connecting method Liquid pipe Diameter (mm) Liquid Connecting method
07 Ø9.52 Braze Ø6.35 Flared
09 Ø9.52 Ø6.35
12 Ø12.7 Ø6.35
16 Ø12.7 Ø6.35
18 Ø12.7 Ø6.35
24 Ø15.88 Ø9.52
28 Ø15.88 Ø9.52
30 Ø15.88 Ø9.52
38 Ø15.88 Ø9.52
48 Ø15.88 Ø9.52
72 Ø25.4 Braze Ø9.52 Flared
96 Ø25.4 Ø9.52

Pipe Flare Torque Specifications:

Diameter (mm) Torque (N·m)
Ø6.35 14~18
Ø9.52 34~42
Ø12.7 49~61
Ø15.88 68~82
Ø19.05 84~98

How are branch pipes selected and installed?

Branch Pipe Selection:

Total indoor capacity (100W) Model (optional)
Less than 335 TAU-335
More than 335, less than 506 TAU-506

The master unit (main outdoor unit) will choose the closest model to the 1st branch pipe.

Installation Notes:

1. Pay attention to the outdoor unit pipe dimensions when connecting the outdoor branch pipe.

2. Diameter adjustments between outdoor branch pipes or between units must be executed at the branch pipe side.

3. Install the outdoor branch pipe (gas/liquid side) horizontally or vertically.

4. When welding with hard solder, blow nitrogen through the pipe to prevent oxidation, which can cause heavy damage. Protect the pipe from water and dust by making the brim as an outer roll.

5. Prepare the pipe end on field, cut off the pipe with a cutter (cut off at the middle), ensure it is horizontal, seal the connection, and wrap with heat insulator and adhesive tape.


What are the procedures for pipe installation, expansion, and brazing?

General Pipe Installation:

• Avoid collision between pipes and unit parts.

• Close valves fully when connecting pipes.

• Protect pipe ends from water and impurities (weld flat or seal with tape).

• Bend pipes with a large semi-diameter (over 4x pipe diameter).

Pipe Expansion (for flared connections, e.g., outdoor liquid pipe):

• Use a special tool for R410A.

• Install the expanding nut first.

• Adjust projecting pipe length using a copper pipe gauge if needed.

• Use ester oil (not mineral oil) as expanding oil.

• Refer to the table for correct expansion dimension ‘A’ and projecting length ‘B’.

Pipe outer diameter (mm)Expanding pipe A (mm) (0/-0.4)Projecting length B (mm) (Special tool for R410A)Projecting length B (mm) (The former tool)
Ø6.359.10-0.51.0-1.5
Ø9.5213.2
Ø12.716.6
Ø15.8819.7

• After expansion, fasten the flare connection using a double-spanner to the correct torque.

Brazing (for outdoor gas pipe, distributing pipes, branch pipes):

• Braze with hard solder.

• During brazing, charge nitrogen through the pipe to prevent oxidation (impurity film) which can clog components and cause failure.

• Seal the pipe end with tape or a stopper to increase resistance while flowing nitrogen.

• Only use nitrogen gas for purging during brazing.


How is a leakage test performed?

1. The outdoor unit is factory tested. Test the field-installed piping individually; do not test after connecting to the unit’s stop valves.

2. Connect a gauge manifold and nitrogen cylinder to both the gas and liquid service ports (ensure valves are closed).

3. Pressurize step-by-step using dry nitrogen only (do not use oxygen, chlorine, or flammable gas):

a. Apply 0.5MPa (approx. 73 psi) for > 5 minutes. Check for pressure drop.

b. Apply 1.5MPa (approx. 218 psi) for > 5 minutes. Check for pressure drop.

c. Apply the target pressure of 4.15MPa (approx. 602 psi). Record the pressure and ambient temperature.

d. Leave pressurized at 4.15MPa for at least 1 day (24 hours). If the pressure does not drop (after correcting for temperature changes), the test is passed. Note: Pressure changes approx. 0.01MPa per 1°C temperature change.

e. If pressure drops at any stage, there is a leak. Use soapy water or a suitable leak detector to find the leak (check brazing points, flared connections). Repair the leak and repeat the test from step ‘a’.

4. After a successful leakage test, release the nitrogen pressure and proceed to evacuation.


How is the system evacuated?

1. Connect a vacuum pump via a gauge manifold to the service ports on both the liquid and gas stop valves.

2. Evacuate the system (including piping and potentially the oil equalization pipe if applicable).

3. Run the vacuum pump until the pressure reaches -100.7 KPa (below -755 mmHg or approx. 29.75 inHg vacuum) or less.

4. Continue running the vacuum pump for at least 1 hour after reaching this vacuum level.

5. Close the manifold valves and stop the vacuum pump.

6. Leave the system for over 1 hour and check if the vacuum pointer on the gauge rises.

7. If the vacuum pointer rises, it indicates moisture or a leak in the system. Check for leaks again and re-evacuate. If no leaks are found, moisture is present, continue evacuation for longer.

8. If the vacuum holds steady for over 1 hour, evacuation is complete.


How are the check valves (stop valves) operated?

Open/Close Method:

1. Remove the valve cap.

2. Use a hexangular spanner (Allen key) to turn the valve stem.

3. Turn counter-clockwise fully to open the valve until it stops. Do not apply excessive force once open.

4. Turn clockwise fully to close the valve.

5. Replace and tighten the valve cap securely after operation.

Tightening Torques:

Valve Shaft (valve body stem) N·m Cap (cover) N·m T-shape nut (check joint/service port) N·m
For gas pipe 8~9 22~27 8~10
For liquid pipe 5~6 13~16

How is additional refrigerant charged?

1. The unit comes factory charged (W1), requires an on-site charge (W2 – usually 0kg for these models based on the table), and additional charge based on liquid line length (W3).

2. Calculate the additional refrigerant volume (W3) based on the installed liquid pipe lengths and diameters:

W3 = (L1 × 0.35) + (L2 × 0.25) + (L3 × 0.17) + (L4 × 0.11) + (L5 × 0.054) + (L6 × 0.022)

Where L1 to L6 are the lengths (m) of liquid pipes with diameters Ø22.22, Ø19.05, Ø15.88, Ø12.7, Ø9.52, and Ø6.35 mm respectively. Use the table below for per-meter values:

Liquid pipe diameter (mm)Additional refrigerant amount (kg/m)
Ø6.350.022 kg/m
Ø9.520.054 kg/m
Ø12.70.11 kg/m
Ø15.880.17 kg/m
Ø19.050.25 kg/m
Ø22.220.35 kg/m

3. Total refrigerant needed on site = W2 + W3.

4. Total refrigerant in system = W1 + W2 + W3.

5. Charge the calculated additional refrigerant (W3) using a charging scale and manifold gauge.

6. Important R410A Precautions:

• Charge refrigerant in liquid state from the R410A cylinder (typically pink).

• Use dedicated R410A tools (manifold, hoses).

• Do not use a charging cylinder as R410A composition can change.

• Use an anti-counter-flow adapter to prevent compressor oil from entering the refrigerant cycle.

7. If the full additional charge cannot be added while the unit is stopped, add the remaining amount during trial operation mode.

8. Complete charging within 30 minutes if the unit is running.

9. Record the total charged amount (W1+W2+W3) on the label for maintenance purposes.

10. Running the unit with insufficient refrigerant for a long period will cause compressor failure.


What are the requirements for heat insulation?

• Both gas pipe and liquid pipe must be heat insulated separately.

• Material for the gas pipe insulation must withstand temperatures over 120°C.

• Material for the liquid pipe insulation must withstand temperatures over 70°C.

• Insulation thickness should be over 10mm. If ambient temperature is 30°C and relative humidity is over 80%, the thickness should be over 20mm to prevent condensation.

• Apply the insulation material closely to the pipe without gaps.

• Wrap the insulation securely with adhesive tape.

• Keep connection wires separate from the heat insulation material (at least 20cm away).


How should refrigerant pipes be fixed?

• Refrigerant pipes vibrate and expand/shrink during operation.

• Fix the pipe securely at intervals of every 2-3 meters to prevent central stress concentrating in one area, which could cause the pipe to break.


How is communication wiring configured?

• Outdoor and all indoor units are connected in parallel using 2 non-polar wires (terminals P and Q).

• The ground wire of the outdoor unit must pass through the buckle magnetic ring.

• The shielding layer of the communication wire must be connected together and earthed at a single point (usually at the outdoor unit).

• Total communication wire length cannot exceed 1000m.

• Use 2-core x (0.75-2.0mm²) shielded wire between outdoor/indoor units and between indoor units.

Wired Controller Connection:

• Use 0.75mm² × 3 core shielding line for wired controllers, with a maximum length of 250m.

• The shielding layer must be grounded at one end.

• Connection methods:

1. 1 to Multi (Group Control): One wired controller controls 2-19 indoors. Connect the controller to the designated master indoor unit via 3 polar wires (A, B, C). Connect other slave indoors to the master indoor via 2 or 3 polar wires (AC indoors use B, C; DC indoors use A, B, C* – refer to indoor manual). Indoor 5 in the diagram is the master.

2. 1 to 1: One wired controller controls one indoor unit. Connect via 3 polar wires (A, B, C). Indoors 6-18 in the diagram.

3. 2 to 1: Two wired controllers control one indoor unit. Set one as master, one as slave. Connect both controllers and the indoor unit via 3 polar wires (A, B, C). Indoor 19 in the diagram.

• *Note: If using a remote controller, terminals A, B, C on the signal block may not need wires; consult the specific controller/indoor unit table.


What are the power wiring requirements?

• Ensure input voltage is no less than 380V when running; lower voltage may cause abnormal operation.

• Pass the communication line shielding layer of the outdoor unit through the buckle magnetic ring.

• Outdoor unit power source: 3N~, 380-415V, 50/60Hz.

• Indoor unit power source: 1PH, 220-240V~, 50/60Hz.

