FREE ENGLISH HONEYWELL HOME TH2320U4006 P200 PROGRAMMABLE (01) PDF USER GUIDE

FREE ENGLISH HONEYWELL HOME TH2320U4006 P200 PROGRAMMABLE (01) PDF USER MANUAL

FREE ENGLISH HONEYWELL HOME TH2320U4006 P200 PROGRAMMABLE (01) PDF OWNER GUIDE

FREE ENGLISH HONEYWELL HOME TH2320U4006 P200 PROGRAMMABLE (01) PDF OWNER MANUAL

FREE ENGLISH HONEYWELL HOME TH2320U4006 P200 PROGRAMMABLE (01) PDF REFERENCE GUIDE

FREE ENGLISH HONEYWELL HOME TH2320U4006 P200 PROGRAMMABLE (01) PDF INSTRUCTION GUIDE

FREE ENGLISH HONEYWELL HOME TH2320U4006 P200 PROGRAMMABLE (01) PDF REFERENCE MANUAL

FREE ENGLISH HONEYWELL HOME TH2320U4006 P200 PROGRAMMABLE (01) PDF INSTRUCTION MANUAL

FREE ENGLISH HONEYWELL HOME TH2320U4006 P200 PROGRAMMABLE (01) PDF OPERATING INSTRUCTIONS


CLICK HERE TO DOWNLOAD HONEYWELL HOME TH2320U4006 P200 PROGRAMMABLE (01) PDF MANUAL

If this is not the document you want for this product, click here to see if we have any other documents for this product.

What is included in the FocusPRO P200 & S200 Series Thermostat package?

The package includes:
  • FocusPRO® P200 or S200 Series Thermostat
  • UWP Wall Plate
  • Decorative Cover Plate with J-Box Adapter
  • Screws and Anchors
  • 2 AA Batteries (with P200 models)
  • Thermostat Literature

What systems are compatible with the TH2110U4004 & TH2110WF4008 models?

These models are compatible with 24 VAC, single-stage heating and cooling systems including:
  • Heat pumps without auxiliary heat.
  • Gas/oil/electric forced air
  • Single stage cooling
  • Radiant Hydronic heat
  • Hot water coil
  • 750 MV (24 VAC needed at RC & C on S200 models. 750 MV to R and W)

What systems are compatible with the TH2320U4006 & TH2320WF models?

These models are compatible with most 24 VAC heating and cooling systems including:
  • Heat pumps with 1 or 2 compressor stages and auxiliary heat.
  • Dual fuel
  • 1 or 2 stage Gas/oil/electric forced air
  • 1 or 2 stage cooling
  • Radiant Hydronic heat hot water coil
  • 750 MV (24 VAC needed at RC & C on S200 models. 750 MV to R and W)
  • S terminals for C7089U1006 wired outdoor sensor (used for Aux Heat lockout or balance point on heat pump systems. Alternatively, smart model can use the app.)

What WiFi network can the Smart models (TH2110WF4008, TH2320WF) use?

Smart models TH2110WF4008 and TH2320WF can use a 2.4 GHZ or 5 GHZ WiFi network.

How do I install the UWP Wall Plate?

1. Before starting, turn the power off at the breaker box or switch. Open the package to find the UWP. 2. Position the UWP on the wall. Level and mark hole positions. 3. Using a 3/16″ bit, drill holes at marked positions and then lightly tap the supplied wall anchors into the wall using a hammer. 4. Pull the door open and insert the wires through the wiring hole of the UWP. 5. Place the UWP over the wall anchors. Insert and tighten mounting screws supplied with the UWP. Do not overtighten. Tighten until the UWP no longer moves. Close the door. Use the 3x supplied #6 1-1/2″ screws.

How do I install the Optional Cover Plate?

Use the Optional Cover Plate when you need to cover a paint gap from the old thermostat. 1. Separate the Cover Plate from the Mounting Plate. 2. Mount the Mounting Plate onto the wall or J-box using any of the 8 screw holes. Insert and tighten mounting screws supplied with the Cover Plate Kit. Do not overtighten. Make sure the Mounting Plate is level. 3. Attach the UWP by hanging it on the top hook of the Mounting Plate and then snapping the bottom of the UWP in place. 4. Snap the Cover Plate onto the Mounting Plate.

What are the power options for the thermostat?

  • AC Power: Insert R and C wires into designated terminals for AC power. Remove wires by pressing down on the terminal tabs. The C terminal is required for S200 Smart thermostats. If you do not have a C wire, you may use the THP9045A C-wire adapter (sold separately).
  • Battery Power (P200 Models Only): Insert 2 fresh AA batteries for primary or backup power.

How do I set the R Slider Tab?

Use the built-in jumper (R Slider Tab) to differentiate between one or two transformer systems:
  • If there is only one R wire, and it is connected to the R, Rc, or RH terminal, set the slider to the up position (1 wire).
  • If there is one wire connected to the R terminal and one wire connected to the Rc terminal, set the slider to the down position (2 wires).
Slider Tabs for U terminals should be left in place.

What do the wiring terminal designations mean?

