What are the specifications for the TOSHIBA MMD-AP0306BHP-TR?

The specifications for the TOSHIBA MMD-AP0306BHP-TR are as follows:

50Hz Operation:

Cooling/Heating capacity (kW)9.0/10.0
Power supply1phase 50Hz 230V(220V-240V)
Running current (A)0.61
Power consumption (kW)0.094
Starting current (A)1.06
Height (mm)275
Width (mm)1000
Depth (mm)750
Total weight (kg)30
Fan unitCentrifugal fan
Standard air flow (m³/h) (Med./Low)1,260 (1110/930)
Motor output (W)150
External static pressure (Pa) (factory setting)40
External static pressure (Pa)30-40-50-65-80-100-120 (7steps)
Gas side pipe (mm)15.9
Liquid side pipe (mm)9.5
Sound pressure level (dB(A)) (High/Med./Low)36/31/27

60Hz Operation:

Cooling/Heating capacity (kW)9.0/10.0
Power supply1phase 60Hz 220V
Running current (A)0.64
Power consumption (kW)0.094
Starting current (A)1.11
Height (mm)275
Width (mm)1000
Depth (mm)750
Total weight (kg)30
Fan unitCentrifugal fan
Standard air flow (m³/h) (Med./Low)1,260 (1110/930)
Motor output (W)150
External static pressure (Pa) (factory setting)40
External static pressure (Pa)30-40-50-65-80-100-120 (7steps)
Gas side pipe (mm)15.9
Liquid side pipe (mm)9.5
Sound pressure level (dB(A)) (High/Med./Low)36/31/27

What are the parts ratings for the TOSHIBA MMD-AP0306BHP-TR?

The parts ratings for the TOSHIBA MMD-AP0306BHP-TR are as follows:

Fan motor340W150-1
Drain pump motorMDP-1401
Float switchFS-0218-102
Pulse motorEFM-MD12TF-1
Pulse motor valveEDM-B40YGTF-3
TA sensorLead wire length: 328 mm
TC1 sensorØ4 size lead wire length: 1200 mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length: 1200 mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length: 1200 mm Vinyl tube (Red)

What happens when the TOSHIBA MMD-AP0306BHP-TR is reset from a power supply?

When the power supply to your TOSHIBA MMD-AP0306BHP-TR is reset, the following occurs:

1. Identification of outdoor unit: The outdoor unit is identified, and control is redirected according to the identification result.

2. Indoor fan speed and air flow direction control availability settings: Settings such as indoor fan speed and air flow direction control availability are replaced on the basis of EEPROM data.

3. Fault code clearing: If the power supply reset is performed in the wake of a fault, the check code is cleared. If the abnormality persists after the Start / Stop button on the remote controller is pressed to resume operation, the check code is redisplayed on the remote controller.


How is the room temperature controlled on the TOSHIBA MMD-AP0306BHP-TR?

The room temperature control for the TOSHIBA MMD-AP0306BHP-TR has the following settings:

1. Adjustment range – remote controller temperature setting (°C):

COOL / DRY HEAT
Wired type 18~29 18~29
Wireless type 18~30 16~30

2. Fine-tuning in heating operation: The temperature setting may be fine-tuned via the DN code “06”.

SET DATA 0 2 4 6
Temperature setting adjustment +0 °C +2 °C +4 °C +6 °C

How does the fan speed control work on the TOSHIBA MMD-AP0306BHP-TR?

The fan on your TOSHIBA MMD-AP0306BHP-TR operates in one of four speed modes: “HIGH (HH)”, “MED (H)”, “LOW (L)”, and “AUTO”, based on the command from the remote controller. In AUTO fan speed mode, the air speed changes according to the difference between the ambient temperature (Ta) and the set temperature (Ts).

Cooling Operation in AUTO mode:

• The fan speed changes based on the temperature difference (Ta – Ts).

• In AUTO fan speed mode, the fan speed remains the same for 3 minutes each time a speed change occurs. However, a manual speed change command from the remote controller will override this.

• At the beginning of cooling, a higher speed is chosen for a steeper downward temperature gradient.

• As long as the temperature difference remains on a boundary line, the fan speed stays the same.

Heating Operation in AUTO mode:

• The fan speed changes based on the temperature difference (Ta – Ts).

• In AUTO fan speed mode, the fan speed remains the same for 1 minute each time a speed change occurs. A manual change can override this.

• At the beginning of heating, a higher speed is chosen for a steeper upward temperature gradient.

• When the indoor heat exchanger sensor (TC2) temperature is ≥ 60 °C, the fan speed is raised by one step.