• Indoor and outdoor units must use their individual power sources. All indoor units should use one common power source.

• Must install a leakage breaker (Ground Fault Interrupter) and an overcurrent breaker for each power source. Failure to do so may cause electric shock.

• Power cables must be fixed firmly.

• Each outdoor unit must be earthed well.

• If power cable length exceeds the specified range, thicken the cable appropriately.

Outdoor Power Source and Cable Specifications:

Model Power source Power cable Residual Current Circuit Breaker (RCCB) / Ground Fault Interruptor (GFI) Ground wire
Section (mm²) Wire length (m) Circuit Breaker (A) Rated current (A) / Sensitivity (mA) Response time (S) Section (mm²) Screw
VVFA-220R-01T323N~, 380-415V, 50/60 Hz6204040A / 30mAbelow 0.1S6M5
VVFA-280R-01T3210204040A / 30mAbelow 0.1S10M5
VVFA-335R-01T3210204040A / 30mAbelow 0.1S10M5

Indoor Power Source and Communication Wiring Specifications:

Item Indoor total current (A) Power cable section (mm²) Wire length (m) Rated current of overcurrent breaker (A) Rated current of residual circuit breaker(A) / Ground fault interruptor(mA) / response time(S) Communication wire section Outdoor/indoor (mm²) Communication wire section Indoor/indoor (mm²)
<102202020A, 30mA, below 0.1s2-core x (0.75-2.0mm²) shielded wire2-core x (0.75-2.0mm²) shielded wire
≥10 and <153.5253030A, 30mA, below 0.1s
≥15 and <225.5304040A, 30mA, below 0.1s
≥22 and <2710405050A, 30mA, below 0.1s

What happens during trial operation and normal performance?

5-Minute Delay Function:

• After powering off and restarting the unit, the compressor has a built-in delay and will run approximately 5 minutes later to protect itself.

Cooling/Heating Operation:

• Indoor units can be controlled individually.

• Units cannot run in Cool and Heat modes simultaneously within the same system. If modes conflict, the unit set later will enter standby, and the unit set earlier will continue to run.

• If an A/C manager fixes the system mode (Cooling or Heating), units cannot operate in the other mode.

Heating Mode Characteristics:

• If the outdoor temperature rises significantly during heating operation, the indoor fan motor may switch to low speed or stop temporarily.

Defrosting in Heating Mode:

• Outdoor unit defrosting is necessary in heating mode and affects heating efficiency temporarily.

• The unit defrosts automatically for about 2-10 minutes when required.

• During defrost, condensate water will flow from the outdoor unit, and vapour may appear, which is normal.

• The indoor fan motor will run at low speed or stop during defrost. The outdoor fan motor will also stop.

Unit Operation Condition:

• Operate the unit within the allowed temperature and humidity ranges specified in the manual. Operating outside these ranges may trigger protection devices.

• Relative humidity should be lower than 80%. Running the unit continuously with humidity over 80% can lead to dew formation on the unit and potentially dripping water from the air outlet.


How are the Dip Switches set?

SwitchFunctionSetting Detail
BM1-1Indoor unit quantity lock settingOFF: Lock function disabled
ON: Lock function enabled (Set to ON after confirming correct communication with all units)
BM1-2Model settingReserved
BM1-3Model settingSee manual table (Page 18) based on model capacity (08/10/12 HP)
BM1-4Model settingSee manual table (Page 18) based on model capacity (08/10/12 HP)
BM1-5Model settingSee manual table (Page 18) based on model capacity (08/10/12 HP)
BM1-6Model settingSee manual table (Page 18) based on model capacity (08/10/12 HP)
BM1-7Model settingSee manual table (Page 18) based on model capacity (08/10/12 HP)
BM1-8Oil return mode settingOFF: Standard oil return
ON: Enhanced oil return (Use if oil return is poor or noise occurs)
SW4Query buttonPress to enter query state
SW5Increase buttonPress to increase value or sequence number
SW6Decrease buttonPress to decrease value or sequence number
SW7Confirm buttonPress to confirm setting or enter next level menu

Note: BM1 settings related to model capacity (BM1-3 to BM1-7) must be set correctly on site according to the specific outdoor unit model.


How is the outdoor unit digital tube display used for settings and queries?

The outdoor unit has a digital display and four buttons (SW4: Query, SW5: Increase, SW6: Decrease, SW7: Confirm) for checking parameters and making settings.

Querying Parameters:

1. Press SW4 (Query). The display shows “0”.

2. Use SW5 (Increase) or SW6 (Decrease) to select the parameter code you want to query (e.g., “1” for T1 indoor ambient temp, “2” for T2 indoor coil temp, etc. – refer to the manual table for full list).

3. Press SW7 (Confirm). The display shows the value of the selected parameter.

4. Press SW4 (Query) to return to the parameter code selection, or wait 20 seconds for it to exit automatically.

Setting Parameters (Password Required):

1. Press SW4 (Query). Display shows “0”.

2. Press SW7 (Confirm). Display shows “P 0”.

3. Press SW7 (Confirm) again. Display shows “0”.

4. Use SW5/SW6 to enter the password (default: 66). Press SW7 to confirm each digit.

5. After correct password entry, display shows “P –“.

6. Press SW4 (Query). Display shows “0”.

7. Use SW5/SW6 to select the parameter code to set (e.g., “60” for outdoor unit address, “61” for indoor unit quantity – refer to manual table).

8. Press SW7 (Confirm). The display shows the current value of the parameter.

9. Use SW5/SW6 to change the value to the desired setting.

10. Press SW7 (Confirm) to save the new setting. Display shows “P –“.

11. Press SW4 (Query) twice to exit the setting state.

Example: Setting Outdoor Unit Address to 1

SW4 -> SW7 -> SW7 -> SW5 (to 6) -> SW7 -> SW5 (to 6) -> SW7 (Password OK, shows “P –“) -> SW4 -> SW5 (to 60) -> SW7 (Shows current address, e.g., “0”) -> SW5 (to 1) -> SW7 (Setting saved, shows “P –“) -> SW4 -> SW4 (Exit).

Refer to the manual for the complete list of queryable (0-51) and settable (60-81) parameter codes and their meanings.


How does the outdoor unit control the compressor?

Startup Control:

• Ensures prerequisites are met (e.g., no critical errors, 5-minute delay passed).

• Starts at a low frequency and gradually increases based on system demand and stability.

• Includes oil return logic during startup if needed.

Output Control (Frequency Adjustment):

• The compressor’s running frequency is adjusted based on the difference between the target evaporation temperature (Te) or condensation temperature (Tc) and the actual temperatures derived from sensors.

• Target Te/Tc is determined by indoor unit settings and outdoor ambient conditions.

• Frequency is increased or decreased within operational limits (minimum/maximum frequency) to meet the cooling or heating load efficiently while maintaining stable operation.

• PID control is used for precise adjustments based on pressure sensor readings and temperature targets.


How does the defrosting control work?

Defrosting operates only during heating mode to remove ice buildup on the outdoor coil.

Conditions to Enter Defrost:

• The system must be running in heating mode.

• The outdoor coil temperature (T3/Tdef sensor) drops below a certain threshold, indicating potential frost formation.

• A timer condition is met (defrost won’t occur too frequently).

• Intelligent defrost logic compares the change in low pressure and defrost temperature sensor readings to determine the actual frosting degree before initiating defrost.

Defrosting Process:

• The 4-way valve switches (reversing the refrigerant cycle temporarily, similar to cooling mode).

• The indoor fan stops or runs at very low speed.

• The outdoor fan stops.

• The compressor runs to circulate hot gas through the outdoor coil, melting the frost.

Conditions to Exit Defrost:

• The outdoor coil temperature (T3/Tdef) rises above a set point, indicating frost has cleared.

• OR, a maximum defrost time limit (typically 10-12 minutes) is reached.

After Defrost:

• The 4-way valve switches back to heating mode.

• The outdoor and indoor fans resume normal heating operation.


How does the oil return control work?

Oil return control ensures sufficient lubricating oil returns to the compressor, especially during prolonged low-load operation or in systems with long piping.

Conditions to Initiate Oil Return:

• The system detects conditions conducive to poor oil return, such as:

• Compressor running continuously for a long duration (e.g., several hours).

• Operating at low frequencies for extended periods.

• Specific temperature or pressure conditions indicating oil might be trapped in the system.

• Some systems may have a timed oil return cycle (e.g., every 8 hours of cumulative compressor run time).

• Enhanced oil return mode can be selected via Dip Switch BM1-8 if standard oil return is insufficient.

Oil Return Process:

• The system temporarily adjusts operating parameters to increase refrigerant velocity and encourage oil flow back to the compressor.

• This may involve briefly increasing compressor frequency and potentially adjusting valve positions.

• The oil return cycle runs for a predetermined duration (typically a few minutes).

Completion:

• After the cycle duration, the system returns to normal operation based on the current demand.


What do the failure codes mean?

