Free English RUVICK LGG360T (01) PDF document. Download the PDF, use the online viewer, or browse the FAQs for easy troubleshooting.


CLICK HERE TO DOWNLOAD RUVICK LGG360T (01) PDF DOCUMENT

If this is not the document you want for this product, click here to see if we have any other documents for this product.


How to use the PDF below:
* Touchscreen: Swipe up/down with-in the PDF to scroll and pinch or spread with two fingers to zoom.
* Mouse: While your mouse is hovering over the PDF, use the mouse wheel to scroll and click on the – / + buttons at the bottom of the PDF to zoom.


What are the functions and features of the RUVICK LGG360T?

The RUVICK LGG360T has the following functions and features:

  • Import and export active/reactive/apparent energy, 4 quadrants reactive energy measuring and storage functions.
  • Measuring the daily and monthly total active/apparent energy and money consumption.
  • Instantaneous parameter measurement functions such as current, voltage, active power, reactive power, apparent power, power factor, frequency, phase angles, demand etc.
  • Maximum demand based on import and export active/reactive/apparent power (KW/KVAR/KVA), Cumulative maximum demand up to 13 month, selectable block and slide mode.
  • Load control functions (Over load control, Arrearage control, Tamper control, Malfunction control, fire disaster control etc.).
  • Supporting 13 months monthly billing and 31 days daily billing, the captured objects can be configured by communication.
  • Supporting at least 6 load profile channels, captured objects can be configured, storage capacity can be customizable, up to 360 days.
  • Large LCD display with OBIS codes and backlight, power-off display function, can display by pressing key button.
  • Many convenient user interfaces such as optical communication port (IEC62056-21), RS485 multi-drop port, MBUS port, LCD display, keypad and key buttons.
  • DLMS/COSEM communication protocol, for good connectivity and strong compatibility.
  • Supporting uplink remote communication and the module can be customizable such as GPRS/3G/4G/Ethernet/G3-PLC/PRIME-PLC/Mesh-RF and so on, which can be suitable for different installation site (if the function is enabled).
  • Supporting tamper and alarm functions such as current polarity reversal, current short (Bypass), current open, tamering terminal cover, tampering meter cover, tampering metering cabinet door, tampering strong magnet etc.
  • Supporting power grid quality analysis such as missing potential, Invalid voltage (under and over voltage), earth fault, voltage imbalance, current imbalance, reverse phase sequence, over load etc.
  • Supporting firmware upgrade locally and remotely.
  • The prepayment function includes the balance warning, remaining days early warning, friendly control mode, emergency overdraft, step tariff, expense management, short code query, vending based on money into meter, vending based on the primary or second side (CT rate) etc.
  • The step tariff up to 10 steps and money resolution up to 1/10000 GHC.
  • The expense management of meter includes Levies (NEL/SLL), VAT, NHIS, Monthly service charge, Fixed service charge (meter rent/debt), Maximum demand charge, Power factor charge, up to 5 kinds subsidy etc.
  • The split type supports CIU/UIU communication port, which is convenient for users to charge and query in real time.
  • The split type supports mainstream communication wired module MBUS, it is stable and convenient for installing on site.
  • High security mechanism conformed with STS/CTS prepayment standard.
  • Supporting friendly control and various agile friendly mode like holiday, weekend and specified time (if the function is enabled).
  • Automatic software calibration technology for simple, fast, high accuracy calibration.
  • New idea meter structure, which is novel, beautiful and applicable.

What are the Meter Type Specifications for the RUVICK LGG360T?

The Meter Type Specifications for the RUVICK LGG360T are detailed in the following table:

Meter Type Connection Reference voltage (V) Reference current (A) Active pulse constant(imp/kWh) Reactive pulse constant(imp/kvarh) Accuracy class
LGG360T 3P4W 3×230/400 5(10) 10000 10000 Active class 0.5s Reactive class 1

What are the Electrical Specifications for the RUVICK LGG360T?

The Electrical Specifications for the RUVICK LGG360T are as follows:

Normal working voltage range 0.8Un 1.2Un
Limit working voltage range 0.6Un 1.3Un
Rated operating frequency 50Hz
Starting current 0.1%lb
No load condition Not more than 1 pulse output within no load condition period
Insulation protection level 2
Voltage circuit power consumption ≤1.5W & 5 VA
Current circuit power consumption < 2 VA
Clock battery one external battery can be replaced
Clock battery capacity ≥1200mAh
Clock accuracy (daily error) ≤0.5s/d (Clock change rate 0.015s/C
Data retention time after power off ≥15year
External breaker controller Up to 10000 times operating limit under rated working current conditions; Up to 100000 times operating limit under no-load conditions;

What are the Climate and Environment Conditions for the RUVICK LGG360T?