• If the air conditioner goes thermo OFF during heating, the fan speed drops to LL (breeze).


What is the cold air discharge prevention control on the TOSHIBA MMD-AP0306BHP-TR?

During heating operation, the cold air discharge prevention control on your TOSHIBA MMD-AP0306BHP-TR sets the upper limit of the fan tap based on the indoor heat exchanger sensor temperatures (TC1, TC2, TCJ). This prevents cold air from blowing into the room.

The fan speed is controlled based on the following temperature zones:

Zone A (below 26°C): Fan OFF. “HEATING STANDBY” is displayed on the remote.

Zone B (26°C to below 28°C): Breeze speed.

Zone C (28°C to below 30°C): Low speed.

Zone D (30°C to below 32°C): Medium speed.

Zone E (32°C and above): High speed.

If the fan operates continuously in Zone B for 6 minutes, it automatically moves to Zone C. During defrosting, the control point is shifted by +6 °C.


How does the freeze prevention control work on the TOSHIBA MMD-AP0306BHP-TR?

During cooling operation on your TOSHIBA MMD-AP0306BHP-TR, the freeze prevention control operates based on the readings of the indoor heat exchanger sensors (TC1, TC2, TCJ) to prevent the coil from freezing.

Control Logic 1:

• If the unit operates in the “J zone” (e.g., TC1 at 0°C, TC2/TCJ at -14°C) for 5 minutes, it is forced into thermo OFF.

• If it operates in the “K zone”, a timer is paused.

• If it operates in the “I zone” (e.g., TC1 at 10°C, TC2/TCJ at -10°C), the timer is cleared, and the unit returns to normal operation.

• If continuous operation in the J zone forces a thermo OFF, the indoor fan operates in breeze mode until it moves into the I zone.

• This control terminates when TC1, TC2, and TCJ are all ≥ 12°C, or after 20 minutes of stoppage.

Control Logic 2:

• If the unit operates in the “M zone” (e.g., TC2/TCJ at -2.0°C) for 45 minutes, it is forced into thermo OFF.

• In the “N zone”, a timer is paused. When returning to the M zone, the timer count resumes.

• In the “L zone” (e.g., TC2/TCJ at 5°C), the timer is cleared, and the unit returns to normal operation.

• This control resets when TC1, TC2, and TCJ are all ≥ 12°C, or after 20 minutes of stoppage.


How does the drain pump control work on the TOSHIBA MMD-AP0306BHP-TR?

The drain pump control on your TOSHIBA MMD-AP0306BHP-TR works as follows to remove condensed water:

1. During cooling (including DRY operation), the drain pump is operated at all times.

2. If the float switch is activated while the drain pump is in operation, the drain pump continues operating, and the check code [P10] is displayed.

3. If the float switch is activated while the drain pump is turned off, the air conditioner is forced into thermo OFF, and the drain pump is put into operation. If the float switch remains activated for about 5 minutes, the drain pump is turned off, and the check code [P10] is displayed.


How do I use the power saving mode on the TOSHIBA MMD-AP0306BHP-TR?

To use the power saving mode on your TOSHIBA MMD-AP0306BHP-TR, follow these steps:

1. Push the SAVE button on the remote controller.

2. The “SAVE” segment lights up on the wired remote controller display.

3. The requirement capacity ratio is limited to approximately 75%.

4. If the power saving operation is enabled, the settings are retained when the operation is stopped, the mode is changed, or when the power is reset. The power saving operation will be enabled the next time the operation starts.

Note: This function cannot be set by a wireless remote controller or older wired models like the AMT31E.


How do I perform a test operation (frequency fixed operation) on the TOSHIBA MMD-AP0306BHP-TR?

In case of wired remote controller:

1. Push the [CHK] button for 4 seconds or more. [TEST] will be displayed on the screen, and the unit will enter Test run mode.

2. Push the [ON/OFF] button.

3. Using the [MODE] button, set the mode to [COOL] or [HEAT]. Do not use any other mode.

4. After the test run, push the [ON/OFF] button to stop the operation.

5. Push the [CHK] button to clear the test run mode. The [TEST] display will disappear, and the status will return to normal.

In case of wireless remote controller:

1. When the TEMPORARY button is pushed for 10 seconds or more, a “Pi!” sound is heard, and the operation changes to test run. After approximately 3 minutes, a cooling operation starts forcibly. Check that cool air starts blowing.

2. To stop the test operation, push the TEMPORARY button once again (for approximately 1 second).


How can I test the indoor unit functions of the TOSHIBA MMD-AP0306BHP-TR without the outdoor unit or remote?