DisplayMalfunction ContentCause Analysis
E0Communication malfunction between indoor and outdoor units1.Wiring error 2.Address error 3.PCB error 4.Interference
E1Phase sequence error or phase missing1.Wiring error 2.Power supply issue 3.Outdoor PCB error
E2Communication malfunction between outdoor units1.Wiring error 2.Address error 3.PCB error 4.Interference
E3T3 sensor malfunction1.Sensor disconnected 2.Sensor damaged 3.PCB error
E4T4 sensor malfunction1.Sensor disconnected 2.Sensor damaged 3.PCB error
E5T5 sensor malfunction1.Sensor disconnected 2.Sensor damaged 3.PCB error
E8Outdoor unit address setting malfunction1.Address setting error 2.Multiple masters set
E9Water level switch malfunction1.Float switch issue 2.Water pump error 3.Drainage blocked
H0Communication error between main chip and wired controller1.Wiring error 2.Wired controller PCB error 3.Main PCB error
H1Oil level switch protection1.Insufficient oil 2.Switch wiring loose 3.Switch damaged
H3Compressor overheat protection1.Refrigerant shortage 2.System blocked 3.Compressor failure
H4System abnormality (System 1)1.Refrigerant shortage 2.System blocked 3.Expansion valve error
H5IPM module protection1.Voltage unstable 2.Module overheat 3.Compressor/fan failure
H6Low pressure protection1.Refrigerant shortage 2.System blocked 3.Expansion valve error
H7Compressor desynchronizing protection1.Compressor failure 2.IPM module error 3.Wiring error
H8System abnormality (System 2)(Similar to H4, for multi-system units)
H9Electronic expansion valve malfunction (System 1)1.Valve coil issue 2.Valve body stuck 3.Wiring error 4.PCB error
F0Refrigerant leakage detection (System 1)1.Significant refrigerant loss 2.Sensor error
F1Refrigerant leakage detection (System 2)(Similar to F0, for multi-system units)
F2Electronic expansion valve malfunction (System 2)(Similar to H9, for multi-system units)
F3Oil balance valve malfunction (System 1)1.Valve coil issue 2.Valve body stuck 3.Wiring error 4.PCB error
F4Oil balance valve malfunction (System 2)(Similar to F3, for multi-system units)
F5High pressure sensor malfunction1.Sensor disconnected 2.Sensor damaged 3.PCB error
F6Low pressure sensor malfunction1.Sensor disconnected 2.Sensor damaged 3.PCB error
F7T3B sensor malfunction1.Sensor disconnected 2.Sensor damaged 3.PCB error
P0Compressor top temperature protection1.Refrigerant shortage 2.System blocked 3.Sensor error
P1High pressure protection1.Excess refrigerant 2.Poor heat exchange 3.Fan failure 4.System blocked
P2Low pressure protection (Heating)1.Refrigerant shortage 2.Expansion valve error 3.Sensor error
P3Compressor current protection1.Voltage unstable 2.Compressor failure 3.Excess refrigerant
P4Compressor discharge temperature protection1.Refrigerant shortage 2.System blocked 3.Sensor error
P5Condenser high temperature protection (Cooling)1.Poor heat exchange 2.Fan failure 3.High ambient temp
P6Inverter module protection1.Voltage unstable 2.Module overheat 3.Fan failure
P7Communication error between main control board and drive board1.Wiring error 2.Interference 3.PCB failure
P8Outdoor DC fan motor malfunction1.Motor failure 2.Wiring error 3.PCB error
P9Compressor startup failure1.Wiring error 2.Compressor failure 3.Drive board error
L0Number of indoor units malfunction1.Incorrect quantity setting 2.Communication error
L1Capacity setting error1.Incorrect model setting 2.Exceeds capacity limits
L2Address setting conflict1.Duplicate indoor/outdoor address
L3Indoor unit model mismatch1.Incompatible indoor unit connected
L4Indoor and outdoor units mismatch1.Incorrect system combination
L5Master/Slave outdoor unit conflict1.Multiple masters set 2.Incorrect connection
L6Network topology error1.Incorrect communication wiring configuration
L7Mode conflict1.Indoor units set to different modes (Cool/Heat)
LPIndoor unit address setting error1.Duplicate indoor address
U1Indoor T1 sensor malfunction1.Sensor disconnected/damaged 2.Indoor PCB error
U2Indoor T2 sensor malfunction1.Sensor disconnected/damaged 2.Indoor PCB error
U3Indoor T2B sensor malfunction1.Sensor disconnected/damaged 2.Indoor PCB error
U4Indoor fan motor malfunction1.Motor failure 2.Wiring error 3.Indoor PCB error
U5Indoor EEPROM malfunction1.Data corruption 2.Indoor PCB failure
U6Zero crossing detection error1.Power supply issue 2.Indoor PCB failure
U7Wired controller malfunction1.Controller error 2.Wiring error

Note: This list combines common VRF codes; specific codes may vary slightly. Refer to the display on the unit and detailed troubleshooting section.


How can common problems be troubleshooted?

1. Unit Cannot Start At All

• Checkpoints: Power supply off? Power plug loose? Breaker tripped? Voltage abnormal? Timer set correctly? Controller ON?

• Solution: Turn power on, secure plug, reset breaker, check voltage, check timer settings, turn controller on.

2. Insufficient Cooling/Heating

• Checkpoints: Temperature setting appropriate? Air filter dirty? Doors/windows open? Air inlet/outlet blocked? Fan speed too low? Outdoor unit heat exchanger dirty/blocked? System in defrost mode (heating)? Refrigerant level correct?

• Solution: Adjust set temperature, clean filter, close doors/windows, remove obstructions, increase fan speed, clean outdoor unit, wait for defrost to finish, check refrigerant charge (professional needed).

3. Water Leaks from Indoor Unit

• Checkpoints: Unit tilted? Drain hose blocked or improperly installed? Humidity too high (>80%)?

• Solution: Level the unit, clear/reinstall drain hose, reduce humidity if possible.

4. Water Leaks from Outdoor Unit

• Checkpoints: Normal condensation during cooling? Normal meltwater during defrost (heating)?

• Solution: Usually normal, ensure proper drainage if needed.

5. Abnormal Noise

• Checkpoints: Unit installed securely? Foreign objects inside? Fan blades hitting something? Refrigerant flow sounds (gurgling)? Expansion/contraction sounds?

• Solution: Secure installation, remove foreign objects, check fan clearance. Flow/expansion sounds are often normal.

6. Unit Emits Odor

• Checkpoints: Air filter dirty? Odor source in the room being circulated?

• Solution: Clean filter, eliminate room odor source.

7. Remote Control Not Working / Display Dim

• Checkpoints: Batteries dead/incorrectly installed? Distance/angle to unit correct? Obstructions between remote and unit? Strong light interference (fluorescent)?

• Solution: Replace/reinstall batteries, check distance/angle/obstructions, turn off interfering lights.

8. Mist from Air Outlet

• Checkpoints: Room air cooled rapidly causing condensation?

• Solution: Normal phenomenon, especially in high humidity.

9. Specific Error Code Displayed (e.g., E0, P1, U4)

• Checkpoints: Refer to the Failure Code table in the manual.

• Solution: Follow the cause analysis and corrective actions suggested for the specific code. May require professional service.

Important: If the problem persists after checking these points, or if a serious error code appears, turn off the unit, disconnect power, and contact qualified service personnel. Do not attempt complex repairs yourself.


What is the function of the high pressure switch protection device?

The high pressure switch is a device which can stop the unit automatically when the unit runs abnormally. When the high pressure switch acts, the cooling/heating mode will stop but the running LED on the wired controller will still be lit. The wired controller will display a failure code.


When does the high pressure switch protection device activate?

The protection device will act in the following cases:

• In cooling mode, air outlet and air inlet of the outdoor unit are clogged.

• In heating mode, the indoor filter is sticked with dust; indoor air outlet is clogged.


What should I do if the protection device acts?

When the protection device acts, please cut off the power source and re-start up after eliminating the trouble.


What happens when there is a power failure while the unit is running?

When power fails during running, all operations will stop.


How does the unit behave after power is restored following a failure?

After being electrified again:

• If the unit has a re-start up function, it can resume to the state before power off automatically.

• If the unit does not have a re-start up function, it needs to be switched on again manually.


What should I do if the unit runs abnormally due to thunder, lightning, or interference?

When abnormal occurs in running because of the thunder, the lightning, the interference of car or radio, etc, please cut off the power source. After eliminating the failure, press the “ON/OFF” button to start up the unit.


How does the heating mode work and how does outdoor temperature affect it?

The heating mode adopts the heat pump type that absorbs outdoor heat energy and releases it into indoor. So if the outdoor temperature goes down, the heating capacity will decrease.


What checks are needed before the trial operation?

Before trial operation:

• Before being energized, measure the resistor between power terminal block (live wire and neutral wire) and the grounded point with a multimeter, and check if it is over 1MΩ. If not, the unit cannot operate.

• To protect the compressor, energize the outdoor unit for at least 12 hours before the unit runs. If the crankcase heater is not energized for 6 hours, the compressor will not work. Confirm the compressor bottom is getting hot.

• Except for the condition that there is only one master unit connected (no slave unit), under the other conditions, open fully the outdoor operating valves (gas side, liquid side, oil equalization pipe). If operating the unit without opening the valves, compressor failure will occur.

• Confirm all indoor units are being electrified. If not, water leakage will occur.

• Measure the system pressure with pressure gauge, at the same time, operate the unit.


What should I do during the trial operation?

In trial operation, refer to the information of the performance section.

When the unit cannot start up at the room temperature, make trial operation for the outdoor unit.


How do I use the BM1 dip switch settings?

The BM1 dip switch settings introduction:

Switch Setting Function/Description
BM1_1 0 Start to search indoor unit (Default)
1 Stop searching indoor unit and lock the quantity
BM1_2 to BM1_5 Capacity selection (See table below)
BM1_6 0 Indoor units ON/OFF simultaneous control available (Default)
1 Indoor units ON/OFF simultaneous control unavailable
BM1_7 0 Defrosting level: Ordinary (Default)
1 Defrosting level: Strengthen defrosting
BM1_8 0 Quiet running function is invalid (Default)
1 Quiet running function is valid

Note: System cannot operate without locking, and cannot operate when the locking number is not in accordance with the actual quantity.


What are the BM1 dip switch settings for Capacity Selection?

BM1_2 BM1_3 BM1_4 BM1_5 Capacity selection
0 0 1 1 8HP
0 1 0 1 10HP
0 1 1 1 12HP

How do I enter and navigate the parameter settings using the outdoor digital tube display?

Key operations:

• Long press ENTER (SW7) 3 seconds to enter dial parameter selection.

• Short press ENTER (SW7) switch edit mode.

• Short press EXIT (SW6) exit.

• Long press ENTER (SW7) 3 seconds to enter parameter view or modify mode.

• Short press UP (SW4) data increase.