The Climate and Environment Conditions for the RUVICK LGG360T are detailed in the following table:

Normal working temperature -25 55
Limit working temperature -40 75
Storage and transportation temperature -40 75
Storage and working humidity ≤95%RH
Dust and water proof class IP54

What are the Performance Index values for the RUVICK LGG360T?

The Performance Index values for the RUVICK LGG360T are detailed in the following table:

Impulse voltage 8KV 1.2/50us
AC Voltage 4KV
EMC-Immunity to electrostatic Discharge 8KV for contact discharge 15KV for air discharge
EMC-Fast Transient Burst 4KV
EMC-Surge Immunity 4KV
EMC-Immunity to electromagnetic RF fields 10V/m with current 30V/m without current
EMC-Radio Interference 30MHz~1GHz < 30dB
EMC-Immunity to conducted disturbances, induced radio-frequency fields 150kHz~80MHz
EMC-Damped oscillatory waves immunity Common mode:2.5KV Differential mode: 1.0KV

What are the metering modes for the Total and export active/apparent energy function in the RUVICK LGG360T?

The metering modes for the Total and export active/apparent energy function in the RUVICK LGG360T are:

  • Total active/apparent energy: |+A| = |+A|+ |-A|.
  • Export active/apparent energy:|-A| = |-A|.

What are the metering modes for the Import and export reactive energy and independent 4 quadrants metering function in the RUVICK LGG360T?

The metering modes for the Import and export reactive energy and independent 4 quadrants metering function in the RUVICK LGG360T are:

  • Import reactive energy:|+R| = |I| + |IV|, it can be configured.
  • Export reactive energy:|-R| = |II| + |III|, it can be configured.
  • Quadrant I reactive energy: |+R| = |I|.
  • Quadrant II reactive energy: |+R| = |II|.
  • Quadrant III reactive energy: |+R| = |III|.
  • Quadrant IV reactive energy: |+R| = |IV|.

What instantaneous measuring parameters are supported by the RUVICK LGG360T?

The instantaneous measuring parameter function in the RUVICK LGG360T includes: voltage, current, power factor, active power, reactive power, apparent power, power grid frequency, phase angles etc. It also measures the cumulative monthly average power factor.


What are the display performance characteristics of the LCD screen on the RUVICK LGG360T?

The display performance characteristics of the LCD screen on the RUVICK LGG360T are:

  • The size of LCD screen is 60mm×30mm the size of main numeral is 5×10mm.
  • The material of LCD is HTN, the working temperature scope of which is -40 80.
  • The LCD has high contrast ratio and the drive mode of which is 1/4 DUTY, 1/3 BIAS.
  • The best visual angle of LCD is 6 o’clock.
  • The polaroid of LCD has anti-ultraviolet function.

What do the LCD display symbols on the RUVICK LGG360T meter indicate?

The LCD display symbols on the RUVICK LGG360T meter have the following descriptions:

LCD Display Symbol Symbol Description
8.8.8.8.8.8.8.8 Data display area includes energy, instantaneous parameters and time etc.
8.8.8.8.8.8.8.8 According to the OBIS definition of IEC62056-61, the CDE will be displayed and the historical data which adds F number in the OBIS display area.
kWh\MWh\kvarh\kVAh\V\A\Hz etc. Unit display area includes energy, instantaneous parameters, such as: kWh\MWh\kvarh\kVAh\V\A\Hz etc.
Symbol for GPRS signal intensity symbol GPRS signal intensity symbol
Symbol for No battery or battery is low No battery or battery is low
Symbol for Communication symbol Communication symbol
Symbol for Alarm symbol Alarm symbol
Symbol for Tamper symbol Tamper symbol
Symbol for Disconnected relay symbol Disconnected relay symbol
Symbol for Connected relay symbol Connected relay symbol
Credit Days Means credit related information
T8 Multi TOU tariff and step tariff symbol (if the function is actived)
+P -P +Q -Q Four quadrant symbols, +P and -P mean active power plus and minus; +Q and -Q mean reactive power plus and minus;
L1 L2 L3 Each phase voltage symbols and each phase current reverse symbols
Symbol for Successful symbol Successful symbol
Symbol for Failed symbol Failed symbol
I II III IV V VI Special alarm symbol

What is the default scroll display cycle and contents for the RUVICK LGG360T in scroll display mode?