Terminal Description
S C7089U1006 wired outdoor sensor connection (TH2320U4006 and TH2320WF models only)
S C7089U1006 wired outdoor sensor connection (TH2320U4006 and TH2320WF models only)
L/A – A Heat Pump fault input
O/B Changeover valve (reversing valve)
Y Compressor contactor (stage 1)
AUX-W2 Auxiliary heat / Heat (stage 2) (TH2320U4006 and TH2320WF models only)
Y2 Compressor contactor (stage 2) (TH2320U4006 and TH2320WF models only)
E Emergency Heat (TH2320U4006 and TH2320WF models only)
G Fan
W Heat (stage 1)
C 24VAC common. For 2-transformer systems, use Common wire from cooling transformer.
K To THP9045A C-Wire adapter if needed (S200 or P200)
U Not used on these models
U Not used on these models
R 24VAC power from heating transformer*
Rc 24VAC power from cooling transformer*
* Terminal can be jumped using Slider Tab.

How do I wire a Heat Only Gas or Oil Furnace?

Applicable to all P200 & S200 models. Set R/Rc switch UP.
  • Connect Furnace R to Thermostat R.
  • Connect Furnace W to Thermostat W.
  • Connect Furnace G to Thermostat G (Note: G is used for independent fan control only. Most heat-only gas or oil forced air systems do not use a fan [G] wire).
  • Connect Furnace C to Thermostat C (Required for S200, optional for P200 battery backup).

How do I wire a Cool Only system?

Applicable to all P200 & S200 models. Set R/Rc switch UP.
  • Connect Air Handler R to Thermostat R.
  • Connect Air Handler Y to Thermostat Y.
  • Connect Air Handler G to Thermostat G.
  • Connect Air Handler C to Thermostat C (Required for S200, optional for P200 battery backup).

How do I wire a Hot Water Boiler (Heat Only)?

Applicable to all P200 & S200 models. Set R/Rc switch UP.
  • Connect Boiler R (T) to Thermostat R.
  • Connect Boiler W (T) to Thermostat W.
  • Connect Boiler C to Thermostat C (Required for S200, optional for P200 battery backup).

How do I wire a 1H/1C Gas Furnace?

Applicable to all P200 & S200 models. Set R/Rc switch UP.
  • Connect Furnace R to Thermostat R.
  • Connect Furnace W to Thermostat W.
  • Connect Furnace Y to Thermostat Y.
  • Connect Furnace G to Thermostat G.
  • Connect Furnace C to Thermostat C (Required for S200, optional for P200 battery backup).

How do I wire a 2 Transformer System, 1H/1C: Oil Furnace with Air Conditioning?

Applicable to all P200 & S200 models. Set R/Rc switch DOWN.
  • Connect Air Handler Rc to Thermostat Rc.
  • Connect Air Handler Y to Thermostat Y.
  • Connect Air Handler G to Thermostat G.
  • Connect Air Handler C to Thermostat C (Required for S200, optional for P200 battery backup).
  • Connect Oil Furnace R to Thermostat R.
  • Connect Oil Furnace W to Thermostat W.

How do I wire a 2 Transformer System, Hot Water Heat with Air Conditioning (or Hot Water Coil)?

Applicable to all P200 & S200 models. Set R/Rc switch DOWN.
  • Connect Air Handler Rc to Thermostat Rc.
  • Connect Air Handler Y to Thermostat Y.
  • Connect Air Handler G to Thermostat G.
  • Connect Air Handler C to Thermostat C (Required for S200, optional for P200 battery backup).
  • Connect Boiler R to Thermostat R.
  • Connect Boiler W to Thermostat W.

How do I wire a 2H/1C Gas Furnace?

Applicable to TH2320 models only. Set R/Rc switch UP.
  • Connect Furnace R to Thermostat R.
  • Connect Furnace W to Thermostat W (Heat Stage 1).
  • Connect Furnace W2 to Thermostat AUX/W2 (Heat Stage 2).
  • Connect Furnace Y to Thermostat Y.
  • Connect Furnace G to Thermostat G.
  • Connect Furnace C to Thermostat C.

How do I wire a 2H/2C Gas Furnace?

Applicable to TH2320 models only. Set R/Rc switch UP.
  • Connect Furnace R to Thermostat R.
  • Connect Furnace W to Thermostat W (Heat Stage 1).
  • Connect Furnace W2 to Thermostat AUX/W2 (Heat Stage 2).
  • Connect Furnace Y to Thermostat Y (Cool Stage 1).
  • Connect Furnace Y2 to Thermostat Y2 (Cool Stage 2).
  • Connect Furnace G to Thermostat G.
  • Connect Furnace C to Thermostat C.

How do I wire Hot Water Heat with a Power Open Zone Valve?

Applicable to all P200 & S200 models. Set R/Rc switch UP. Requires a separate 24 VOLTS Transformer.
  • Connect Transformer R to Thermostat R.
  • Connect Zone Valve TH terminal to Thermostat W.
  • Connect Zone Valve TR terminal AND Transformer C terminal together (do not connect to thermostat).
  • Connect Transformer C to Thermostat C (Required for S200, optional for P200 battery backup).
  • Connect Zone Valve End Switch terminals to Boiler T terminals (R(T) and W(T)).

How do I wire Hot Water Heat with a Power Open/Power Closed Series 20 Zone Valve?

Applicable to all P200 & S200 models. Set R/Rc switch UP. Requires a separate Transformer.
  • Connect Transformer R terminal to Thermostat R AND Zone Valve terminal 1.
  • Connect Thermostat W to Zone Valve terminal 2.
  • Connect Transformer C terminal to Zone Valve terminal 3.
  • Connect Transformer C to Thermostat C (Required for S200, optional for P200 battery backup).
  • Connect Zone Valve terminals 4 and 5 to the auxiliary circuit for operating the boiler (see valve instructions).
  • Note: Thermostat must be configured for Radiant Heat with 0 (Zero) cool stages (ISU setting).