• Short press DOWN (SW5) data decrease.

• Short press SW6 exit parameter view or modify mode.

Display parts:

• LD1, LD2, LD3, LD4: 4 digital tubes from left to right.

• Dial code list display mode: LD1 display “_”.

• Parameter display mode: LD1 display “=”.


How can I view indoor unit parameters using SW1, SW2, and SW3?

You can view the indoor machine 128 sets of parameters: SW1 and SW2 represent the indoor unit address, SW3 range is 3-14 can view the indoor unit parameters.


What are the system addresses corresponding to SW1 and SW2 settings for indoor unit parameters?

SW1 SW2 System Address
0 0-F 1 to 16 (PCB address 0#~15#)
1 17 to 32 (PCB address 16#~31#)
2 33 to 48 (PCB address 32#~47#)
3 49 to 64 (PCB address 48#~63#)
7 65 to 80 (PCB address 64#~79#)
8 81 to 96 (PCB address 80#~95#)
9 97 to 112 (PCB address 96#~111#)
A 113 to 128 (PCB address 112~127#)

What indoor unit parameters can be viewed using SW3 settings 3 through 14?

SW3 Function Digital tube LD1 ~ 4 display
3 Indoor unit communication check and program version Communication normal display indoor unit program version (1 decimal), the communication interrupted normal display “0000” (5 consecutive round of no communication success), communication has been abnormal display “—- “. For example: 3.9, means the indoor unit version is V3.9
4 Indoor unit failure Display indoor failure code; no failure, display 0
5 Indoor unit capacity The indoor unit capacity (unit: HP, one decimal), 1.5 HP displays 1.5
6 Indoor EEV open angle Electronic expansion valve (EEV) open angle (Unit: PIs)
7 Indoor ambient temp. Tai Ambient temperature (Unit: °C)
8 Indoor gas temperature Tc1 Gas pipe temperature (Unit: °C)
9 Indoor liquid temperature Tc2 Liquid pipe temperature (Unit: °C)
10 (A) Indoor startup mode, actual fan speed and SCODE code LD2 indicates startup mode (O: Stop C: cooling H: Heating)
LD3 indicates actual fan speed of indoor unit (0 – stop, 1 – low speed, 2 – medium speed and 3 – high speed)
LD4 indicate SCODE code (0~15(F)).
For example, C3B indicates cooling running at high wind, and the SCODE is 11.
11 (B) Indoor set temperature Tset Indoor set temperature (Unit: °C)
12 (C) Reserve
13 (D) Reserve
14 (E) Forced indoor cooling / heating / stop (1) press ENTER (SW7) for 3 seconds, to enter setting state, the instruction value is flashing displayed
(2) press UP (SW4) or DOWN (SW5) to adjust instruction (COOL/HEAT/OFF).
(3) after finish the adjustment, press ENTER (SW7) for 3 seconds, execute the setting instruction and stop flashing

How do I select the outdoor unit and view its parameters using SW1 and SW3?

0~3 of SW1 is used to select the outdoor number. SW3 range of 0, 1, 15, observe the outdoor unit parameters.

(The master unit can display the parameters of the other outdoor unit and the indoor units, while the slave outdoor only displays its own parameters).


What outdoor unit parameters can be viewed or set using SW3?

SW1 SW2 SW3 Function Digital tube LD2 ~ 4 display
Outdoor unit address 0-3 0 0 Display outdoor unit failure code and Display special running code Outdoor unit fault code (when the number of indoor units is not locked, Cycle in turn shows “number of indoor units, number of outdoor units, type of power supply “.
(1) Number of indoor units :” U16″ means that the outdoor unit is connected to 16 indoor units.
(2) Number of outdoor units :5.5 P. for 150 model.
(3) Power type :220 for single phase 220 V, 380 for 3~380 V.

Special operating code:
DRM1 mode: flashing display d1″;
DRM2 mode: cycle display in turn “d2, compressor frequency “;
DRM3 mode: cycle display “d3, compressor frequency”
Self-cleaning mode: in cooling display “CLC”,” in Heat flashing CLH”
0 2 Display operation mode LD2-LD4 means
Stop: OFF, Cooling: CCC Heating: HHH,
Cooling only: C— Heat pump: H–
0 3 Outdoor fan 1 speed 345 representation 345rpm
• Press ENTER (SW7) for 3s continuously, display 1111, then to set: flashing. Press UP (SW4) once, fan speed will go up 1 level; press DOWN (SW5) once, fan speed will decrease 1 level.
• Press EXIT (SW6) for 3s continuously, display 0000, then quit the setting condition, and stop flashing.
0 4 Outdoor fan 2 speed 345 representation 345rpm
• Press ENTER (SW7) for 3s continuously, display 1111, then to set: flashing. Press UP (SW4) once, fan speed will go up 1 level; press DOWN (SW5) once, fan speed will decrease 1 level.
• Press EXIT (SW6) for 3s continuously, display 0000, then quit the setting condition, and stop flashing.
0 5 Frequency converter INV1 current frequency 110 representation 110.0Hz
• Press ENTER (SW7) for 3 seconds, display 1111, enter the set state: flashing display, each according to the 1 UP (SW4) frequency rise 1Hz, every 1 times DOWN (SW5) frequency drop 1Hz; Long press UP (SW4) or DOWN (SW5) can quickly adjust the frequency.
• Press EXIT(SW6) for 3 seconds, display 0000, quit the set state, stop flashing display;
(When the system is faulty, the compressor is forbidden to start.)
0 7 Outdoor unit LEVa1 open degree Press ENTER (SW7) for 3 seconds, 1111, enter the setting state: flashing, press UP (SW4) valve fully open, press DOWN (SW5) the valve is fully closed; press DOWN (SW5) once, opening will decrease 1 level.
Press EXIT (SW6) for 3s continuously, display 0000, then quit the setting condition, and stop flashing.
B 0 Outdoor unit solenoid valve output LD2: 4WV : 1 ON 0 OFF
LD3: SV1 : 1 ON 0 OFF
LD4: SV2 : 1 ON 0 OFF
Outdoor unit address 0-3 C 0 High voltage switch input LD2: HPS 1 ON 0 OFF
LD3: LPS 1 ON 0 OFF
LD4: reserved, display “-“
E 0 Heater output LD2: CH1: 1 ON 0 OFF
LD3: BH: 1 ON 0 OFF
LD4: Reserved, Display “-“
F 0 Program version 1 means Ver1.0

What pressure and temperature parameters can be viewed for the outdoor unit?

Using LD2-LD4 display:

SW1 SW2 SW3 Function Digital tube LD2 ~ 4 display
0 0 1 Pd Unit: kg, 2 decimal
0 2 1 Ps Unit: kg, 2 decimal
0 3 1 Td Unit: °C
0 5 1 Tdef
0 9 1 Tc
0 1E 1 Ts

Using LD1-LD4 display:

SW1 SW2 SW3 Function Digital tube LD1 ~ 4 display
0 1 15 (F) Tao Unit: °C
0 2 15 (F) Pd_temp
0 4 15 (F) Ps_temp
0 8 15 (F) Inverter compressor INV1 ON/OFF time Unit: Min
0 10 (A) 15 (F) Inverter compressor INV1 current Tm Unit: A, 1 decimal
0 11 (B) 15 (F) Unit current input Unit: A, 1 decimal
0 12 (C) 15 (F) Inverter compressor INV1 DC voltage Unit: V
0 13 (E) 15 (F) Inverter compressor INV1 temperature Unit: °C

How can I view the system status on the master unit display?

SW1 SW2 SW3 Function Digital tube LD1 ~ 4 display
0 0 2 Refrigerant type 410A means 410A refrigerant
0 1 2 The outdoor units total capacity in one system Total outdoor unit capacity (unit: HP)
For example: 5.0 means total capacity is 5HP
0 2 2 Total indoor unit capacity 50 means 50HP
0 3 2 The indoor units quantity in one system For example: 64
0 4 2 Running indoor QTY Thermostat ON indicates indoor running
0 5 2 Indoor QTY whose operation modes are as the same as that of outdoor E.g.: 13 indoors
0 6 2 Cooling /Heating target temperature Unit: °C
0 7 2 Actual average Tc2 temperature

How do I perform automatic refrigerant recovery?

Set SW1=0, SW2=8, SW3=2.

Press ENTER (SW7) for 3 seconds, into refrigerant recovery, digital tube display “C0” and “low pressure data” alternately flashing, indicate enter the refrigerant recovery operation.

Forced cooling mode, all indoor units open. Do not judge superheat, oil temperature conditions.

After 3 mins, Digital tube shows “C1” and “low pressure data” flashing alternately, indicate manual close the liquid pipe stop valve.

When Ps ≤ 1 kg (0.1MPa), Digital Display C2″, indicate manual close the gas pipe stop valve.

After 5s, the system stops automatically, Digital Display C3″, Power off.

Note: after recovery must cancel the setting or re-power on.


How do I force the indoor unit expansion valve fully open or cancel the forced control?

Set SW1=0, SW2=12(C), SW3=2.

Press ENTER (SW7) for 3 seconds, display 1111, indoor valve fully open.

Press EXIT (SW6) for 3 seconds, display —-, cancel the forced control of the indoor unit expansion valve.


How do I force all indoor units into cooling or heating mode, or cancel manual control?

• All the indoor unit in cooling (SW1=0, SW2=13(D), SW3=2): Press ENTER (SW7) for 3 seconds, display 1111, open; Press EXIT (SW6) for 3 seconds, —-, close.

• All the indoor unit in heating (SW1=0, SW2=14(E), SW3=2): Press ENTER (SW7) for 3 seconds, display 1111, open; Press EXIT (SW6) for 3 seconds, —-, close.

• Cancel all manual control (running class) (SW1=0, SW2=15(F), SW3=2): Press ENTER (SW7) for 3 seconds, display 1111 cancel; or press EXIT (SW6) for 3 seconds, display 0000, cancel. Remove all manual control (part), all indoor unit close.