The default scroll display cycle for the RUVICK LGG360T is 6 seconds. The scroll display contents are as follows:

No. OBIS display Description
1 C.60.0 Balance
2 1.29.1 Money used in current month
3 1.29.0 Energy used in current month
4 1.30.1.1 Money used in last day
5 1.30.0.1 Energy used in last day
6 1.29.1.1 Money used in last month
7 1.29.0.1 Energy used in last month
8 1.29.1.2 Money used in last 2th month
9 1.29.0.2 Energy used in last 2th month
10 1.29.1.3~12 Money used in last 3th-12th month
11 1.29.0.3~12 Energy used in last 3th-12th month
12 C.60.9 Remaining days
13 C.53.1 Current electricity tariff price
14 C.63.1 NEL charge used in last month
15 C.63.2 SLL charge used in last month
16 C.63.9 Fixed charge (meter rent) used in last month
17 C.63.10 Fixed charge (Debt) used in last month
18 C.63.12 Max demand charge in last month
19 C.63.13 Power factor charge in last month
20 C.63.14 Service charge in last month
21 C.63.15 GoG lifeline subsidy S1 in last month
22 C.63.16 GoG old subsidy S2 in last month
23 C.63.17 GoG new subsidy S3 in last month
24 C.63.18 Utility Relief (UR) in last month
25 C.63.6 VAT charge in last month
26 C.63.7 NHIS charge in last month
27 19.40.0.1~19.40.0.5 Charge Token last 5 times
28 C.60.1 Accumulated charge amount
29 1.6.0 Maximum demand and occurred date time in current month

How does the key operation affect the display mode on the RUVICK LGG360T?

The key operation on the RUVICK LGG360T affects the display mode as described below:

Key Operation Key Holding Time Operation Description
Short press Less than 2 seconds Turn over the current screen by short press, and return to scroll display mode after 64seconds without operation.
Short long press More than 2 seconds but less than 4 seconds Turn over display list by short long press, and need to release the key when displays “PAGING”. Return to automatic scroll display mode after 3 minutes without operation.
Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display list by long press, and need to release the key when displays “BACING”
Medium long press More than 6 seconds but less than 8 seconds Cancel temporary alarm by medium long press (If the function is actived), and need to release the key when display “CLuuArn”.
Overlong press More than 8 seconds Quitting by long press, and return to automatic scroll display list

It will return to scroll display mode when without operation after 64 seconds.


What information is displayed when using the default key display table on the RUVICK LGG360T?

The default key display table on the RUVICK LGG360T shows the following information:

No. OBIS display Description
1 Full screen Full screen display test
2 0.9.1 Real time
3 0.9.2 Real date (DD, MM, YY)
4 C.1.0 Meter Serial Number
5 1.4.0 Current rising demand
6 C.15.43 Meter Reading count
7 C.53.45 Cumulative current month power-on hours
8 C.15.22 Cumulative MD reset count
9 1.8.0 Cumulative Total active energy (kWh)
10 2.8.0 Cumulative Export active energy (kWh)
11 5.8.0 Cumulative Reactive Energy quadrant I (kVArh)
12 6.8.0 Cumulative Reactive Energy quadrant II (kVArh)
13 7.8.0 Cumulative Reactive Energy quadrant III (kVArh)
14 8.8.0 Cumulative Reactive Energy quadrant IV (kVArh)
15 3.8.0 Cumulative Reactive Energy import (kVArh)
16 4.8.0 Cumulative Reactive Energy export (kVArh)
17 9.8.0 Cumulative Total Apparent Energy (kVAh)
18 10.8.0 Cumulative Export Apparent Energy (kVAh)
19 9.6.0 Current month cumulative MD (kVA)
20 32.7.0 Instantaneous phase A voltage
21 52.7.0 Instantaneous phase B voltage
22 72.7.0 Instantaneous phase C voltage
23 31.7.0 Instantaneous phase A current
24 51.7.0 Instantaneous phase B current
25 71.7.0 Instantaneous phase C current
26 91.7.0 Instantaneous neutral current
27 14.7.0 Instantaneous frequency
28 13.7.0 Instantaneous power factor
29 15.7.0 Instantaneous total active power in KW
30 3.7.0 Instantaneous import reactive power in KVAR
31 9.7.0 Instantaneous import apparent power in KVA
32 C.60.7 Overload Threshold value
33 C.60.2 Emergency overdraft value
34 12.35.0 Overvoltage threshold value
35 12.31.0 Under voltage threshold value
36 C.7.21 Power off count
37 C.15.1 Total tamper count
38 0.4.2 CT rate molecule
39 0.4.4 CT rate denominator

What is the behavior of the RUVICK LGG360T meter in Power off mode?

In Power off mode on the RUVICK LGG360T meter, the meter operates relying on battery and will display content for 10 seconds when the meter power off. The LCD will be displayed when pressing the key button, and the display contents are the same as the scroll display mode. The LCD display will be closed automatically after 64 seconds without any operation.