The TOSHIBA MMD-AP0306BHP-TR has a check function to test the indoor unit singly without communication with the remote controller or outdoor unit. This function should be used for only a few minutes to avoid causing trouble.

How to operate:

1. Short-circuit the CHK pin (CN71 on the indoor P.C. board). The operation mode will differ depending on whether the unit status is normal (both float switch and fan motor are normal) or abnormal (either float switch or fan motor is abnormal).

2. During normal time, if you also short-circuit the DISP pin (CN72 on the indoor P.C. board), the minimum opening degree (30 pls) can be set for the indoor PMV. When the DISP pin is open, the maximum opening degree (1500 pls) can be obtained.

How to clear:

Open the CHK pin. The system will stop once and then automatically return to operation after several minutes.

Normal time Abnormal time
DISP pin open DISP pin short circuit
Fan motor (H) (H) Stop
Indoor PMV (*) Max. opening degree (1500 pls) Min. opening degree (30 pls) Min. opening degree (30 pls)
Louver Horizontal Horizontal Immediate stop
Drain pump ON ON ON
Communication All ignored All ignored All ignored
P.C. board LED Lights Lights Flashes

How do I set the indoor unit function DN code on my TOSHIBA MMD-AP0306BHP-TR?

To set the indoor unit function DN code on your TOSHIBA MMD-AP0306BHP-TR, you must use a wired remote controller and the system must be at rest. Follow this procedure:

1. Push the SET, TEMP up, and CL buttons simultaneously and hold for at least 4 seconds. The unit No. displayed first is the address of the header indoor unit in group control. The fan and louver of the selected indoor unit will move.

2. Each time the UNIT LOUVER button (left side) is pressed, one of the indoor unit Nos. under group control is displayed in turn. The fan and louver of the selected unit will move.

3. Use the TEMP buttons to select the desired CODE No. (DN code) of the function you want to change.

4. Use the TIME buttons to select the desired SET DATA associated with the selected function.

5. Push the SET button. The display will change from flashing to steady.

6. When the CL button is pushed, the system returns to the normal off state.


What are the available function DN codes for the TOSHIBA MMD-AP0306BHP-TR?

DN Item Description At shipment
01 Filter display delay timer 0000: None, 0001: 150H, 0002: 2500H, 0003: 5000H, 0004: 10000H According to type
02 Dirty state of filter 0000: Standard, 0001: High degree of dirt (Half of standard time) 0000: Standard
03 Central control address 0001: No.1 unit to 0064: No.64 unit 0099: Unfixed
04 Specific indoor unit priority 0000: No priority, 0001: Priority 0000: No priority
06 Heating temp shift 0000: No shift, 0001: +1 °C, 0002: +2 °C to 0010: +10 °C (Up to +6 recommended) 0002: +2 °C (Floor type 0000: 0 °C)
0d Existence of [AUTO] mode 0000: Provided, 0001: Not provided (Automatic selection from connected outdoor unit) 0001: Not provided
0F Cooling only 0000: Heat pump, 0001: Cooling only (No display of [AUTO] [HEAT]) 0000: Heat pump
10 Type Refer to Type CODE No. [10] table in the PDF Depending on model type
11 Indoor unit capacity 0000: Unfixed, 0001 to 0034 According to capacity type
12 Line address 0001: No.1 unit to 0030: No.30 unit 0099: Unfixed
13 Indoor unit address 0001: No.1 unit to 0064: No.64 unit 0099: Unfixed
14 Group address 0000: Individual, 0001: Header unit of group, 0002: Follower unit of group 0099: Unfixed
1E Temp difference of [AUTO] mode selection 0000: 0 deg to 0010: 10 deg 0003: 3 deg (Ts ±1.5)
28 Automatic restart of power failure 0000: None, 0001: Restart 0000: None
2A Selection of option / error input (CN70) 0000: Filter input, 0001: Alarm input (Air washer, etc.), 0002: None 0002: None
2E HA terminal (CN61) select 0000: Usual, 0001: Leaving-ON prevention control, 0002: Fire alarm input 0000: Usual (HA terminal)
31 Ventilating fan control 0000: Unavailable, 0001: Available 0000: Unavailable
32 TA sensor selection 0000: Body TA sensor, 0001: Remote controller sensor 0000: Body TA sensor
33 Temperature unit select 0000: °C (at factory shipment), 0001: °F 0000: °C
5d Static pressure selection Set data from 0000 to 0006 for pressures from 30 Pa to 120 Pa depending on model 0000: Standard
60 Timer setting (wired remote controller) 0000: Available (can be performed), 0001: Unavailable (cannot be performed) 0000: Available
92 External interlock release condition 0000: Operation stopped, 0001: Release signal received 0000: Operation stopped
D0 Whether the power saving mode can be set by the remote controller 0000: Invalid, 0001: Valid 0001: Valid

How do I manually set the addresses on my TOSHIBA MMD-AP0306BHP-TR using the remote controller?

