DIXELL XR570C (01) PDF SUMMARY:
How do I display the target set point?
To display the target set point, push and immediately release the SET key; the display will show the Set point value. Push and immediately release the SET key or wait for 5 seconds to display the probe value again.
How do I start a manual defrost?
To start a manual defrost, push the DEF key for more than 2 seconds.
How do I see the max stored temperature?
To see the max stored temperature:
- Press and release the down arrow key.
- The “Hi” message will be displayed followed by the maximum temperature recorded.
- By pressing the down arrow key or waiting for 5 seconds, the normal display will be restored.
How do I see the min stored temperature?
To see the min stored temperature:
- Press and release the up arrow key.
- The “Lo” message will be displayed followed by the minimum temperature recorded.
- By pressing the up arrow key or waiting for 5 seconds, the normal display will be restored.
How do I reset the max and min temperature recorded?
To reset the stored temperature, when max or min temperature is displayed, press SET key until “rST” label starts blinking.
How do I change the setpoint?
To change the Set Point:
- Push the SET key for 2 seconds to change the Set point value.
- The value of the set point will be displayed and the and LEDs start blinking.
- To change the Set value push the up or down arrows within 10s.
- To memorize the new set point value push the SET key again or wait 10s.
How do I enter in parameter list “Pr1”?
To enter the parameter list “Pr1” (user accessible parameters) operate as follows:
- Enter the Programming mode by pressing the Set and UP key for few seconds ( and start blinking).
How do I enter in parameter list “Pr2”?
To enter in the parameter list “Pr2” (installer level) operate as follows: To access parameters in “Pr2” a security code is required.
- To enter in “Pr1” level.
- Select “Pr2” parameter and press the “SET” key.
- The “PAS” flashing message is displayed, shortly followed by “0 – -“ with a flashing zero.
- Use up or down arrows to input the security code in the flashing digit; confirm the figure by pressing “SET”. The security code is “321”.
- If the security code is correct the access to “Pr2” is enabled by pressing “SET” on the last digit.
Each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing ´SETµ + UP. When a parameter is present in “Pr1” LED is on.
How do I change the parameter value?
To change the parameter’s value operate as follows:
- Enter the Programming mode.
- Select the required parameter with up or down arrows.
- Press the “SET” key to display its value ( and LED starts blinking).
- Use up or down arrows to change its value.
- Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key. The new programming is stored even when the procedure is exited by waiting for the time-out.
How do I lock the keyboard?
- Keep pressed for more than 3 s the down and up arrow keys.
- The “POF” message will be displayed and the keyboard is locked. At this point it is only possible the viewing of the set point or the MAX or Min temperature stored.
How do I unlock the keyboard?
Keep pressed together for more than 3s the down and up arrow keys.
How do I use the Stand-by function?
If the stand–by function is enabled (OnF = 1), by holding pressed the SET key for 5s., the instrument shows “OFF”. The stand–by function switches OFF all the relays and stops the regulation. During the stand by if a monitoring system is connected, it does not record the instrument data and alarms.
When the instrument is under Stand-by, all the relays are under power supply. Don’t connect any loads to the normal closed contact of the relays.
How do I display the current hour and date?
- Enter parameter list “Pr1” (press SET +UP for some seconds).
- The controller displays the parameter rtc.
- Press SET key, the controller displays the following labels:
- Hur (hour) and the current hour
- Min (Minute) and the current minutes
- dAy (day) and the current day. Mon (Monday), Tue (Tuesday), Wed (Wednesday), Thu (Thursday), Fri (Friday), Sat (Saturday), Sun (Sunday)
- Press UP key or wait for 5 seconds to go back to normal temperature display.
How do I program hour, date and holiday?
- Enter parameter list “Pr1” (press SET +UP for some seconds).
- The controller displays the parameter rtc.
- Press SET key, the controller displays hour and date.
- By pressing SET it will be possible to program the current hour, date and the 3 week end days.
- Press UP key or wait for 5 seconds to go back to normal temperature display.
How do I install and mount the controller?
The controller shall be mounted on panel, in a 29×71 mm hole, and fixed using the special bracket supplied. The temperature range allowed for correct operation is 0 to 60°C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by the cooling holes.
How do I make probe connections?
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.
How does the Hot Key work to download data to the instrument?
- Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, insert the “Hot Key” and then turn the Controller ON.
- Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory, the “DoL” message is blinking. After 10 seconds the instrument will restart working with the new parameters.
- Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON again.
At the end of the data transfer phase the instrument displays the following messages: “end “ for right programming – The instrument starts regularly with the new programming. “err“ for failed programming – In this case turn the unit off and then on if you want to restart the download again or remove the “Hot key” to abort the operation.
How do I upload data from the instrument to the Hot Key?
- Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if present, then turn it ON again.
- When the Controller is ON, insert the “Hot key” and push down arrow key, the “uPL” message appears.
- Push “SET“ key to start the UPLOAD, the “uPL” message is blinking.
- Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON again.
At the end of the data transfer phase the instrument displays the following messages: “end “ for right programming. “err“ for failed programming – In this case push “SET” key if you want to restart the programming again or remove the not programmed “Hot key”.
What do I do if the EE alarm appears?
To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is displayed for about 3s.
How do I silence the buzzer or alarm relay output?
If “tbA = y”, once the alarm signal is detected the buzzer and the relay are is silenced by pressing any key. If “tbA = n”, only the buzzer is silenced while the alarm relay is on until the alarm condition recovers.
How do I recover from probe alarms?
Probe alarms (“P1” (probe1 faulty), “P2” and “P3”) automatically stop 10s after the probe restarts normal operation. Check connections before replacing the probe.
How do I recover from temperature alarms?
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts.
How do I recover from a door switch alarm?
Door switch alarm “dA” stop as soon as the door is closed.
How do I recover from external alarms?
External alarms “EAL”, “bAL” stop as soon as the external digital input is disabled “PAL” alarm is recovered by switching OFF the instrument.