How do I display and set E2 control parameters?

Each need to be set separately, setting method:

(1) Press ENTER (SW7) for 3 seconds, enter the setting state, flashing display the current value.

(2) Press UP (SW4) or DOWN (SW5) to adjust parameters.

(3) After the adjustment is completed:

A> In the current state of the code, press the ENTER (SW7) for 3 seconds within the effective setting time, save the current setting value and exit the setting state, stop the flicker display, wait for 5 seconds and then power up again.

B> In the current state of the code, not press ENTER (SW7) or change the dip switch selection, do not save the current set value, exit the setting state, stop flashing display.


What are the E2 control parameters available for setting?

Use SW1=15(F), SW3=2, and adjust SW2 to select the parameter. View/Set using LD1-4 display.

SW1 SW2 SW3 Function Digital tube LD1 ~ 4 display (Setting options)
15 (F) 0 2 Remark of indoor unit adjusting valve when heating standby 0-unavailable 1-available
1 2 Oil return mode select 0- long piping unavailable
1-long piping available
2 2 Area selection 0- American unavailable
1- American available
3 2 Start mode priority 0- first open is priority;
1- last open is priority
2- cooling priority;
3- heating priority
4 2 Capacity over match selection 1- forbidden
5 2 ECO and normal operation selection 0- ECO 1- Normal operation
6 2 Cooling only or heat pump selection 0- Cooling only
1-heat pump
7 2 New and old protocol selection 96-new protocol
24-old protocol
8 2 Fan mode selection 0-normal
1-Energy efficiency testing
2-High ESP
9 2 Modbus protocol selection 0-Modbus protocol
1-Central wired controller protocol
10 (A) 2 Expansion valve LEV fault shield selection 0- not shielded, normal detection
1- shielded
11 (B) 2 Snow-proof operation setting 0-without snow-proof operation,
1-snow-proof operation
12(C) 2 Power restrain operation control mode selection 0-unavailable 1-available
13(D) 2 ModeBus Fahrenheit unit selection 0-°C 1- °F
15 (F) 14(E) 2 Allow access to factory automation test mode mark (for factory testing) 0- forbidden
1- allow(default)
15 (F) 15(F) 2 Allow access to self-cleaning 0- forbidden
1- allow(default)

How do I manually control outdoor unit components or cancel manual controls?

Set SW1=6, SW2=15(F), SW3=2.

Operation methods:

• Press ENTER (SW7) for 3 seconds, display 1111, then to quit, or press EXIT (SW6) for 3 seconds, display 0000, then quit the set.

• Cancel items: Movable component control by hand such as compressor, motor, electronic expansion valve (LEV), solenoid valve (SV) and so on (including evacuation and charging; excluding rated operation, compulsory operation, indoor run/stop, etc.)


How can I examine the local EE data?

Use SW1, SW2, and SW3 to select the EE data address. Display with digital tube LD1~4.

• SW1=12(C): Addresses 000H-0FFH. Address calculation: addr=SW2*10H +SW3.

• SW1=13(D): Addresses 100H-1FFH. Location for 100H-13FH: addr=100H + SW2*10H +SW3. Addresses 140H-1FFH is fault information area.

• Data display: hexadecimal display, H represents hexadecimal number.


How does the compressor start up?

After receiving the outdoor startup instruction, outdoor open SV1 30 seconds and then standby. When startup, the compressor will keep for 3 min at 45rps (when Ta<40°C) or 3 min at 40rps (when Ta>=40°C).

• In cooling mode, meet running 1min & (Td-CT)≥20°C or Ps≤0.1MPa (or max. running time is 3min), quit the startup control;

• In heating mode, meet running 1min and & (Td-CT)≥20°C or Ps≤0.1MPa (or max. running time is 3min), quit the startup control;

• During startup, the high pressure protection, high exhaust protection and current protection is priority and the low exhaust up frequency protection is shielded.


How is the compressor output controlled?

Compressor Pd/Ps control, control the compressor frequency to output appropriate cooling/heating capacity.

The control at the end of the startup control.


How is the target Ps selected automatically in cooling mode based on ambient temperature?

According to the ambient temperature select target Ps automatically:

Mode Outdoor ambient temperature Target Ps Ps correction during running
Effect priority mode (default) Ta≤12°C Setting value – R°C During running: correct the Ps according to the compression ratio
12°C < Ta < 40°C 0 (set by dip switch)
Energy-saving mode Ta≤12°C Setting value – R°C
12°C < Ta < 40°C 2 (set by dip switch)
Both Modes Ta≥40°C Setting value +2°C

R value setting: Ta<-5°C, Target Ps: setting value -8°C.

-5°C ≤ Ta < 12°C, Target Ps is the slope value of setting value and (setting value -8°C).


How is the target Pd selected automatically in heating mode based on piping length and ambient temperature?

According to the piping length to select target Pd and also according to the ambient temperature select target Pd automatically:

Mode Outdoor ambient temperature Target Pd Pd correction during running
Effect priority mode (default) Ta≥15°C Setting value +3°C During running: correct the Pd according to the compression ratio
Ta≥7°C Setting value +2°C
Ta≥-5°C 48 (set by dip switch)
Ta<-5°C Setting value -2°C
Energy-saving mode Ta≥15°C Setting value +3°C
Ta≥7°C Setting value +2°C
Ta≥-5°C 46 (set by dip switch)
Ta<-5°C Setting value -2°C

When does the unit enter defrosting mode?

Entering condition (needs Ta≤20°C AND one of the OR conditions below):

• After heating startup 60min

• Last defrosting ~ heating cumulative operation time is more than 60 minutes

• A: Ta≥6°C, Te≤-10°C For 5min continuously

• B: -15≤Ta<6°C, Te≤(5Ta-72)/7 For 5min continuously

• C: -23≤Ta<-15°C, Te≤(Ta-69)/4 For 5min continuously

• D: Tao<-23°C, Te≤-23°C For 5min continuously

• X: During the oil return operation meets the following condition, the cumulative operation time reset:

OR Outdoor Te≥10°C, for 1min continuously

OR Outdoor Te≥15°C, for 10min continuously


What happens during defrosting?

During defrosting, four-way valve power off, outdoor fan stop, indoor fan stop, outdoor PMV open to 470pls.


When does the unit exit defrosting mode?

Quit defrosting condition (OR):

• After defrosting operation 10min

• OR Outdoor Te≥15°C, for 1min continuously

• OR Outdoor Te≥20°C, for 30s continuously

• OR Outdoor Te≥30°C, for 5s continuously

• OR Tc ≥ 54°C


When does oil return control start in cooling mode?

Entering condition:

A: In cooling mode

• The master unit compressor cumulative operation time:

OR When load rate < 20%: after 2 hours

OR When load rate ≥ 20%: after 4 hours

• AND After the outdoor unit startup:

AND Load rate ≤ 30%

OR (Load rate > 30% AND Finish the outdoor startup control ~ after 20min)

Note: load rate = Σindoor HP(Thermo ON) / Σindoor HP * 100%


When does oil return control start in heating mode?

Entering condition:

B: In heating mode

• The master unit compressor cumulative operation time:

OR When load rate < 25%: after 1 hours, 4-way valve doesn't reversing oil return operation

OR 25% ≤ load rate < 50%: after 2 hours, 4-way valve doesn't reversing oil return operation

OR 50% ≤ load rate < 75%: after 4 hours, 4-way valve doesn't reversing oil return operation

• AND After the outdoor unit startup:

AND Load rate ≤ 30%

OR (Load rate > 30% AND Finish the outdoor unit startup control ~ after 20min AND Finish defrosting ~ after 30min)

Note: if load rate ≥ 75% and the outdoor unit output rate ≥ 75% for 10 min, oil return time reset.


How is oil return controlled?

1) Oil return in cooling mode, the compressor according to the 75% of maximum frequency control, the outdoor PMV opening angle is 470 pls, the Thermo ON indoor PMV opening angle is 250 pls, the Thermo OFF indoor PMV opening angle is 125 pls.

2) Oil return in heating mode (4-way valve reversing), the compressor according to the 75% of maximum frequency control, the outdoor PMV opening angle is 470 pls, the Thermo ON and Thermo OFF indoor PMV opening angle is 125 pls. When Td > 95 °C and TdSH > 15 °C, the indoor PMV opening angle increased 10%, max. time is 2; When Td < 90 °C, return to the usually opening.

3) Oil return in heating mode (4-way valve doesn’t reversing), the compressor according to the indoor units load rate and current running frequency to confirm the oil return enter frequency, the maximum frequency can’t exceed 75% of the maximum frequency. the PMV of the outdoor and the Thermo ON indoor unit control automatically, Thermo OFF indoor PMV opening angle is 250 pls.


When does oil return stop (quit condition)?

1) In cooling mode:

• OR After 5min

• OR (After 1min AND (Td < CT + 10°C, for 10s continuously OR Ts - ET < 15°C, for 10s continuously))

2) In heating mode (4-way valve reversing):

• OR After 5min

• OR (After 2min AND (Td < CT + 10°C, for 10s continuously OR Ts - ET < 15°C, for 10s continuously))

3) In heating mode (4-way valve doesn’t reversing):

• OR After 5min

• OR Td ≥ 105°C, for 5s continuously


What are the common failure codes displayed on the outdoor unit’s digital tube and their meanings?