How do I wire a 1H/1C Heat Pump without Aux Heat?

Applicable to all P200 & S200 models. Set R/Rc switch UP.
  • Connect Heat Pump/Air Handler R to Thermostat R.
  • Connect Heat Pump/Air Handler O or B (Reversing Valve) to Thermostat O/B (Configure O/B setting in ISU 2060. Some use B, some use O).
  • Connect Heat Pump/Air Handler Y to Thermostat Y.
  • Connect Heat Pump/Air Handler G to Thermostat G.
  • Connect Heat Pump/Air Handler C to Thermostat C (Required for S200, optional for P200 battery backup).
  • Connect Heat Pump L (Fault Terminal, if present) to Thermostat L/A.
  • IMPORTANT: Do NOT connect any wire to W for heat pump applications! This can cause heat to run continuously.

How do I wire a 2H/1C Heat Pump with Electric Aux Heat?

Applicable to TH2320 models only. Set R/Rc switch UP.
  • Connect Heat Pump/Air Handler R to Thermostat R.
  • Connect Heat Pump/Air Handler O or B (Reversing Valve) to Thermostat O/B (Configure O/B setting in ISU 2060. Some use B, some use O).
  • Connect Heat Pump/Air Handler Y to Thermostat Y.
  • Connect Heat Pump/Air Handler G to Thermostat G.
  • Connect Heat Pump/Air Handler C to Thermostat C.
  • Connect Heat Pump/Air Handler AUX/W2 (Auxiliary Heat) to Thermostat AUX/W2.
  • Connect Heat Pump/Air Handler E (Emergency Heat, if separate) to Thermostat E. (Note: If Aux and E use the same heat strips, E is often not used. Configure ISU 2175 for separate Aux/E if needed).
  • Connect Heat Pump L (Fault Terminal, if present) to Thermostat L/A.
  • Optional: Connect S terminals to C7089U1006 Wired Outdoor Sensor for balance point/aux heat lockout.
  • IMPORTANT: Do NOT connect any wire to W for heat pump applications! This can cause heat to run continuously.

How do I wire a 3H/2C Heat Pump with Electric Aux Heat?

Applicable to TH2320 models only. Set R/Rc switch UP.
  • Connect Heat Pump/Air Handler R to Thermostat R.
  • Connect Heat Pump/Air Handler O or B (Reversing Valve) to Thermostat O/B (Configure O/B setting in ISU 2060. Some use B, some use O).
  • Connect Heat Pump/Air Handler Y to Thermostat Y (Compressor Stage 1).
  • Connect Heat Pump/Air Handler Y2 to Thermostat Y2 (Compressor Stage 2).
  • Connect Heat Pump/Air Handler G to Thermostat G.
  • Connect Heat Pump/Air Handler C to Thermostat C.
  • Connect Heat Pump/Air Handler AUX/W2 (Auxiliary Heat) to Thermostat AUX/W2.
  • Connect Heat Pump/Air Handler E (Emergency Heat, if separate) to Thermostat E. (Note: If Aux and E use the same heat strips, E is often not used. Configure ISU 2175 for separate Aux/E if needed).
  • Connect Heat Pump L (Fault Terminal, if present) to Thermostat L/A.
  • Optional: Connect S terminals to C7089U1006 Wired Outdoor Sensor for balance point/aux heat lockout.
  • IMPORTANT: Do NOT connect any wire to W for heat pump applications! This can cause heat to run continuously.

How do I wire a Dual Fuel, 2H/1C Heat Pump?

Applicable to TH2320 models only. Set R/Rc switch UP. Assumes separate boards for Heat Pump and Furnace.
  • Connect Heat Pump/Furnace R to Thermostat R.
  • Connect Heat Pump O or B (Reversing Valve) to Thermostat O/B (Configure O/B setting in ISU 2060).
  • Connect Heat Pump Y to Thermostat Y.
  • Connect Heat Pump G to Thermostat G.
  • Connect Heat Pump C to Thermostat C.
  • Connect Furnace W to Thermostat AUX/W2 (This is the fossil fuel backup heat).
  • Connect Heat Pump L (Fault Terminal, if present) to Thermostat L/A.
  • Optional: Connect S terminals to C7089U1006 Wired Outdoor Sensor for balance point.
  • IMPORTANT: The W terminal connection is specifically for the furnace backup in a dual fuel setup and connects to AUX/W2. Do NOT connect any other wire labeled W directly to the W terminal on the thermostat for heat pump applications.

How do I wire a Dual Fuel, 3H/2C Heat Pump?

Applicable to TH2320 models only. Set R/Rc switch UP. Assumes separate boards for Heat Pump and Furnace.
  • Connect Heat Pump/Furnace R to Thermostat R.
  • Connect Heat Pump O or B (Reversing Valve) to Thermostat O/B (Configure O/B setting in ISU 2060).
  • Connect Heat Pump Y to Thermostat Y (Compressor Stage 1).
  • Connect Heat Pump Y2 to Thermostat Y2 (Compressor Stage 2).
  • Connect Heat Pump G to Thermostat G.
  • Connect Heat Pump C to Thermostat C.
  • Connect Furnace W to Thermostat AUX/W2 (This is the fossil fuel backup heat).
  • Connect Heat Pump L (Fault Terminal, if present) to Thermostat L/A.
  • Optional: Connect S terminals to C7089U1006 Wired Outdoor Sensor for balance point.
  • IMPORTANT: The W terminal connection is specifically for the furnace backup in a dual fuel setup and connects to AUX/W2. Do NOT connect any other wire labeled W directly to the W terminal on the thermostat for heat pump applications.