How does the RUVICK LGG360T display its running status?

The RUVICK LGG360T displays its running status by taking a real time function check, operation check, and error self-check on the LCD. The status display table is as follows:

Status Name Status Symbol Status Description
Battery Status Symbol for Battery Status Battery Status symbol, it will be showed when the battery is low or no battery;
Voltage Status L1
L2
L3
Lx will be displayed if the actual phase voltage is ok, Lx flickers if the actual phase voltage is high or low, and reverse symbol will be displayed if the actual phase current is reversed.
Smiling face Symbol for Smiling face This symbol will be displayed if operation is successful.
Crying face Symbol for Crying face This symbol will be displayed if operation is failed.
Paging PAGING The meter is paging now.
Backing BACKING The meter is paging back.
Demand clearance CLr-Ded This symbol will be displayed for 2 seconds in the main display area if demand clearance is occurred.
Event clearance CLr-Ent This symbol will be displayed for 2 seconds in the main display area if event clearance is occurred.
Load clearance CLr-Lod This symbol will be displayed for 2 seconds in the main display area if load clearance is occurred.
Billing clearance CLr-BIL This symbol will be displayed for 2 seconds in the main display area if billing clearance is occurred.
EEPROM fault E2P-Err This symbol will be displayed in the main display area until meter reset to restart when the EEPROM fault is occurred during power up process.
EEPROM data error E2P-VEr This symbol will be displayed for 2 seconds in the main display area if EEPROM data error is occurred during power up process.
DATA FLASH fault FLH-Err This symbol will be displayed in the main display area until meter reset to restart, if DATAFLASH fault is occurred during power up process.

How is the sound alarm cancelled on the RUVICK LGG360T?

The buzzer sounds on the RUVICK LGG360T if the remaining days are less than 3 days. Users can manually cancel the sound alarm by keying in “612”. The sound alarm will be closed automatically during 18:00~06:00 to avoid disturbing the normal rest of users.

The display when cancelling the sound alarm is:

Operation Instruction Displaying
Cancel successfully 612 SUCCESS®
Cancel rejected 612 ГЕШЕСЕ

What displays are shown on the RUVICK LGG360T LCD screen after charging with a TOKEN?

After charging with a TOKEN on the RUVICK LGG360T, the charging results displayed on the LCD screen are:

Change result Displaying
Charge successful 55 Credit 100.00
Wrong TOKEN EE ГЕЈЕСЕ
Used TOKEN EE USED.
Expired TOKEN EE old
Expired Key EE EXP irEd
Over Charge EE Quer

How is the key changed using Management TOKENs on the RUVICK LGG360T?

The key change procedure on the RUVICK LGG360T using Management TOKENs requires that the key only can be changed when two TOKENs are inputed at the same time. Users must input two TOKENS within 120 seconds.


What information can users acquire using the 3-digit short codes on the RUVICK LGG360T meter?

Users of the RUVICK LGG360T meter can input 3 digits of short codes to acquire meter information. The query short codes are:

Short code No. Function description Short code No. Function description
800 Total active energy 801 Balance
802 Current date 803 Current time
804 Meter No. 805 SGC No.
806 Relay operation reason 807 Tamper status
808 Remaining days 809 Tariff No.
810 Overdraft amount 813 Total active energy last day
814 Total consumed energy in current month 815 Total consumed amount in current month
816 Last charged date and time 817 Last charge amount
818 Logout Token 819 Total power off times
820 Accumulated charge amount 821 Accumulated total active energy of last month
822 Accumulated total active energy of latest second month 823 Accumulated total active energy of latest third month
824 Accumulated total active energy of latest 4th month 825 Accumulated total active energy of latest 5th month
826 Accumulated total active energy of latest 6th month 827 Accumulated total active energy of latest 7th month
828 Accumulated total active energy of latest 8th month 829 Accumulated total active energy of latest 9th month
830 Accumulated total active energy of latest 10th month 831 Accumulated total active energy of latest 11th month
832 Accumulated total active energy of latest 12th month 841 Last charge TOKEN
842 Charge TOKEN of latest second time 843 Charge TOKEN of latest third time
844 Charge TOKEN of latest 4th time 845 Charge TOKEN of latest 5th time
846 Charge TOKEN of latest 6th time 847 Charge TOKEN of latest 7th time
848 Charge TOKEN of latest 8th time 849 Charge TOKEN of latest 9th time
850 Charge TOKEN of latest 10th time 866 Over voltage threshold
867 Under voltage threshold 868 Maximum current threshold
869 Maximum power threshold 870 Phase A voltage
871 Phase B voltage 872 Phase C voltage
873 Version of key 874 Version of firmware
875 Key type 877 Accumulated meter running time
880 Phase A current 881 Phase B current
882 Phase C current 884 Total instantaneous active power
888 Total power factor 889 Power grid frequency
900 The consumed energy of last day 910 Maximum demand of current month
911 Date and time of maximum demand of current month 921 The consumed amount of last month
942 The consumed amount of latest second month 923 The consumed amount of latest third month
944 The consumed amount of latest 4th month 925 The consumed amount of latest 5th month
946 The consumed amount of latest 6th month 927 The consumed amount of latest 7th month
948 The consumed amount of latest 8th month 929 The consumed amount of latest 9th month
950 The consumed amount of latest 10th month 931 The consumed amount of latest 11th month
952 The consumed amount of latest 12th month 954 Total tamper times
955 Total demand manual reset times 980 NEL charge used in last month
981 SLL charge used in last month 985 VAT charge in last month
986 NHIS charge in last month 988 Fixed charge (meter rent) used in last month
989 Fixed charge (Debt) used in last month 991 Max demand charge in last month
992 Power factor charge in last month 993 Service charge in last month
994 GoG lifeline subsidy S1 in last month 995 GoG old subsidy S2 in last month
996 GoG new subsidy S3 in last month 997 Utility Relief (UR) in last month