Inverter outdoor unit failure code:

Digital tube indication on master unit Indication on wired controller (hex) Failure code definition Failure description Remarks
20-0 14 Defrosting temp. sensor (Te) failure Continuous disconnect for 60 seconds or short circuit, failure alarm Resumable
21 15 Ambient temp. sensor (Ta) failure Continuous disconnect for 60 seconds or short circuit, failure alarm Resumable
22 16 Suction temp. sensor Ts failure AD value is below 11(open circuit) or over 1012(short circuit) for 60seconds, in defrosting and within 3 minutes after defrosting, no alarm Resumable
23 17 Discharging temp. sensor Td failure After compressor is running for 5 minutes, AD value is below 11(open circuit) or over 1012(short circuit) for 60seconds, in course of startup, defrosting and within 3 minutes after defrosting, no alarm Resumable
26-0 1A Communication failure with indoor units No indoor units connection can be detected for continuous 200 seconds.
26-1 1A Number of indoor units less than connected indoor units It was detected that the number of indoor units was less than the set number for 300 seconds. Resumable
26-2 1A Number of indoor units more than connected indoor units It was detected that the number of indoor units was more than the set number for 300 seconds.
28 1C Discharge pressure sensor (Pd) failure Continuous disconnect for 60 seconds or short circuit, failure alarm. Resumable
29 1D Suction pressure sensor (Ps) failure Continuous disconnect for 60 seconds or short circuit, failure alarm. Resumable
30 1E High pressure switch (HPS) failure When the high pressure switch is disconnected, failure alarm. When the high pressure switch is closed, failure removed. Failure is locked if it occurs 3 times in one hour. Once failure locked, un-resumable.
33 21 EEPROM failure Outdoor unit EEPROM failure Un-resumable
34 22 Discharge temp. too high (Td) Td≥[115]°C, failure alarm; Td≤[85]°C, failure removed. Failure is locked if it occurs 3 times in one hour. Once failure locked, un-resumable
35 23 4-way valve revering failure After the compressor starts, it runs continuously for 10 minutes, if the 4-way valve does not reverse, failure alarm. The failure will be removed after 3 minutes. Failure is locked if it occurs 3 times in one hour. Once failure locked, un-resumable
39-0 27 Suction pressure (Ps) too low (1) Cooling: Ps≤0.05 MPa or Ps≤0.1MPa for 5 consecutive minutes, failure alarm. Ps≥0.25MPa, failure removed.
(2) Heating: Ps≤0.03Mpa or Ps≤0.05MPa for 5 consecutive minutes, failure alarm. Ps≥0.2MPa, failure removed.
Failure is locked if it occurs 3 times in one hour.
Once confirmation, un-resumable
39-1 27 Compression ratio (ε)too high Compression ratio (ε) ≥12.0 for 5 consecutive minutes, failure alarm. The failure will be removed after 3 minutes. Failure is locked if it occurs 4 times in 2 hours. Once failure locked, un-resumable.
40 28 Discharge pressure (Pd) too high Pd≥4.15MPa or Pd≥3.9MPa for 5 consecutive minutes, failure alarm. Pd ≤3.3MPa, failure removed. Failure is locked if it occurs 3 times in one hour. Once failure locked, un-resumable.
43 2B Discharge temp. too low protection(Td) TdSH ≤ 10°C for 5 consecutive minutes, failure alarm. After the oil temperature is satisfied, the failure will be removed. Failure is locked if it occurs 3 times in one hour. Once failure locked, un-resumable.
46 2E Communication failure with inverter module No module board signal is received within 30 seconds or data error. It will be automatically restored after receiving correctly. Resumable
51-0 33 LEVa over current LEV driver chip detection Resumable
51-2 33 LEVb over current Resumable
52-0 34 LEVa circuit open failure Resumable
52-2 34 LEVb circuit open failure Resumable
53 35 CT current too low or current sensor failure 1. When the compressor runs continuously for 1 minute, the compressor frequency ≥50 Hz for 5 minutes. If the current sensor sampling value is less than 10, failure alarm. The failure will be removed after 3 minutes.
2. When the compressor stops, the failure will alarm if CT > 6A lasts for 3min. The failure will be removed after 3 minutes.
Resumable
58 3A Sub-cooling temp. sensor Tsco temp. sensor failure Continuous disconnect for 60 seconds or short circuit, failure alarm. Resumable
59 3B Sub-cooling temp. sensor Tliqsc temp. sensor failure Resumable
64 40 CT value too high When the CT current exceeds the specified value for 5 consecutive seconds, failure alarm. The failure will be removed after 3 minutes. Failure is locked if it occurs 3 times in one hour. Once failure locked, un-resumable.
71-0 47 Upper DC Fan failure The failure will alarm when it runs below 20 rpm for 40 seconds or below 20% of the target value for 2 minutes. The failure will be removed after 3 minutes. Failure is locked if it occurs 3 times in one hour. Once failure locked, un-resumable.
71-1 47 Lower DC Fan2 failure
78 4E Lack of refrigerant 1.Cooling: Ps≤0.2MPa for 30 consecutive minutes, failure alarm. Ps≥0.3MPa for 30 consecutive minutes, failure removed.
2.Heating: Both LEVa equals to 470pls and Ts-Ps≥20°C for 60 consecutive minutes, failure alarm. Ps≥0.2MPa for 30 consecutive minutes, failure removed.
Resumable
81 51 Inverter module temp. too high Inverter temp.≥90°C, failure alarm. Inverter temp. ≤70°C, failure removed. Failure is locked if it occurs 3 times in one hour. Once failure locked, un-resumable.
82 52 Compressor over current protection When the compressor current exceeds the specified value for 5 consecutive seconds, failure alarm. The failure will be removed after 3 minutes. Failure is locked if it occurs 3 times in one hour. Once failure locked, un-resumable.
83 53 Model setting error Model setting does not match the outdoor unit. Once failure locked, un-resumable.
110 6E The inverter module over current (hardware) Module hardware over current. Failure is locked if it occurs 3 times in one hour.
Instantaneous over current of hardware at rectifier side of inverter module. Failure is locked if it occurs 3 times in one hour.
Once failure locked, un-resumable.
111 6F Compressor out of control During start-up or operation, the rotor position cannot be detected for 6 consecutive times, failure alarm. The inverter module will be automatic recovery after compressor stops for 5 seconds. Resumable
112 70 The temp. of the inverter module radiator is too high The temp. of the inverter module radiator ≥94°C, failure alarm. The temp. of the module radiator < 94°C, the inverter module will be automatic recovery. Resumable
114 72 The inverter input power voltage is abnormal The voltage > DC642V, failure alarm.
The voltage < DC642V, the inverter module will be automatic recovery.
OR
The voltage < DC420V, failure alarm.
The voltage > DC420V, the inverter PCB will be automatic recovery.
OR
The power supply of inverter module is interrupted instantaneously.
Resumable
116 74 Abnormal communication between the inverter module and the control PCB If no communication signal is detected for 30 seconds, failure alarm. After detection, inverter module will recover immediately. Resumable
117 75 The inverter module over current (software) Module rectifier side software instantaneous overcurrent Resumable
Inverter Module overload Resumable
Module software over current Resumable
118 76 Compressor startup failed The compressor failed to start continuously for 5 times. Resumable
119 77 Current detection circuit failure The module rectifier side current detection circuit is abnormal. Resumable
The sensor used for current detection of inverter controller is abnormal, disconnected or connected incorrectly. Resumable
121 79 Power supply of inverter module board is abnormal Power supply of inverter board is broken down instantly. Resumable
122 7A The temp. sensor of inverter module is abnormal. The resistance of inverter temperature sensor is abnormal or not connected. Resumable
124 7C Inverter module power supply failure inverter power supply failure Resumable

What do the standby codes displayed on the outdoor unit mean when there is no failure?

In case of no failure, if the starting conditions of the system are not met, the digital tube of the outdoor unit will display the standby code of the air conditioner:

Code Meaning Condition
555.0 Standby state of capacity over-matched The ratio of indoor capacity to outdoor capacity is over 130%.
555.1 Heating at high ambient temp. Ta>27°C, the indoor units standby when they are running in heatling mode.
555.3 Cooling at ambient temp. too high or too low Ta>54°C or Ta<-10°C, the indoor units standby when they are running in cooling mode.
555.b The running mode of outdoor unit does not match with the indoor units. The outdoor unit maybe setted to cooling only or heating only.

How do I troubleshoot Temperature Sensor Failure (Codes 20-24)?

Follow these steps:

1. Check if the sensor terminal is fixed well. If No, reconnect the terminal. If Yes, proceed to step 2.

2. Check if the sensor resistor/characteristic is proper. If No, replace the sensor. If Yes, proceed to step 3.

3. Check if the PCB is faulty. If Yes, replace the PCB.


How do I troubleshoot High/Low Pressure Sensor Failure (Codes 28, 29)?

Follow these steps:

1. Check if the sensor terminal is fixed well. If No, reconnect the terminal. If Yes, proceed to step 2.

2. Test the voltage between the red terminal and black terminal using a multimeter. Is it 5V? If No, replace the PCB. If Yes, proceed to step 3.

3. Test the voltage between the white terminal and black terminal using a multimeter. Is it between 0.5V and 3.5V? If Yes, replace the pressure sensor. If No, proceed to step 4.

4. Replace the connecting board.


How do I troubleshoot Communication Circuit Failure between Indoor and Outdoor (Codes 26-0, 26-1, 26-2)?

Follow these steps:

1. Check if the wiring between P and Q is wrong or broken down. If Yes, modify the communication wire. If No, proceed to step 2.

2. Check if the wire of CN29 on the outdoor connecting board is normal. If No, modify the port. If Yes, proceed to step 3.

3. Check if the wire of CN15 on the outdoor connecting board is normal. If No, check/fix CN15 wiring. If Yes, proceed to step 4.

4. Check if indoor and outdoor units are electrified at the same time. If No, ensure simultaneous power connection. If Yes, proceed to step 5.

5. Check if the communication wire is separate from high-voltage wire on the layout. If No, change the communication wiring type/route. If Yes, proceed to step 6.

6. Check if the indoor quantity is correct (check by rotary switch). If No, proceed to step 7. If Yes, shut off power supply, and the outdoor unit searches for indoors again.

7. Check if there is a noise source. If Yes, eliminate the noise source. If No, proceed to step 8.

8. Check if the failure disappears after changing the indoor PCB. If No, proceed to step 9.

9. Check the outdoor PCB. If faulty, replace it.


How do I troubleshoot Outdoor EEPROM Failure (Code 33)?