How do I mount the thermostat onto the UWP Wall Plate?

1. Push excess wire back into the wall opening. 2. Close the UWP door. It should remain closed without bulging. 3. Align the UWP with the thermostat and push gently until the thermostat snaps into place. 4. Turn the power on at the breaker box or switch.

How do I set up an S200 Smart Thermostat?

S200 Smart thermostats can be set up using the Resideo Pro app. Scan the QR code provided in the manual to download the app. After initial physical installation and power-up, the thermostat will ask if you wish to perform setup on the device or by using the app.
  • Using App: Select this option, open the Resideo Pro app and follow the instructions.
  • On Device: Select this option and follow the steps in the “Configure the Thermostat” section.

How do I access the Installer Menu?

1. Press and hold the bottom left button (Menu/Back) and Up arrow button simultaneously for 5 seconds. 2. The INSTALLER MENU options will appear. Press ↑ or ↓ to cycle through the options. 3. When the desired menu option (e.g., ISU, TEST) is displayed, press SELECT. 4. To return to the Home screen, press the EXIT button (upper left) or wait for the thermostat to time out.

What are the options in the Installer Menu?

  • ISU: Installer Setup options (configure thermostat parameters).
  • TEST: Installer Test options (test system components like heat, cool, fan).
  • INFO: Displays a code used by the Resideo technical support team when needed.
  • RSET: Reset options (Reset Schedule, WiFi [S200], or Perform a Factory Reset).
  • REV: Displays thermostat’s Firmware version (STAT) and WiFi version (WiFi).

How do I configure the thermostat using the ISU (Installer Setup Options)?

1. Access the Installer Menu (Press and hold bottom left button and Up arrow for 5 seconds). 2. Press ↑ or ↓ until ISU is displayed, then press SELECT. 3. The display shows the ISU number on the left and the ISU setting on the right. 4. Press ↑ or ↓ to change the setting for the currently displayed ISU number. 5. After choosing the correct setting, press NEXT to advance to the next ISU setting. 6. To finish setup, press the SAVE & EXIT button; this will save your settings and return to the Home screen.

What are the Installer Setup Options (ISU)?

Depending on system settings, not all options may be available. Factory defaults are in bold.
#ISUISU NameISU Options
1040Scheduling options1 = 1 week, 2 = 5-2 Programmable, 3 = 5-1-1 Programmable, 4 = 7-Day Programmable
1050Temperature Indication ScaleF = Fahrenheit, C = Celsius
1060Outdoor Sensor (TH2320 models only)0 = None, 1 = Wired Outdoor Sensor, 2 = Internet Weather (TH2320WF)
2000Heating System Type1 = Conventional Forced Air Heat, 2 = Heat Pump, 3 = Radiant Heat, 5 = None (Cool Only)
2010Heating Equipment TypeConventional: 1 = Standard Gas, 2 = High Efficiency Gas, 3 = Oil, 4 = Electric, 5 = Hot Water Fan Coil; Heat Pump: 7 = Air to Air, 8 = Geothermal; Radiant: 9 = Hot Water, 12 = Steam
2060Reversing Valve O/B0 = O (O/B on Cool), 1 = B (O/B on Heat)
2070Compressor Stages0, 1, 2 (Only 1 stage on TH2110)
2071Heat Stages/Backup Heat StagesHeat: 1, 2; Backup Heat: 0, 1 (TH2320 only)
2110Fan Control in Heat (if 2010 = 4 or 5)1 = Equipment Controls Fan, 2 = Thermostat Controls Fan
2175Aux/E terminal control (TH2320 only)0 = Drive both Aux & E together, 1 = Aux and E independent
2180Backup Heat Source (HP Only, TH2320)31 = Electric Forced Air, 32 = Standard Gas, 33 = High Eff. Gas, 34 = Oil/HW Fan Coil, 35 = HW Radiant, 36 = Other
2185Emergency Heat Source (TH2320 only)(Same options as 2180)
3000System Changeover0 = Hidden (Manual only), 1 = Enabled (Automatic)
3015Auto Changeover Differential0 °F to 5 °F (0.0 °C to 2.5 °C)
3020Finish With High Heat Stage (TH2320 only)0 = No, 1 = Yes
3021Finish With High Cool Stage (TH2320 only)0 = No, 1 = Yes
3090Backup Heat Droop (TH2320 only)[0] = Comfort, 2 °F to 15 °F (1.0 °C to 7.5 °C). (Comfort only if ISU 2180 = Electric)
3110Upstage Timer for Backup Heat (TH2320 only)0 = Off, 1=30min…15=16hrs (See manual for full list)
3120Compressor Lockout / Balance Point (TH2320 only, 1060=1 or 2)Off, -15°F to 60°F (-26.0°C to 15.5°C)
3121Outdoor Lockout Backup Heat (TH2320 only)Off, 5°F to 65°F (-15.0°C to 18.5°C)
3125Lockout Fan after a Cool call[0] = Off, 1=5min…24=120min (See manual for full list)
3140Compressor Cycle Rate (Stage 1)1-6 (CPH)
3141Compressor Cycle Rate (Stage 2) (TH2320 only)1-6 (CPH)
3150Heating Cycle Rate (Stage 1)1-12 (CPH)
3151Heating Cycle Rate (Stage 2) (TH2320 only)1-12 (CPH)
3160Heating Cycle Rate Auxiliary Heat (TH2320 only)1-12 (CPH)
3165Heating Cycle Rate Emergency Heat (TH2320 only)1-12 (CPH)
3240Compressor Protection0 = Off, 1 = 5 minutes
4090Adaptive Intelligent Recovery0 = No, 1 = Yes
4100Maximum Cool Setpoint50°F to 99°F (99°F) / 10.0°C to 37.0°C (37.0°C)
4101Minimum Cool Setpoint50°F to 99°F (50°F) / 10.0°C to 37.0°C (10.0°C)
4102Maximum Heat Setpoint32°F to 90°F (90°F) / 0.0°C to 32.0°C (32.0°C)
4103Minimum Heat Setpoint32°F to 90°F (40°F) / 0°C to 32.0°C (4.5°C)
4110Keypad Lockout0 = Disabled, 1 = Enabled
7020Number of Air Filters0-2
7110Air Filter 1 Replacement Reminder0 = Off, Run Time Days (10-150), Calendar Days (30-75), Calendar Months (3-15)
7111Air Filter 2 Replacement Reminder(Same options as 7110)
14003Backlighting0 = On Demand, 1 = Continuous (C-wire needed)
14004Backlight brightness1-5 (Only if 14003=1)
14005Idle screen selection0 – Minimum Info, 1 – Setpoint shown, 2 – Maximum display
14006Idle screen message center (WiFi only)1 – Time, 2 – Outdoor Temp, 3 – Outdoor Humidity, 4 – Indoor Humidity (Options 2/3 need ISU 1060 = Internet or Wired)
14007Home screen message center (WiFi only)1 – Time, 2 – Outdoor Temp, 3 – Outdoor Humidity, 4 – Indoor Humidity (Options 2/3 need ISU 1060 = Internet or Wired)
14010Clock format12/24
14015Daylight Saving Time0 = Off, 1 = On
14020Temperature Display Offset-3 to 3°F (0) / -1.5 to 1.5°C (0)