If corresponding short codes do not exist, the following information will be displayed:

Operation Instruction Displaying
Short codes non-existent 99 ГЕШЕСЕ

What are the executing short codes for the RUVICK LGG360T meter?

The executing short codes for the RUVICK LGG360T meter are:

Short code No. Function description Short code No. Function description
611 Executing emergency overdraft 612 Executing cancellation of temporary alarm
613 Executing cancellation of sound alarm 614 Executing active meter cover open and terminal cover detecting
620 Executing pairing operation

If corresponding short codes do not exist, the following information will be displayed:

Operation Instruction Displaying
Short codes non-existent 99 ГЕШЕСЕ

What are the operation prompts for emergency overdraft on the RUVICK LGG360T?

The operation prompts for emergency overdraft on the RUVICK LGG360T are:

Operation Instruction Displaying
Emergency overdraft successful 611 SUCCESS®
Overdraft function is activated 01 ГЕШЕСЕ
Overdraft rejected 02 ГЕШЕСЕ
Arrears after overdraft 03 ГЕШЕСЕ

What is the procedure for CIU/UIU Pairing on the RUVICK LGG360T?

To perform CIU/UIU Pairing on the RUVICK LGG360T:

  1. Input short code 620 on CIU first, pressing enter key, the “step1” will be displayed on LCD.
  2. Input the meter No. which needs to be paired, pressing enter key, the “step2” will be displayed on LCD.
  3. Input the pairing code (123456) and pressing enter key.

The meter and CIU are pairing when the “Connect” is displaying on the CIU. The “SS-007” will be displayed on CIU means pairing is successful; the “EE-007” means pairing is failed.


What are the error codes for CIU Operating Failed Prompt on the RUVICK LGG360T?

The error codes for CIU Operating Failed Prompt on the RUVICK LGG360T are:

Error No. Specified analysis and description Solving methods
EE–001 When inputting the recharging mode, Token subclass is error Token issuing is incorrect, please contact with the vender or utility.
EE–002 The Token is not the key changing Token Illegal input is normal, no need to deal with; otherwise, please contact with the vender or utility.
EE–003 The key can not turn into DITK To change the initial key is not allowed on site, it is correct prompt.
EE–004 The key can not turn into general key To change the general key is not allowed on site, it is correct prompt.
EE–005 The test of connecting relay is failed When the relay is disconnected, the test of connecting relay is not supported, it is correct prompt.
EE–006 Changing key is overtime please try to ensure that two Token of changing key are finished within 120 seconds
EE–007 Pairing or cancelling pairing is failed Please ensure that the input meter serial number and the pairing password are correct
EE–008 CIU/UIU or meter are not paired yet Please use after pairing

What are the successful prompts for CIU Operation on the RUVICK LGG360T?

The successful prompts for CIU Operation on the RUVICK LGG360T are:

Prompt No. Specified analysis and description
SS–001 Changing key is successful
SS–002 Clearing tamper is successful
SS–003 Prepaid mode changing into post-paid mode is successful
SS–004 Post paid mode changing into prepaid mode is successful
SS–005 Relay test is successful
SS–006 All test are successful
SS–007 Pairing is successful
SS–008 Data synchronization is successful between meter and CIU/UIU
SS–009 Enabling meter cover and terminal cover detection is successful

What is the accuracy of the internal RTC clock module in the RUVICK LGG360T?