Follow these steps:

1. Check if the EEPROM is fixed well. If No, reconnect it. If Yes, proceed to step 2.

2. Replace the EEPROM.


How do I troubleshoot 4-Way Valve Reversing Failure (Code 35)?

Follow these steps:

1. Check if the connection between the 4-way valve and the connecting board is good. If No, re-connect. If Yes, proceed to step 2.

2. Check if the system meets the condition for 4-way valve reversing (Pd-Ps > 0.6MPa). If No, check if SV1 leaks. If Yes, proceed to step 3.

3. Measure if the CN49 voltage on the connecting board is 220VAC after the 4-way valve reversing condition is met. If No, replace the connecting board. If Yes, proceed to step 4.

4. Check if the compressor running current is normal. If No, check the compressor. If Yes, proceed to step 5.

5. Check if there is air noise after the 4-way valve reverses, and if the temperature of connection pipes with the 4-way valve is normal. If No, proceed to step 6.

6. Replace the 4-way valve.


How do I troubleshoot High Pressure Switch Shutoff Failure (Code 30)?

Follow these steps:

1. Check if the connection between the pressure switch and connecting board is good. If No, re-connect. If Yes, proceed to step 2.

2. Check if the system pressure meets the condition that the pressure switch shuts off. If No, replace the pressure switch. If Yes, proceed to step 3.

3. Make the pressure switch close and measure if the terminal is conductive using a multimeter. If No, check switch/measurement. If Yes, proceed to step 4.

4. Check if the system is clogged. If Yes, check the piping system. If No, proceed to step 5.

5. Make the pressure switch terminal on the connecting board short circuit. Check if the failure still exists. If Yes, replace the connecting board. If No, proceed to step 6.

6. Replace the pressure switch and measure again.


How do I troubleshoot Protection of Discharging Temp. Too High (Code 34)?

Follow these steps:

1. Check if the sensor terminal is fixed well. If No, reconnect. If Yes, proceed to step 2.

2. Check if the sensor resistor/characteristic is proper. If No, replace the sensor. If Yes, proceed to step 3.

3. Check if the system is lacking refrigerant. If Yes, charge refrigerant. If No, proceed to step 4.

4. Replace the connecting board.


How do I troubleshoot Protection of Oil Temperature Too Low (Code 36)?

Follow these steps:

1. Check if the Toil sensor is fixed well and if its characteristic is correct. If No, fix or replace the sensor. If Yes, proceed to step 2.

2. Check if the terminal of LEVb is fixed well. If No, reconnect. If Yes, proceed to step 3.

3. In cooling mode, when the indoor unit is off, check if the EEV can completely close. If No, replace or adjust the indoor unit EEV. If Yes, proceed to step 4.

4. Check if refrigerant is too much. If Yes, recharge refrigerant (recover excess refrigerant).


How do I troubleshoot Low Pressure Too Low and Compression Ratio Too High (Codes 39-0, 39-1)?

Follow these steps:

1. Check if the actual pressure is in conformance with the measured data by the sensor. If No, replace the pressure sensor. If Yes, proceed to step 2.

2. Check if the stop valve is open fully. If No, open the stop valve. If Yes, proceed to step 3.

3. Check if the system is lacking refrigerant. If Yes, recharge refrigerant. If No, proceed to step 4.

4. Check if the terminal of the electronic expansion valve coil is fixed well. If No, re-connect the terminals. If Yes, proceed to step 5.

5. Check if the piping system is clogged. If Yes, clear the piping.


How do I troubleshoot Compression Ratio Too Low (Code 39-2)?

Follow these steps:

1. Check if the actual pressure is in conformance with the measured data by the sensor. If No, replace the pressure sensor. If Yes, proceed to step 2.

2. Check if the compressor running current is normal. If No, check the compressor. If Yes, proceed to step 3.

3. Check if the 4-way valve is interconnected correctly. If No or suspect an issue, replace the 4-way valve.


How do I troubleshoot High Pressure Protection (Code 40)?

Follow these steps:

1. Check if the characteristics of the high pressure sensors are normal. If No, replace the pressure sensor. If Yes, proceed to step 2.

2. Check if the stop valve opens fully. If No, open the stop valve. If Yes, proceed to step 3.

3. In cooling mode, check if the outdoor fan motor runs normally. If No, check the fan motor. If Yes, proceed to step 4.

4. In heating mode, check if the indoor fan motor runs normally and if the filter is clogged. If No (motor issue) or Yes (filter clogged), check the indoor unit (fan/filter). If Yes (motor normal) and No (filter not clogged), proceed to step 5.

5. Check if the piping system is clogged. If Yes, clear the piping.


How do I troubleshoot Discharging Temp. Sensor Td Too Low Protection (Code 43)?

Follow these steps:

1. Check if the sensor characteristic is correct. If No, replace the sensor. If Yes, proceed to step 2.

2. Check if the terminal of the sensor is fixed well. If No, reconnect. If Yes, proceed to step 3.

3. In cooling mode, when the indoor unit is off, check if the EEV can completely close. If No, replace or adjust the indoor unit EEV. If Yes, proceed to step 4.

4. Check if refrigerant is too much. If Yes, recharge refrigerant (recover excess refrigerant).


How do I troubleshoot Communication with Inverter Module Failure (Code 46)?

Follow these steps:

1. Check if the communication wire between the connecting board and module is connected normally. If No, re-connect. If Yes, proceed to step 2.

2. In cooling mode, when the indoor unit is off, check if the EEV can completely close. If No, check/replace/adjust EEV. If Yes, proceed to step 3.

3. Measure if the voltage of CN28 on the connecting board changes using a multimeter. If No, replace the connecting board. If Yes, proceed to step 4.

4. Replace the module.


How do I troubleshoot Low Pressure Switch Failure (Code 49)?

Follow these steps:

1. Check if the connection between the pressure switch and the connecting board is good. If No, re-connect. If Yes, proceed to step 2.

2. Check if the system pressure meets the condition that the pressure switch shuts off. If Yes and the system lacks refrigerant, recharge the refrigerant. If No or refrigerant level is OK, proceed to step 3.

3. Make the pressure switch terminal on the connecting board short circuit. Check if the failure still exists. If Yes, replace the connecting board. If No, proceed to step 4.

4. Replace the pressure switch.


How do I troubleshoot Current Sensor Failure (Code 53)?

Follow these steps:

1. Check if the connection between the connecting board and the CT board is connected well (CN9). If No, re-connect. If Yes, proceed to step 2.

2. Check if the CT wire is conductive. If No, replace the wire. If Yes, proceed to step 3.

3. Check if it is normal after replacing the CT board. If No, replace the connecting board. If Yes, the CT board was the issue.


How do I troubleshoot CT Over Current (Code 64)?

Follow these steps:

1. Check if the wire between the connecting board and module is connected normally. If No, re-connect. If Yes, proceed to step 2.

2. Check if the CT wire is conductive. If No, replace the wire. If Yes, proceed to step 3.

3. Check if the temperature on top of the fixed frequency compressor is too high. If Yes, proceed to step 5. If No, proceed to step 4.

4. Check if the AC contactor works. If No, check contactor. If Yes, check if the system is normal after replacing the CT detector. If Yes, problem solved. If No, replace the PCB.

5. Check if there is air in the system. If Yes, recharge refrigerant (evacuate and recharge). If No, proceed to step 6.

6. Check if the motor is clogged or bad. If Yes, fix the system (motor). If No, proceed to step 7.

7. Replace the compressor.


How do I troubleshoot DC Motor Blocked (Code 71-0, 71-1)?

Follow these steps:

1. Rotate the fan motor by hand to check if there is obvious friction. If Yes, replace the fan motor. If No, proceed to step 2.

2. Check if the motor and PCB connection is well. If No, re-connect. If Yes, proceed to step 3.

3. Force the fan in low speed and measure if it has alternating voltage between FG and GND. If No, replace the motor. If Yes, proceed to step 4.

4. Replace the outdoor PCB.


How do I troubleshoot No Pressure Drop Between High and Low Pressure (Code 75)?

Follow these steps:

1. Check if the high/low pressure sensor is connected well. If No, re-connect. If Yes, proceed to step 2.

2. Check if the compressor wire is connected normally. If No, correct the compressor wire. If Yes, proceed to step 3.

3. Check if the wires of the inverter compressor are connected oppositely. If Yes, correct the compressor wire. If No, proceed to step 4.

4. Check if the 4-way valve is interconnected correctly. If No or suspect an issue, replace the 4-way valve. If Yes, proceed to step 5.

5. Measure if there is voltage U, V, W of the compressor using a multimeter, and if it is normal. If No, replace the inverter module. If Yes, proceed to step 6.

6. Replace the inverter compressor.


How do I troubleshoot Compressor Current Protection / Transient Over Current issues (Codes 82, 108, 109, 123)?

Follow these steps:

1. Check if the wires of the compressor connect well. If No, reconnect or change the wires. If Yes, proceed to step 2.

2. Measure the compressor winding with a milliohm meter. Check if the compressor resistance is balanced. If No, change the compressor. If Yes, proceed to step 3.

3. Check if the high/low pressure is normal. If No (abnormal), investigate the pressure issue. If Yes, proceed to step 4.

4. Change the module.


How do I troubleshoot Power Module Overcurrent (Code 110)?

Follow these steps:

1. Check if the voltage of the power supply is normal. If No, improve the power supply circuit. If Yes, proceed to step 2.

2. Check if the wire of the electric box is correct, and if the compressor wire is fixed well. If No, correct the wiring according to the diagram. If Yes, proceed to step 3.

3. Check if the power module is normal. If No, replace the power module. If Yes, proceed to step 4.

4. Check if the compressor is normal (compressor coil resistor, insulation). If No, replace the compressor. If Yes, proceed to step 5.