How do I perform an Installer Test?

1. Access the Installer Menu (Press and hold bottom left button and Up arrow for 5 seconds). 2. Press ↑ or ↓ until TEST is displayed, then press SELECT. 3. The display shows the current test mode (e.g., Heat). 4. To test the displayed mode, press ↑. The system should turn on (e.g., Heat Stage 1 On). For multi-stage systems, pressing ↑ again will call for the next stage (e.g., Heat Stage 2 also On). 5. Press NEXT to advance to the next test mode (Heat, Cool, Em Heat, Fan). 6. Press EXIT after testing is done. System Test Status (TH2320 models show additional stages):
System TestSystem Status
Heat0 All Off
1 Heat Stage 1 On
2 Heat Stage 2 also On (TH2320 only)
3 Heat Stage 3 also On (TH2320 only)
Cool0 All Off
1 Cool Stage 1 On
2 Cool Stage 2 also On (TH2320 only)
Em Heat0 All Off
1 Em Heat On
Fan0 Fan Off
1 Fan On

How do I access and use the User Menu?

1. Press the Menu button. 2. Press ↑ or ↓ to cycle through User Menu options. Active Alerts or Reminders will appear first if present. 3. When the desired menu option is displayed, press SELECT. 4. To EXIT and return to the Home screen, press the EXIT button (upper left) or wait for the thermostat to time out. User Menu Options:
  • SCHEDULE: Turn schedule on or off or set/edit schedule settings.
  • APP: Use the app (S200 models).
  • WIFI: Turn WiFi On or Off (S200 models).
  • TEMP: Display outdoor* or indoor temperature (*Outdoor option only shown if ISU 1060 is set to use a wired outdoor sensor or Internet).
  • DATE: Set Date.
  • TIME: Set Time.
  • LOCK**: Change lockout status (OFF, FULL or PART). Partial lockout allows temporary setpoint change only. (**Lockout option only shown if ISU 4110 is set to Lockout Enabled).

How do I set the Time?

Note: Time and date are set automatically when an S200 Smart thermostat is connected to WiFi and registered. Manual setting may be needed otherwise or for P200 models. 1. Press MENU on the thermostat. 2. Press ↑ or ↓ to go to TIME and press SELECT. 3. Press ↑ or ↓ to choose 12- or 24-hour clock format and press NEXT. 4. Press ↑ or ↓ to adjust the hour and press NEXT. 5. Press ↑ or ↓ to adjust the minute and press SAVE & EXIT.

How do I set the Date?

Note: Time and date are set automatically when an S200 Smart thermostat is connected to WiFi and registered. Manual setting may be needed otherwise or for P200 models. 1. Press MENU on the thermostat. 2. Press ↑ or ↓ to go to DATE and press SELECT. 3. Press ↑ or ↓ to choose YEAR and press NEXT. 4. Press ↑ or ↓ to choose MONTH and press NEXT. 5. Press ↑ or ↓ to choose DATE and press SAVE & EXIT.

How do I change the System Operation Mode?

1. Press the MODE button to cycle to the next available System mode. 2. Cycle through the modes until the desired System mode is displayed. Available System modes vary by model and system settings, but may include:
  • AUTO: Thermostat selects heating or cooling as needed (if enabled in ISU 3000).
  • HEAT: Controls only the heating system.
  • COOL: Controls only the cooling system.
  • EM HEAT: Emergency Heat (for heat pump systems). Controls only backup heat.
  • OFF: Heating and cooling systems are off.