The internal RTC clock module in the RUVICK LGG360T has an accuracy of no more than 0.5s per day at normal temperature, and it switches automatically in leap year.


What are the tariff list supports for the TOU Tariff Function in the RUVICK LGG360T?

The TOU Tariff Function in the RUVICK LGG360T meter has two sets of tariff lists: the active tariff list and the passive tariff list. Each tariff list supports a maximum of 4 tariffs, 4 season tables, 4 weekly tables, 4 daily tables, and 4 period tables.


What are the types of holidays supported by the TOU Holiday Function in the RUVICK LGG360T?

The TOU Holiday Function in the RUVICK LGG360T supports two kinds of holidays: public holidays and special holidays. Public holidays happen every year and only require one record through optimizing the time format. Special holidays happen only in a particular year, with a maximum number of 50 holidays recorded per particular year.


How many steps of step tariff are supported by the RUVICK LGG360T prepayment meter?

The RUVICK LGG360T prepayment meter supports step tariff up to 10 steps. Each step has a threshold energy and step tariff charge, matched with a one-to-one relationship. The initial step threshold energy is 0.


How many steps of service charge are supported by the Monthly Service Charge function in the RUVICK LGG360T?

The service charge in the RUVICK LGG360T is up to 5 steps, each with a threshold energy and service charge. The meter deducts the basic service charge at the beginning of the month and calculates the remaining charge at the end of the month based on energy consumption. If the meter has a longtime power off of more than 2 months, the meter will fill the basic service charge for the power off month.


How many kinds of subsidy charge are supported by the RUVICK LGG360T?

The RUVICK LGG360T supports up to 5 kinds of subsidy charge, with each step having a threshold energy and subsidy charge. Examples include GoG Lifeline Subsidy S1, GoG Old Subsidy S2, GoG new Subsidy S3, and Utility relief (UR).


How many kinds of fixed charge are supported by the RUVICK LGG360T?

The RUVICK LGG360T supports up to 3 kinds of fixed charge, which are calculated at the end of the month, such as Meter rent charge or customer’s debt charge.


How many kinds of levies charge are supported by the RUVICK LGG360T?

The RUVICK LGG360T supports up to 5 kinds of levies charge, calculated at the end of the month, such as NEL (National Electricity Levy) and SLL (Street Light Levy).


How many kinds of VAT charge are supported by the RUVICK LGG360T?

The RUVICK LGG360T supports up to 3 kinds of value added tax charge, which the meter will calculate at the end of the month. Examples include VAT (value added tax) and NHIS (National Healthy Insurance Scheme).


How does the RUVICK LGG360T calculate the maximum demand charge?

The RUVICK LGG360T calculates the maximum demand charge at the end of the month based on the customer’s monthly maximum demand (KVA). If the maximum demand is not bigger than the basic maximum demand, then the basic maximum demand charge will be deducted. If the meter has a longtime power off for more than 2 months, the meter will fill the basic maximum demand charge for the power off month.


How does the RUVICK LGG360T calculate the power factor charge?

The RUVICK LGG360T calculates the power factor charge at the end of the month based on the customer’s monthly average power factor. If the average power factor is bigger than the power factor coefficient, the power factor charge will be deducted based on the utility’s formula: Power Factor Charge= (1-Average PF/ Coefficient)*Maximum Demand Charge.


What is the default billing time for the Monthly Billing Function on the RUVICK LGG360T?

The default billing time for the Monthly Billing Function on the RUVICK LGG360T is 0:00 on the 1st day every month, which means the billing time is on the 0:00 on 1st day of every month and every year. The billing time uses standard time format and can be changed by communication.


What is the default daily billing time for the Daily Billing Function on the RUVICK LGG360T?

The default daily billing time for the Daily Billing Function on the RUVICK LGG360T is 0:00, which means the daily billing time is on the 0:00 on every day of every month and every year. The daily billing time uses standard time format and can be changed by communication.


What is the default capture cycle for the Load Profile Function on the RUVICK LGG360T?

The default capture cycle for the Load Profile Function on the RUVICK LGG360T is 15 minutes, recording 100 days of data. The meter supports multi-channel load profile records, with the default channels being 6. The capture cycle is based on minute and can be chosen from 10min, 15min, 30min, 60min, etc.


What are the three kinds of load control functions available on the RUVICK LGG360T?

The load control function on the RUVICK LGG360T has three kinds: remote operation, local operation and manual operation. The meter can record the reason of the last relay operation.


What is the relay state for a ‘Normal connecting’ operation reason in the RUVICK LGG360T load control log?

For a ‘Normal connecting’ operation reason in the RUVICK LGG360T load control log, the Relay state is ‘Connected’ and the Operation No. is 0.


