KUSSMAUL AUTO CHARGE T 091-80-32 (01) PDF MANUAL


Post questions, comments, reviews or page errors in the comment box below.

Click here to download KUSSMAUL AUTO CHARGE T 091-80-32 (01) PDF MANUAL


PDF Content Summary:

****** Page 1 ****** INSTRUCTION MANUAL AUTO CHARGE T AUTOMATIC BATTERY CHARGER TRANSIENT SUPPRESSED # : 091 -Bo-xx NOTE : This charger is designed for electric utility, circuit breaker operating applications and anywhere in a high electromagnetic field environment File: IM_091 -go-xx Revised By: Date: 4-1 5-2004 170 Cherry Avenue West Sayville, NY 11796 kussmaul.com INPUT IS vole, 50/60 Hz, eamps a YEAR WARRANTY KUSSMAUL ELECTRONICS ENERGIZED AND READY, WHEN SECONDS COUNT Ph: 800-346-0857 Fax: 631-567-5826 sales@kussmaul.com

****** Page 2 ****** INTRODUCTION The Auto Charge T, Model 091-80-xx battery charger is a compact completely automatic charger designed for installation in systems which require a transient suppressed char- ger. Ideal for electric utility applications to maintain the batteries used in high voltage circuit breaker trip circuits or wherever the charger may be exposed to high electromag- netic fields. Red, yellow and green indicators are provided to indicate whether the battery is fully charged, charging normally or receiving the maximum current. Construction of the Auto Charge T is extremely rugged to withstand shock and vibration. In addition the line power input lines and the charger output terminals are provided with filters and MOV transient suppressors. These suppression circuits permit the char- ger to meet ANSI/IEEE C37.90.1-1989. INSTALLATION The Auto Charge T Automatic Battery Charger should be installed in an area with adequate ventilation. A power cord is supplied for connection to 115 volts 60 Hz. 1. Mount the charger using the four holes provided for this. 2. Connect the wiring from the battery to the Output Terminal Strip. Spade lugs that have been securely crimped, or soldered, should be used. 3. Double check all wiring before proceeding. 4. Wire the A.C. power line cord to 115 volts. 5. Pilot light will light to show that the charger has power. 170 Cherry Avenue West Sayville, NY 11796 kussmaul.com KUSSMAUL ELECTRONICS ENERGIZED AND READY, WHEN SECONDS COUNT Ph: 800-346-0857 Fax: 631-567-5826 sales@kussmaul.com

****** Page 3 ****** INSTALLATION WIRING DIAGRAM AUTO CHARGE T TRANSIENT PROTECTED AUTOMATIC CHARGER o ooo POWE CONSTANT VOLTAG BATTERY I…….CHARGER OVERLOAD, LOW OR EXCESSIVE LOAD AXIMUM CURRENT, NORMAL aldilnlölöläb NEG pos BATTERY VEHICLE GROUND CHART IMPORTANT: Wire size is for a maxi- mum length of 20 feet. If wiring is to be longer, larger wiring is required. Additional information is available on request. CONNECTION BAT- BAT+ ITEM BATTERY NEGATIVE BATTERY POSITIVE DEFINITION NEGATIVE CHARGING LEAD FOR BATTERIES POSITIVE CHARGING LEAD FOR BATTERY # 1 WIRE SIZE 12 AWG 12 AWG

****** Page 4 ****** SPECIFICATION e OUTLINE SPECIFICATION CHART SPECIFICATIONS: Input: 115V 50/60Hz, 2 amps 091-80 6 Input Fuse: 5 amps Output: see chart Output Current: see chart Weight: 12 lbs 6.75 MODEL # 091-80-12 091-8004 091-80-32 091-80-36 091-8048 091-80-72 091-80-96 091-80-120 9/32″ DIA. 4 HOLES 4.25 AMPS VOLTAGE 12 12 6 5 4 3 2 1.5 1.2 12.75 6 12 24 32 36 48 72 96 120 UTO CHARGE 12.00 4.75 OUTLINE DRAWING 4

****** Page 5 ****** INSTALLATION RECORD DATE INSTALLED INSTALLED BY VEHICLE IDENTIFICATION VEHICLE OWNER WARRANTY POLICY All products of Kussmaul Electronics Company Inc. are warranted to be free of defects of material or workmanship. Liability is limited to repairing or replacing at our factory, without charge, any material or defects which become apparent in normal use within 3 years from the date the equipment was shipped. Equipment is to be returned, shipping charges prepaid and will be returned, after repair, shipping charges paid. Kussmaul Electronics Company, Inc. shall have no liability for damages of any kind to associated equipment arising from the installation and/or use of the Kuss- maul Electronics Company, Inc. products. The purchaser, by the acceptance of the equipment, assumes all liability for any damages which may result from its installation, use or misuse, by the purchaser, his or its employees or others. Members of Fire and Emergency Manufacturers and Service Association EMS Members of National Fire Protection Members of Fire Apparatus Manufacturers Made in USA 170 Cherry Avenue West Sayville, NY 11796 kussmaul.com Association Association NFPA KUSSMAUL ELECTRONICS ENERGIZED AND READY, WHEN SECONDS COUNT AMA Ph: 800-346-0857 Fax: 631-567-5826 sales@kussmaul.com