How do I change the Fan Operation Mode?

1. Press the FAN button to cycle to the next available Fan mode. 2. Cycle through the modes until the desired Fan mode is displayed. Available Fan modes vary with system settings, but may include:
  • AUTO: Fan runs only when the heating or cooling system is on (default for most systems).
  • ON: Fan runs continuously.
  • CIRC: Fan runs intermittently, about 33% of the time, to circulate air.

How does Auto Changeover work?

When the thermostat is set to Auto Changeover mode (System Mode set to AUTO), it maintains separate Heat and Cool setpoints. 1. Ensure the thermostat is in AUTO mode (press MODE until AUTO shows). Press SAVE (center left button). 2. Press ↑ or ↓. The upper right display shows either HEAT TO or COOL TO flashing, along with the corresponding setpoint. 3. Use ↑ or ↓ to adjust the displayed setpoint (Heat or Cool). 4. If you want to adjust the other setpoint (e.g., adjust Cool when HEAT TO is flashing), press the MODE button. This will switch the flashing text between HEAT TO and COOL TO and allow adjustment of the other setpoint. The thermostat will automatically run heating or cooling as needed to keep the room temperature between the Heat and Cool setpoints. A differential (set in ISU 3015) prevents rapid switching between modes.

Can the Heat and Cool setpoints be the same in Auto Changeover mode? What is the differential?

Yes, the Heat and Cool setpoints can technically be set to the same temperature. However, most users prefer a 2-3 degree difference. To prevent the system from constantly switching between heating and cooling if the setpoints are close or the same, the thermostat uses an Auto Changeover Differential (set in ISU 3015, default 0°F/0°C but typically needs to be higher, e.g., 3°F/1.5°C). If the system last ran Heat, the temperature must rise above the Cool setpoint by the differential amount before it switches to Cool mode. If it last ran Cool, the temperature must drop below the Heat setpoint by the differential amount before it switches to Heat mode. This prevents short cycling between heating and cooling.

How do I view and understand Alerts?

When an alert is active, an alert icon (triangle with exclamation mark) appears in the lower part of the display. 1. Press MENU. Active alerts will be the first menu items shown. Use ↑ or ↓ if needed to scroll to the alert message. 2. Press SELECT to display the alert number (e.g., 405). 3. If there is more than one active alert, pressing NEXT allows you to view additional alert numbers. 4. Alerts cannot be dismissed directly (except for “Set Time and Date” by setting the time/date). They clear automatically when the condition is resolved (e.g., replacing batteries clears alert 405/407). Press EXIT to return to the home screen. Some alerts require homeowner action (like replacing batteries), while others may need professional service. Alert Meanings:
Alert NumberAlert Meaning
405Thermostat batteries are low. Replace batteries.
407Thermostat batteries are critically low. Replace batteries.
164Heat Pump Fault. Heat pump is energizing the L terminal to indicate a fault.
170Thermostat Memory Failure. Internal problem with the thermostat memory.
171Set Time and Date. To clear this alert, enter the Menu, and follow steps to set the time and date.
173Internal Sensor Error. Issue with the built-in temperature sensor.
178Wired Outdoor Sensor Error. Check wires and connections to outdoor sensor.
388Register online (For Smart models)
399WiFi, internet connection lost *
400WiFi, no signal *
602Internal humidity sensor error
607WiFi network error *
* WiFi alerts will not be shown when WiFi is set to Off under the WiFi menu.

How do I view and handle Reminders?

When a reminder is active (e.g., Replace Air Filter), a reminder icon (calendar page) appears in the lower part of the display. 1. Press MENU. Active reminders (after any active alerts) will be the next menu items shown. Use ↑ or ↓ if needed. 2. Press SELECT to display the reminder (e.g., REPL). 3. Once selected, the reminder message scrolls across the screen. 4. Press DISMISS to reset the reminder timer, or press EXIT to return to the home screen without resetting it. 5. If there is more than one active reminder, press NEXT after selecting one to view others that have not been reset.

How does the Program Schedule work?

You can program four time periods per day, with potentially different settings for weekdays and weekends (depending on ISU 1040 setting). Using the schedule helps save energy. The periods are:
  • WAKE: Set the time you wake up and the desired temperature until you leave.
  • AWAY: Set the time you leave home and the desired energy-saving temperature while away.
  • HOME: Set the time you return home and the desired temperature until bedtime.
  • SLEEP: Set the time you go to bed and the desired energy-saving temperature overnight.
Note: S200 users registered with the Resideo App can use Geofencing instead of a time-based schedule.

How do I adjust the program schedules?

1. Press MENU, then press ↑ or ↓ until SCHED is displayed. 2. A square appears around ON or OFF. To use the schedule, ensure ON is selected (use ↑ or ↓ if needed). Press SELECT to edit the schedule (or EXIT to leave). 3. If editing, the day(s) being edited will flash. Press SELECT to confirm the day(s). (Depending on ISU 1040, it might be Mon-Fri, Sat, Sun, or individual days). 4. The word Wake will flash. Press NEXT. Press ↑ or ↓ to turn this specific period (Wake) ON or OFF. Press NEXT. 5. If the period is ON, the time will flash. Press ↑ or ↓ to adjust the start time for this period. Press NEXT. 6. The Heat setpoint will flash. Press ↑ or ↓ to adjust the Heat temperature for this period. Press NEXT. 7. The Cool setpoint will flash. Press ↑ or ↓ to adjust the Cool temperature for this period. Press NEXT. 8. The display will move to the next schedule period (Away, Home, Sleep). Repeat steps 4-7 for each period. 9. After setting all periods for the selected day(s), repeat the process for other days if necessary (depending on schedule type). 10. Press the SAVE & EXIT button (upper left) to save all changes and return to the home screen. To quickly change just one setting within the schedule, navigate to that setting, make the change, and press SAVE & EXIT.