What are the different types of events recorded by the RUVICK LGG360T?

The events recorded by the RUVICK LGG360T can be divided into:

  • Up to 100 standard event records with occurred date and time: Low battery, clock sync, clock malfunction, NV memory malfunction, meter malfunction, MD reset, firmware upgrade etc.
  • Up to 100 tamper event records with occurred date and time: meter cover open, terminal cover open, meter cabinet door open, strong magnetic interference, login failed, parameter configuration, high temperature, current polarity reversal, current short (Bypass), current open etc.
  • Up to 50 charge event records with occurred date and time: charging value, charging TOKEN etc.
  • Up to 100 control event records with occurred date and time: disconnect the breaker, connect the breaker, breaker control failure etc.
  • Up to 100 power grid event records with occurred date and time: missing potential, Invalid voltage (under and over voltage), earth fault, voltage imbalance, loss of voltage, current imbalance, reverse phase sequence, over load, etc.

How is the alarm function indicated on the RUVICK LGG360T, and what does the ‘Lightening’ alarm prompt on the Alarm light signify?

The alarm function on the RUVICK LGG360T is indicated by the alarm light (LED), buzzer, liquid crystal alarm sign and so on. The ‘Lightening’ alarm prompt on the Alarm light signifies that the alarm light is on by default if the following events occurred: voltage imbalance, reverse phase sequence, under voltage, over voltage, over power, current reversing, current short(bypass), strong magnetic interference, terminal cover removal, meter cover removal, meter cabinet door opened etc. It can also be configured for other events.


What events trigger the ‘Sound’ alarm prompt on the Buzzer for the RUVICK LGG360T?

The ‘Sound’ alarm prompt on the Buzzer of the RUVICK LGG360T sounds by default if the following events occurred: arrearage etc. It can also be configured for other events.


What events trigger the Triangle alarm symbol ($\triangle$) on the RUVICK LGG360T?

The Triangle alarm symbol ($\triangle$) on the RUVICK LGG360T is displayed by default if the following events occurred: reverse phase sequence, under voltage, over voltage, missing potential, over power, meter malfunction etc. It can also be configured for other events.


What events trigger the Tampering alarm symbol on the RUVICK LGG360T?

The Tampering alarm symbol on the RUVICK LGG360T is displayed by default if the following events occurred: current reversing, current short(Bypass), strong magnetic interference, terminal cover removal, meter cover removal, module cover removal, meter cabinet door opened etc. It can also be configured as other events.


What events trigger the Alarm symbol of subscript I (I) on the RUVICK LGG360T?

The Alarm symbol of subscript I (I) on the RUVICK LGG360T is displayed by default if the following events occurred: meter cover removal; it can also be configured as other events.


What events trigger the Alarm symbol of subscript II (II) on the RUVICK LGG360T?

The Alarm symbol of subscript II (II) on the RUVICK LGG360T is displayed by default if the following events occurred: terminal cover removal; it can also be configured as other events.


What events trigger the Alarm symbol of subscript III (III) on the RUVICK LGG360T?

The Alarm symbol of subscript III (III) on the RUVICK LGG360T is displayed by default if the following events occurred: overpower; it can also be configured as other events.


What events trigger the Alarm symbol of subscript IV (IV) on the RUVICK LGG360T?

The Alarm symbol of subscript IV (IV) on the RUVICK LGG360T is displayed by default if the following events occurred: strong magnetic interference; it can also be configured as other events.


What events trigger the Alarm symbol of subscript V (V) on the RUVICK LGG360T?

The Alarm symbol of subscript V (V) on the RUVICK LGG360T is displayed by default if the following events occurred: bypass or module cover removal; it can also be configured as other events.


What events trigger the Alarm symbol of subscript VI (VI) on the RUVICK LGG360T?

The Alarm symbol of subscript VI (VI) on the RUVICK LGG360T is displayed by default if the following events occurred: reverse phase sequence; it can also be configured as other events.


What are the communication specifications for Optical Communication on the RUVICK LGG360T?

The Optical Communication on the RUVICK LGG360T follows these specifications:

  • Following IEC62056-21 optical communication physical interface standard.
  • Conforming to the standard of DLMS (E mode).
  • The initial baud rate is 300bps, 7 data bits, 1 even bit; 19200bps after successful handshaking, 8 data bits, without check bit.
  • The users can read and modify the parameters of the meter by PC software or HHU.

What are the communication specifications for Uplink Remote Communication on the RUVICK LGG360T?