To set the addresses manually, you need to pair the indoor unit with a remote controller one-to-one. Turn on the power and follow these steps:

1. Push and hold the SET, CL, and TIME UP buttons at the same time for more than 4 seconds. The LCD will start flashing.

Set Line (system) address:

2. Push the TEMP buttons repeatedly to set the CODE No. to 12.

3. Push the TIME buttons repeatedly to set a system address. (This must match the address on the interface P.C. board of the header outdoor unit in the same refrigerant line.)

4. Push the SET button.

Set Indoor unit address:

5. Push the TEMP buttons repeatedly to set the CODE No. to 13.

6. Push the TIME buttons repeatedly to set an indoor unit address.

7. Push the SET button.

Set Group address:

8. Push the TEMP buttons repeatedly to set the CODE No. to 14.

9. Push the TIME buttons repeatedly to set a group address. Use 0000 for an individual unit, 0001 for a header unit, or 0002 for a follower unit.

10. Push the SET button.

11. Push the CL button. The address setting is complete. The word “SETTING” will flash and then disappear.

NOTE: Do not use address numbers 29 or 30 for system addresses as they cannot be used on outdoor units and will cause an [E04] error.


How do I clear an error on my TOSHIBA MMD-AP0306BHP-TR using the wired remote controller?

Clearing an error of the outdoor unit:

This procedure clears the currently detected outdoor unit error for the connected refrigerant line. The indoor unit error is not cleared.

1. Push and hold the CL and VENT buttons for 4 seconds or longer to enter the service monitoring mode.

2. Push the TEMP button to set the CODE No. to “FF”.

3. The display will count down from “0005” to “0000” at 5-second intervals. The error is cleared when “0000” appears.

4. Push the VENT button to return the display to normal.

Clearing an error of the indoor unit:

Push the ON/OFF button on the remote controller. Only the error of the indoor unit controlled by that remote controller will be cleared.


How do I use the monitoring function on the wired remote controller for my TOSHIBA MMD-AP0306BHP-TR?

You can use the service monitoring mode on the RBC-ATM32E remote controller to check sensor temperatures and operation status.

1. Push and hold the VENT and CL buttons for 4 seconds or longer to enter the service monitoring mode. The service monitor lights up, and the temperature for CODE No. 00 appears first.

2. Push the TEMP button to change the CODE No. of the item you want to monitor.

3. Push the left part of the UNIT LOUVER button to change the item to monitor. This allows you to view sensor data from the indoor unit and outdoor unit in the refrigerant line.

4. Push the VENT button to return the display to normal.

Monitored Data (Indoor Unit):

CODE No. Data Example
00 Room temperature (in control) [0024]=24 °C
01 Room temperature (Remote controller)
02 Air Temperature (TA)
03 Coil Temperature (TCJ)
04 Coil Temperature (TC2)
05 Coil Temperature (TC1)
08 PMV [0050]=500 pls

What are some normal behaviors of the TOSHIBA MMD-AP0306BHP-TR that I should check before troubleshooting?

Before assuming a fault with your TOSHIBA MMD-AP0306BHP-TR, check for these normal behaviors:

NO. Behavior Possible cause
1 A compressor would not start • Could it just be the 3-minute delay period (3 minutes after compressor shutdown)?
• Could it just be the air conditioner having gone thermo OFF?
• Could it just be the air conditioner operating in fan mode or put on the timer?
• Could it just be the system going through initial communication?
2 An indoor fan would not start • Could it just be cold air discharge prevention control, which is part of heating?
3 An outdoor fan would not start or would change speed for no reason • Could it just be cooling operation under low outside temperature conditions?
• Could it just be defrosting operation?
4 An indoor fan would not stop • Could it just be the elimination of residual heat being performed as part of the air conditioner shutdown process after heating operation?
5 The air conditioner would not respond to a start / stop command from a remote controller • Could it just be the air conditioner operation under external or remote controller?

A microprocessor malfunction due to poor power quality or external noise can also mimic a fault. Check for possible noise sources and ensure proper shielding of remote controller and signal wires.


How can I troubleshoot my TOSHIBA MMD-AP0306BHP-TR based on check codes displayed on the indoor unit?