How do I temporarily override the program schedule?

1. Press ↑ or ↓ to adjust the temperature to your desired setting. 2. “Hold Until [Time]” will appear, indicating the override is temporary. No further action is needed. The new temperature will be held until the start time of the next scheduled period. 3. To cancel the Temporary Hold early, press and release the HOLD button until CANCEL HOLD is displayed, or adjust the schedule.

How do I permanently override the program schedule?

1. Press ↑ or ↓ to adjust the temperature to your desired setting. 2. Press and release the HOLD button until HOLD PERMANANTLY is displayed. The new temperature will be held indefinitely. 3. To cancel the Permanent Hold and resume the schedule, press and release the HOLD button until CANCEL HOLD is displayed.

How do I use the Keypad Lockout feature?

The Keypad Lockout option is only available in the User Menu if the installer enabled it (ISU 4110 = 1). 1. Press Menu on the thermostat. 2. Press ↑ or ↓ to go to LOCK. Press SELECT. 3. Press ↑ or ↓ to choose the desired lockout level: * OFF: Unlocked, full access allowed. * PART: Partial lockout. Allows only temperature changes. Schedule and settings cannot be accessed. * ON: Full lockout. No changes can be made using the thermostat buttons. 4. Press SELECT to confirm the choice. 5. Press the SAVE & EXIT button.

How do I unlock the Keypad?

1. If the keypad is locked (Partially or Fully), the word UNLOCK will appear next to the left center button when you press any button. 2. Press the left center button (where UNLOCK appears). The display will show “0—” in the upper part. 3. Enter the password “1234”. Press ↑ or ↓ to change the first digit (‘0’) to ‘1’. 4. Press SELECT. 5. Repeat step 3 and 4 for the remaining digits: set the second digit to ‘2’ and press SELECT, set the third digit to ‘3’ and press SELECT, set the fourth digit to ‘4’ and press SELECT. 6. Once all four digits are entered correctly and SELECT is pressed the final time, the keypad will unlock. 7. If you enter an incorrect digit, press BACK to go back one step and re-enter the correct digit, then press SELECT.

What is Adaptive Intelligent Recovery (AIR)?

Adaptive Intelligent Recovery (AIR), also known as “Learning”, is a comfort feature (enabled/disabled in ISU 4090). When active, “Recovery” appears on the display below the room temperature as the thermostat transitions from an energy-saving setpoint (like Away or Sleep) to a comfort setpoint (like Wake or Home). Over time, the thermostat learns how long your heating or cooling system takes to reach the desired temperature. It then starts the heating or cooling system earlier than the scheduled time, ensuring the indoor temperature matches the setpoint exactly *at* the scheduled time (e.g., the house is already at 70°F when the Wake period begins at 6:00 AM).

What is the built-in compressor protection feature?

This feature prevents damage to your cooling system’s (or heat pump’s) compressor that could occur if it is restarted too quickly after shutting down. The thermostat enforces a minimum off-time (typically 5 minutes, set in ISU 3240). During this waiting period, the display will show the message “Waiting For Equipment” below the room temperature reading, and the system will not start cooling (or heating in heat pump mode). Once the safe wait time has elapsed, the message disappears, and the system can start normally (“Cool On” or “Heat On” will appear).

How do I replace the accent piece on the thermostat?

This applies to FocusPRO N100, P200, and S200 models, often used for private labeling. 1. Gently pull the existing accent piece (the bottom curved piece, often with branding) away from the main body of the thermostat. It should detach. 2. Align the new accent piece with the bottom of the thermostat. 3. Push the new accent piece gently until it snaps securely into place.

How do I replace the batteries (P200 Models Only)?

The thermostat display will indicate when batteries are low (Alert 405 or 407). 1. Grasp the thermostat body and gently pull it straight away from the UWP wall plate it’s mounted on. 2. Turn the thermostat over and remove the old AA batteries. 3. Insert two new, fresh AA alkaline batteries, observing the polarity markings (+/-) inside the battery compartment. 4. Align the thermostat back onto the UWP wall plate. 5. Push gently until the thermostat snaps back into place.

Troubleshooting: The display is blank.

  • Check the circuit breaker for the HVAC system and reset if necessary.
  • Make sure the power switch for the heating & cooling system is on.
  • Make sure the furnace or air handler access door is closed securely.
  • For P200 models: Make sure fresh AA alkaline batteries are correctly installed.
  • For S200 models (or P200 using C-wire): Ensure the C-wire connection is secure and providing 24VAC.

Troubleshooting: Heating or cooling does not run.

  • Check the display: “HEAT ON” should appear in the lower right when heating is called for, “COOL ON” when cooling is called for.
  • If “WAITING FOR EQUIPMENT” is displayed, the compressor protection delay is active. Wait 5 minutes.
  • Verify System Mode: Press MODE to ensure it’s set to HEAT or COOL as desired (or AUTO if enabled).
  • Check Setpoint vs. Room Temp: Press ↑ or ↓. The upper right shows the setpoint, the center shows the room temperature. Ensure the setpoint requires heating (setpoint > room temp) or cooling (setpoint < room temp).
  • Check circuit breaker and reset if necessary.
  • Make sure the power switch at the heating & cooling system is on.
  • Make sure the furnace/air handler door is closed securely.