The Uplink Remote Communication on the RUVICK LGG360T has the following specifications:

  • The communication way is optional.
  • Baud rate: 9600bps, 8 data bits, no check bit.
  • Conforming to DLMS/COSEM protocol.
  • Communication module is selectable, supporting GPRS/3G/4G/G3-PLC/PRIME-PLC/Mesh-RF etc.
  • It can communicate with the AMI system remotely.

What are the communication specifications for Downlink MBUS Communication on the RUVICK LGG360T?

The Downlink MBUS Communication on the RUVICK LGG360T has the following specifications:

  • The communication way is optional.
  • The communication way of energy meter and CIU/UIU is wired MBus.
  • The maximum communication cable size is 2.5 mm².
  • The longest communication distance is 150 meters.

What are the input/output functions supported by the auxiliary ports on the RUVICK LGG360T meter?

The RUVICK LGG360T meter supports Output function, such as the auxiliary port 19 and 20 are for the multi-function output, configurable to Active pulse output, Reactive pulse output, or Pulse per second output. The input/output function details are:

No. Auxiliary Port Description
1 15 and 16 To connect external breaker
2 17 and 18 To disconnect external breaker
3 19 and 20 For the calibration pulse output line
4 21 and 22 For the RS485 communication
5 23 and 24 For the MBUS communication
6 24 and 25 To detect the status of external breaker
7 24 and 26 To detect the status of the meter box
8 27 and 28 For the external signal input

What are the required attention matters for the RUVICK LGG360T upon opening the box?

The attention matters for the RUVICK LGG360T upon opening the box are:

  • Please contact the supplier as soon as possible if the meters have obvious damage mark caused by violent impact or dropping when the box is opened.
  • After getting out from the packing box, the meter should be placed on flat and safe plane, front up, stacked up less than 5 layers. The meter should be wrapped back into the original packing box if it is not installed for usage within a short period.
  • Please contact the supplier if product type or appearance of meter in the original packing box does not match.
  • Please contact the supplier as soon as possible and do not install or power on if the internal packing or external cover is damaged when the meter gets out from packing box. Please check the lead sealing of both sides is OK or not, for those meters lack of or without lead sealing, do not install for usage and please contact the supplier as soon as possible.

What are the installation instructions to follow for the RUVICK LGG360T meter?

The installation instructions for the RUVICK LGG360T meter are:

  • The installation of the meter requires an experienced electrician or professional person, and make sure that this manual has been read. During installation, if the meters have obvious damage marks caused by violent impact or dropping, please do not install or power on and contact the supplier as soon as possible.
  • The meter should be installed in a ventilated and dry place, making sure that the installation and usage are safe and reliable. The meter should be put into protection cabinet in case it may be damaged at foul or other unsafe place.
  • The meter has two upper hooks, 2 bottom installation holes, which can be fixed with M4 * 15 tapping screws. Making the holes ready on the bottom plate according to the back of the installation size, and the base should be fixed on object that is solid, fireproof and not easy to shake.
  • The meter should be wired correctly according to the wiring figure. It is recommended to use copper wire or copper connectors as the inlead of wiring terminal block, the screws of terminal block should be tightened to avoid bad contact or fire caused by fever of thin lead wire.
  • Wiring according to the terminal mark, the main circuit: 1-3 for the entrance and exit lines of phase A current wire, 2 is phase A voltage wire; 4-6 for the entrance and exit lines of phase B current wire, 5 is phase B voltage wire; 7-9 for the entrance and exit lines of phase C current wire, 8 is phase C voltage wire; 10-12 for the entrance and exit lines of neutral current wire, 11 is neutral wire.

What are the common malfunctions and their elimination methods for the RUVICK LGG360T?

The malfunction diagnosis and analysis list for the RUVICK LGG360T is:

Malfunction phenomenon Reason analysis Elimination method Notes
Unnormal communication Communication address, baud rate, checkout bits are not the same as the communication requirements of meter Configuring correct communication parameter according to instructions
Unnormal indication AC Voltage is ok or not, wiring confirms to wiring figure or not Checking wiring and voltage of grid
Clock error of overproof Battery is low or not Changing battery
Instantaneous parameters are incorrect AC voltage is ok or not, wiring confirms to wiring figure or not Checking wiring and voltage of grid

What are the recommended storage conditions for the RUVICK LGG360T?

Products should be transported and stored according to the rule of JB/T 9329-1999 <> and should not be impacted violently during transportation and sealing off. The storing place should be clean, the general environmental temperature is -40°C~55°C, the limit environmental temperature is -40°C~70°C, the limit environmental temperature at cold area is -45°C~70°C, relative humidity not more than 85%, and there are no enough harmful substances which cause corrosion in the air.


CLICK HERE TO DOWNLOAD RUVICK LGG360T (01) PDF DOCUMENT


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.