5. Check if there are other failures recently, such as 112, 113, 114. If Yes, solve the failures due to relative information. If No, remove the failure (this might resolve the issue or indicate it was transient).


How do I troubleshoot Compressor Out of Control (Code 111)?

Follow these steps:

1. Check if the voltage of the power supply is normal. If No, improve the power supply circuit. If Yes, proceed to step 2.

2. Check if the wires among U, V, W of the compressor are normal. If No, replace the wires. If Yes, proceed to step 3.

3. Check if the compressor is normal (compressor coil resistor, insulation). If No, replace the compressor. If Yes, proceed to step 4.

4. Compressor load too much, check the reason.


How do I troubleshoot IPM Modular Temp Too High / Radiator Temp Too High (Codes 81, 112)?

Follow these steps:

1. Check if the temperature sensor characteristic is correct. If No, replace the sensor. If Yes, proceed to step 2.

2. Check if the radiator is blocked. If Yes, clean the radiator. If No, proceed to step 3.

3. Check if the screw of the module is fixed well, and if radiating silica gel is daubed enough and evenly, if there is no dirt on the radiator. If No to any condition, fix it well and daub gel again, clean the radiator. If Yes to all conditions, proceed to step 4.

4. Improve the running environment of the outdoor unit.


How do I troubleshoot Protection of Overload (Code 113)?

Follow these steps:

1. Check if the voltage of the power supply is normal. If No, improve the power supply circuit. If Yes, proceed to step 2.

2. Check if the wire of the electric box is correct. If No, correct the wiring according to the diagram. If Yes, proceed to step 3.

3. Check if the compressor is normal (compressor coil resistor, insulation). If No, replace the compressor. If Yes, proceed to step 4.

4. Check if the power module is normal. If No, replace the power module. If Yes, proceed to step 5.

5. Compressor load too much, check the reason.


How do I troubleshoot Voltage Too Low of DC Bus Line (Code 114)?

Follow these steps:

1. Check if the voltage of the power supply is normal. If No, improve the power supply circuit. If Yes, proceed to step 2.

2. Check if the wire of the electric box is correct. If No, correct the wiring according to the diagram. If Yes, proceed to step 3.

3. Check if the AC contactor or relay acts well. If No, adjust or replace the relay. If Yes, proceed to step 4.

4. Measure if the DC bus line voltage between P and N of the module is less than 375V. If No, the circuit of the DC bus line voltage on the inverter control board is abnormal, replace the inverter control board. If Yes, proceed to step 5.

5. Check the rectifier, reactor, electrolytic capacitor in the inverter main circuit.


How do I troubleshoot Voltage Too High of DC Bus Line (Code 115)?

Follow these steps:

1. Check if the voltage of the power supply is normal. If No, improve the power supply circuit. If Yes, proceed to step 2.

2. Check if the wire of the electric box is correct. If No, correct the wiring due to diagram. If Yes, proceed to step 3.

3. Measure if the DC bus line voltage between P and N of the module is over 644V. If No, the circuit of the DC bus line voltage on the inverter control board is abnormal, replace the inverter control board. If Yes, proceed to step 4.

4. Check the rectifier, reactor, electrolytic capacitor in the inverter main circuit.


How do I troubleshoot Communication Abnormal Between Transducer (Inverter Board) and Control PCB (Code 116)?

Follow these steps:

1. Check if the wire between the control PCB and inverter board is abnormal. If Yes, adjust the communication wire. If No, proceed to step 2.

2. Check if the communication circuit of the main control PCB is abnormal (if signal LED flashes abnormally). If Yes, replace the main control board. If No, proceed to step 3.

3. Check if the inverter module board is abnormal. If Yes, the detecting circuit on the inverter board is broken down, replace the inverter module board. If No, proceed to step 4.

4. Solve the failures due to relative information.


How do I troubleshoot Transducer Over Current (Software Protection) (Code 117)?

Follow these steps:

1. Check if the voltage of the power supply is normal. If No, improve the power supply circuit. If Yes, proceed to step 2.

2. Check if the wire of the electric box is correct. If No, correct the wiring due to diagram. If Yes, proceed to step 3.

3. Check if the compressor is normal (compressor coil resistor, insulation). If No, replace the compressor. If Yes, proceed to step 4.

4. Check if the power module is normal. If No, replace the power module. If Yes, proceed to step 5.

5. Compressor load too much, check the reason.


How do I troubleshoot Compressor Startup Failure (Code 118)?

Follow these steps:

1. Check if the voltage of the power supply is normal. If No, improve the power supply circuit. If Yes, proceed to step 2.

2. Check if the power module is normal. If No, replace the power module. If Yes, proceed to step 3.

3. Check if the compressor is normal (compressor coil resistor, insulation). If No, replace the compressor. If Yes, proceed to step 4.

4. Compressor load too much check the reason.


How do I troubleshoot Current Detecting Circuit Abnormal of Transducer (Code 119)?

Follow these steps:

1. Check if the wire between DCCT and control board, wire between IPM and compressor are correct; check if the wiring direction of DCCT is normal. If No, correct the wiring according to the diagram. If Yes, proceed to step 2.

2. Check if the current sensor is normal. If No, replace the current sensor. If Yes, proceed to step 3.

3. Replace the inverter PCB.


How do I troubleshoot Radiator Temp. Sensor of Transducer Abnormal (Code 122)?

Follow these steps:

1. Check if the connection between the temp. sensor and inverter board is correct. If No, adjust the connection. If Yes, proceed to step 2.

2. Measure if the temp. sensor resistor is normal. If No, replace the sensor. If Yes, proceed to step 3.

3. Replace the inverter control board.


How do I troubleshoot Power Supply of Transducer Abnormal (Code 120)?

Follow these steps:

1. Check if the voltage of the power supply is normal. If No, improve the power supply circuit. If Yes, proceed to step 2.

2. Check if the wire of the electric box is correct. If No, correct the wiring due to diagram. If Yes, proceed to step 3.

3. Check if the relay or AC contactor acts well. If No, adjust or replace the relay or AC contactor. If Yes, proceed to step 4.

4. Measure if the DC bus line voltage between P and N on the module is less than 140V. If No, the DC bus line voltage circuit on the inverter board is broken down, replace the inverter module board. If Yes, proceed to step 5.

5. Check the rectifier, reactor, electrolytic capacitor in the inverter main circuit.


How do I troubleshoot Power Supply of Inverter Board is Abnormal (Code 121)?

Follow these steps:

1. Check if the voltage of the power supply on the inverter control board is normal. If No, improve the power supply circuit. If Yes, proceed to step 2.

2. Check if the wire between the control PCB and inverter board is abnormal. If Yes, adjust the communication wire. If No, proceed to step 3.

3. Check if the circuit of the inverter control board is abnormal. If Yes, replace the power module (or inverter control board based on context). If No, proceed to step 4.

4. Solve the failures due to relative information.


What are the sensor characteristics?

Temp. sensor characteristic:

No. Sensor type Characteristic
1 Indoor coil/outdoor suction/oil temp./defrost/ambient temp. sensor R (25°C)=10ΚΩ Β (25°C/50°C)=3700K
2 Wired controller ambient temp./indoor ambient temp. sensor R (25°C)=23ΚΩ Β (25°C/50°C)=4200K
3 Outdoor discharging temp. sensor R (80°C)=50ΚΩ Β (25°C/80°C)=4450K

Typical resistor values for Sensor Type 1 (R25=10ΚΩ±3%, B25/50=3700K±3%):

Temp (°C) Rmax (KΩ) R(t) Normal (KΩ) Rmin (KΩ) MAX (+) % MIN (-) %
-30145.82135.02124.227.007.00
-25113.93106.8499.756.646.64
-2088.2082.9977.796.276.27
-1567.8064.0260.235.915.91
-1052.1549.4146.675.555.55
-540.3338.3536.365.185.18
031.4530.0028.564.824.82
524.7423.6922.634.454.45
1019.6518.8718.104.094.09
1515.7315.1714.603.733.73
2012.6912.2811.863.363.36
2510.3010.009.703.003.00
308.468.197.923.313.31
356.986.736.493.633.63
405.785.565.343.943.94
454.804.604.414.254.25
504.003.833.654.564.56

Typical resistor values for Sensor Type 2 (R25=23ΚΩ±3%, B25/50=4200K±3%):

Temp (°C) Rmax (KΩ) R(t) Normal (KΩ) Rmin (KΩ) MAX (+) % MIN (-) %
-30538.77513.12487.465.005.00
-25384.09366.75349.414.734.73
-20278.79266.91255.024.454.45
-15204.83196.61188.394.184.18
-10151.87146.15140.443.913.91
-5113.49109.51105.533.643.64
085.4782.6979.913.363.36
564.8962.9461.003.093.09
1049.6848.3146.952.822.82
1538.3637.4136.452.552.55
2029.8729.2128.552.272.27
2523.4623.0022.542.002.00
3018.6618.2517.852.222.22
3514.9414.5914.232.442.44
4012.0511.7411.422.662.66
459.779.509.222.882.88
507.977.737.493.093.09

Typical resistor values for Sensor Type 3 (R80=50ΚΩ±3%, B25/80=4450K±3%):

Temp (°C) Rmax (KΩ) R(t) Normal (KΩ) Rmin (KΩ) MAX (+) % MIN (-) %
01749.011921.992094.979.009.00
101007.851098.471189.108.258.25
20605.19654.25703.327.507.50
30374.89402.03429.176.756.75
40238.33253.54268.756.006.00
50155.09163.68172.285.255.25
60103.16108.02112.884.504.50
7070.0572.7875.513.753.75
8048.5050.0051.503.003.00
9033.6834.9636.243.673.67
10023.7624.8425.914.334.33
11017.0117.9018.805.005.00
12012.3413.0813.825.675.67
1309.099.7010.326.336.33
1406.827.337.857.007.00

CLICK HERE TO DOWNLOAD AIRWELL VVFA-335R-01T32 (01) PDF MANUAL


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.