The following table lists check codes detected by the indoor unit of your TOSHIBA MMD-AP0306BHP-TR and their descriptions. The indicator light block refers to the lights on the wireless receiver.

Check code Indicator light block (Operation/Timer/Ready) Typical fault site Description of error
E03 Flash/Off/Off Indoor-remote controller periodic communication error Communication from remote controller or network adaptor has been lost.
E04 Flash/Off/On Indoor-outdoor periodic communication error Signals are not being received from outdoor unit.
E08 Flash/Flash/Off Duplicated indoor address Indoor unit detects an address identical to its own.
E10 Flash/Flash/On Indoor inter-MCU communication error MCU communication between main controller and motor microcontroller is faulty.
E18 On/Flash/Flash Error in periodic communication between indoor header and follower unit Periodic communication between indoor header and follower units cannot be maintained.
F01 Flash/Off/Off (Alternating) Indoor heat exchanger temperature sensor (TCJ) error Heat exchanger temperature sensor (TCJ) has been open / shortcircuited.
F02 Flash/Off/Flash (Alternating) Indoor heat exchanger temperature sensor (TC2) error Heat exchanger temperature sensor (TC2) has been open / shortcircuited.
F03 Flash/Off/On (Alternating) Indoor heat exchanger temperature sensor (TC1) error Heat exchanger temperature sensor (TC1) has been open / shortcircuited.
F10 Flash/Flash/On (Alternating) Ambient temperature sensor (TA) error Ambient temperature sensor (TA) has been open / short-circuited.
F29 Flash/On/Flash (Simultaneous) P.C. board or other indoor error Indoor EEPROM is abnormal.
L03 On/Flash/Off (Simultaneous) Duplicated indoor group header unit There is more than one header unit in group.
L07 On/Flash/Flash (Simultaneous) Connection of group control cable to stand-alone indoor unit A stand-alone indoor unit is connected to a group control cable.
L08 Flash/Off/Flash (Simultaneous) Indoor group address not set Address setting has not been performed for one or more indoor units.
L09 Flash/Off/On (Simultaneous) Indoor capacity not set Capacity setting has not been performed for indoor unit.
L30 Off/Flash/Off (Simultaneous) Indoor external error input (interlock) Unit shutdown has been caused by external error input (CN80).
P01 Flash/Flash/Off (Alternating) Indoor AC fan error Indoor AC fan error is detected (activation of fan motor thermal relay).
P10 On/Flash/Off (Alternating) Indoor overflow error Float switch has been activated.
P12 On/Flash/On (Alternating) Indoor DC fan error Indoor DC fan error (e.g. overcurrent or lock-up) is detected.
P31 Flash/On/On (Alternating) Other indoor unit error Follower unit cannot be operated due to header unit alarm (E03 / L03 / L07 / L08).

How do I detach the air filter from the TOSHIBA MMD-AP0306BHP-TR?

To detach the air filter from your TOSHIBA MMD-AP0306BHP-TR, follow these steps. Remember to stop the air conditioner and turn off the breaker first.

1. Detachment:

Slide the filter toward the opposite side of the arrow mark and then pull out the filter. If two filters are provided, pull out the first filter, and then the second filter will be pulled out connected to the first.

2. Attachment:

Insert the filter into the filter rail toward the arrow mark, slide it until it stops, and then fix it. If two filters are provided, insert the second filter in the same direction after inserting the first filter.


How do I detach the suction panel from the TOSHIBA MMD-AP0306BHP-TR?

To detach the suction panel from your TOSHIBA MMD-AP0306BHP-TR, please follow this procedure:

1. Detachment:

1. Remove the fixing screws A which fix the suction panel. Loosen the fixing screws B.

2. Slide the suction panel to the arrow side and then remove the panel.

2. Attachment:

1. Hook the suction panel to the fixing screws B and tighten screws.

2. Attach the removed screws A to the original positions.


How do I detach the electric parts box cover from the TOSHIBA MMD-AP0306BHP-TR?

To detach the electric parts box cover from your TOSHIBA MMD-AP0306BHP-TR:

1. Detachment:

1. Remove screw A of the electric parts box cover to loosen screw B.

2. Slide the cover toward the arrow direction and pull it towards you. The cover will open using the hinge part as a shaft.

3. Take off the slit of the electric parts box cover from the projection of the side plate and then remove the cover.

2. Attachment:

1. Hook the slit of the cover to the projection of the side plate, close the cover, enter screw B in the keyhole, and then slide it.

2. Fix the electric parts box cover by tightening screws A and B.

How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.