Troubleshooting: Heat or Aux Heat runs when Cooling should be running.

  • Heat Pump Systems Only: Verify the Reversing Valve setting (ISU 2060 – O/B). Some heat pumps energize the valve for heating (B setting), others for cooling (O setting). Ensure the ISU setting matches your equipment.
  • Check for Shorted Wires: Inspect wiring at the thermostat UWP wall plate. Look for any exposed sections of wires that might be touching each other, particularly between heating (W, W2, E) and cooling (Y, Y2) or power (R, Rc) terminals.

Troubleshooting: Heat or Aux heat runs when there is no call for heat or cooling.

  • Verify Display: Ensure the display does not indicate HEAT ON, COOL ON, or AUX HEAT ON.
  • Heat Pump Systems: Verify that no wire is connected to the W terminal on the UWP. The W terminal is generally NOT used for heat pump systems (Aux/backup heat connects to AUX/W2 or E). Check wiring diagrams.
  • Check for Shorted Wires: Inspect wiring at the thermostat UWP wall plate. Look for exposed wire sections that might be shorted, potentially causing the heat circuit to be energized improperly.

Troubleshooting: Cannot change setpoint to the desired temperature.

  • Check Keypad Lockout: If UNLOCK appears next to the left center button when you try to change the setpoint, the keypad is locked. Follow the unlocking procedure (password 1234).
  • Check System Mode: Ensure the thermostat is in the correct mode (Heat, Cool, Auto, Em Heat) for the setpoint you are trying to adjust. Press the MODE button to cycle if needed.
  • Check Temperature Ranges: Verify the desired setpoint is within the allowed range for the current mode:
    • Heat or Em Heat: 32 °F to 90 °F (0 °C to 32.0 °C)
    • Cool: 50 °F to 99 °F (10.0 °C to 37.0 °C)
  • Check Setpoint Limits (ISU): The installer may have configured minimum and maximum setpoint limits (ISU 4100-4103) to restrict the range for energy efficiency. If you cannot reach the full range above, these limits might be active.

Troubleshooting: “WAITING FOR EQUIPMENT” is shown on the display under the room temperature.

This message indicates that the built-in compressor protection feature is engaged. The thermostat is waiting for a short period (usually 5 minutes) before starting the compressor to prevent potential damage from short-cycling. Wait a few minutes, the message should disappear, and the system should start normally.

What are the temperature setting ranges for the thermostat?

  • Heat: 32 °F to 90 °F (0 °C to 32.0 °C)
  • Cool: 50 °F to 99 °F (10.0 °C to 37.0 °C)

What are the operating environment specifications?

  • Working Ambient Temperature: 32 °F to 120 °F (0 °C to 48.9 °C)
  • Operating Ambient Temperature: 32 °F to 102 °F (0 °C to 38.9 °C)
  • Shipping Temperature: -20 °F to 120 °F (-28.9 °C to 48.9 °C)
  • Operating Relative Humidity: 5% to 90% (non-condensing)

What are the physical dimensions?

  • Thermostat: 5-1/8″ W x 3-7/16″ H x 1-3/16″ D (130 mm W x 87 mm H x 29.5 mm D)
  • Cover Plate: 6-1/16″ W x 4-3/5″ H (154mm W x 117 mm H)

What are the electrical ratings?

  • Device Input Power: AC 1.1 VA, 24 VAC nominal (20-30 VAC), 60 Hz
  • Batteries (P200 Models only): Two 1.5V AA batteries
  • Load Ratings (Running Current):
TerminalVoltage (60Hz)Running Current
W Heating24 VAC0.02-1.0 A
W Heating750 mV DC100 mA DC
W2 (Aux) Heating24 VAC0.02-1.0 A
E Emergency Heat24 VAC0.02-0.5 A
Y Compressor Stage 124 VAC0.02-1.0 A
Y2 Compressor Stage 224 VAC0.02-1.0 A
G Fan24 VAC0.02-0.5 A
O/B Changeover24 VAC0.02-0.5 A
L/A Input24 VAC0.02-0.5 A
* Note: Smart thermostats (S200) can utilize 750 MV heat wired to R and W but still require 24 VAC power at Rc and C terminals to operate.

What are the important safety and environmental notices?

  • CAUTION: ELECTRICAL HAZARD: Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
  • CAUTION: EQUIPMENT DAMAGE HAZARD: Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
  • CAUTION: MERCURY NOTICE: If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.
  • CAUTION: ELECTRONIC WASTE NOTICE: The product and batteries should not be disposed of with other household waste. Check for the nearest authorized collection centers or authorized recyclers. The correct disposal of end-of-life equipment will help prevent negative consequences for the environment and human health.

Where can I find customer assistance?

For assistance with this product, please visit customer.resideo.com or call Resideo Customer Care toll-free at 1-800-633-3991.

Where can I find warranty information?

For Warranty information go to honeywellhome.com/support. The product comes with a 5-year limited warranty.

Where can I find the FCC statement?


CLICK HERE TO DOWNLOAD HONEYWELL HOME TH2320U4006 P200 PROGRAMMABLE (01) PDF MANUAL


Leave comments, questions, reviews, tips, tricks, hacks or page errors below. Account not required.